Ablerex Power Master User Manual

June 9, 2024
Ablerex

Ablerex Power Master

The information presented in this manual is not warranted by Ablerex to be authoritative, error-free,or complete. Ablerex assumes no liability for damages, violations of codes, improper installation, system failures, or any other problems that could arise based on the use of this publication.
Ablerex reserves the right to make changes or updates with respect to or in the content of the publication or the format thereof at any time without notice.
Copyright, intellectual, and all other proprietary rights in the content (including but not limited to software, audio, video, text, and photographs) rests with Ablerex or its licensors. All rights in the content not expressly granted herein are reserved.
No rights of any kind are licensed or assigned or shall otherwise pass to persons accessing this information.

Installation Instructions

The free software is available for all single-phase UPS models and downloadable from www.ablerex.eu/download

System requirements

Support OS:

O.S| x86/x64| Version
Ubuntu| x64| 14.04.6/16.04/18.04/20.04/21.1
Ubuntu| x86| 16.04.6
Debian| x64| 9/10
Debian| x86| 9
Mint| x64| 20.3
SUSE Linux Enterprise| x64| 12/15
Red Hat Enterprise| x64| 8
CentOS| x64| 8
Deepin| x64| 23
Peripherals: Com Port(RS-232) or USB

Install Ablerex PowerMaster

Install Ablerex PowerMaster

  • Step 1. Input command: chmod +x powermaster.bin
  • Step 2. Input command: sudo ./powermaster.bin
  • Step 3. Install Complete

Ablerex Power Master-fig2

  • Step 5. Click “Next” to next step

Ablerex Power Master-fig3

Uninstall Ablerex PowerMaster
  • Step 1. Input command: sudo sh /usr/local/powermaster/uninstall
  • Step 2. Uninstall Complete.

Ablerex Power Master-fig4

Main Menu

Ablerex Power Master-fig5

Press “Up” or “Down” key and then press “Enter”Key to into each function. The following chapters introduce each function.

Monitoring UPS Information

Ablerex Power Master-fig6

The function will be divided into four blocks.

  • Shutdown Info
    That will be shown the shutdown time of UPS or OS when UPS has events occurs (e.g., Power Failed).

  • Status Data
    The real-time information for UPS e.g., Input Voltage, Output Voltage, Frequency…etc.

  • UPS Status
    The real-time status for UPS e.g., Power status, Battery Low…etc.

  • UPS Information
    The rating and information for UPS e.g., Rating Voltage/Current, Manufacturer, UPS Model…etc.

Shutdown Info

Function Function Describe Remark
Next OS Shutdown That will be shown the shutdown time of UPS or OS when UPS
has events occurs.
Next UPS Shutdown

Status Data

Function Function Describe Remark
Input Voltage UPS Input Voltage
Output Voltage UPS Output Voltage
Output Current UPS Output Current
Function Function Describe Remark
--- --- ---
Input Frequency UPS Input Frequency
UPS Type UPS Type (e.g. On-Line/Off-Line)
Battery Capacity Battery capacity of UPS
Battery Life Battery Life of UPS Battery Life Function need to Enable on

configure menu.
Autonomy time| Autonomy time of UPS| Autonomy time Function need to Enable on configure menu.
Battery Voltage| Battery Voltage of UPS.| Additional Function need to Enable on configure menu.
Load| Load percentage of UPS.|
Load(W)| Output Active power of UPS| ****

Additional Function need to Enable on configure menu.

Load(VA)| Output Apparent Power of UPS
Temperature °C| Temperature of UPS(Celsius)|
Temperature °F| Temperature of UPS(Fahrenheit)|

UPS Status

Function Function Describe Remark
Power Status Input utility normal or not
Battery Low Battery Low normal or not
Bypass Bypass mode status
AVR UPS Boost/trim status
Battery Status Battery damage/ Disconnection or not
UPS Type UPS type (On-Line/Off-Line)
Test in Progress Under test in Progress or not
Shutdown UPS shutdown status
Beeper UPS beeper status
Link Status UPS communication status

UPS Information

Function Function Describe Remark
Rating Voltage UPS Rating Voltage
Rating Current UPS Rating Current
Rating Battery Voltage UPS Rating Battery Voltage
Rating Frequency UPS Rating Frequency
Manufacturer Manufacturer information
UPS Model UPS Model information
Firmware Version UPS Firmware information

Control

Ablerex Power Master-fig7

Command UPS directly for the following test

  • UPS Self-Test
  • UPS Test to Battery Low
  • Cancel UPS Self-Test
  • UPS & OS Shutdown Test
  • Cancel UPS & OS Shutdown Test

Please follow the below procedure to do.

  • Step 1.Select which UPS to be tested
  • Step 2. Select which command to be sent
  • Step 3.Press “Confirm” to send command

Email Configuration

Ablerex Power Master-fig8

Configure to send the event message (e.g., AC Power Fail) to specific one by email. The following section is for the detail configuration approach.

Function Function Describe
User Name Sender
User email Address select a sender email
Password Password of your email server
SMTP Server SMTP server or IP address
SMTP Server Port SMTP Server port
Receiver Name name of receiver
Mail To Mail address of receiver

If you want to send an email to more than 1 email address, you must use “,” to separate email addresses.

Subject| Subject of email
TLS ENCRYPTION| Enable TLS encryption or not
When it is Enable, it can be sent by E-mail if detects an abnormality event in the UPS
Function| Function Describe
---|---
Communication Established| UPS Communication Established
Communication Lost| UPS Communication disconnection
OS Shutdown Started| Operating OS will start shutdown
Power Failed| Input utility abnormal
Low Battery| UPS Battery Low
Power Restored| Input utility normal
UPS Shutdown Started| UPS will start shutdown
Over Load| UPS over loading
UPS Fail/Battery Disconnect| Battery damage or Disconnection
UPS Self Testing| UPS test in Progress

After setting, you can press “Email Test” to confirm that have received test mail or not. If received, press “OK” to save

Schedules

Ablerex Power Master-fig9

PowerMaster supports the scheduling self test, turn-off function for UPS. The following section is for the detail configuration approach.
Add Schedules:
Press” I” key to add new schedule.

Ablerex Power Master-fig10

Function Function Describe
UPS Name Select which UPS to be tested
Control Select which command of schedule UPS Self-Test 10 Second

Self Test (1-99)Minutes(The test time can be define by the user)

UPS Self-Test Until Battery Capacity

UPS Self Test Until Low Battery Condition

Shutdown Operating System and UPS, then Turn on UPS Shutdown Operating System and UPS

Frequency| Set execute cycle of the schedule
Date Time| Date and time for schedule setting

Edit Schedules:
Use “UP” and Down” key to select the schedule you want to modify and press “Enter” key to modify task.

Ablerex Power Master-fig11

Event Log

Ablerex Power Master-fig12

The event log can be read directly via PowerMaster or export to an file with txt format for application. The following chapter is for the detail operation.

Function Function Describe
Date Select which date to be view
UPS Name Select which UPS to be view
Filter Select which Event to be view
Update For data refreshing
Export Export data save to below folder:

/usr/local/powermaster/UPS/

< , >| Select Previous/Next page
<< , >>| Select First/Last page

Data Log

Ablerex Power Master-fig13

Set the file to be executed before the system shutdown. The selectable time is from 0 min. to 20 min.

Function Function Describe
Date Select which date to be view
UPS Name Select which UPS to be view
Additional Data Press” Additional Data” to see additional data of UPS.

Additional Function need to Enable on configure menu.

Update| For data refreshing
Export| Export data save to below folder

/usr/local/powermaster/UPS/

< , >| Select Previous/Next page
<< , >>| Select First/Last page

General Settings

Ablerex Power Master-fig14

Allows user to select and set to Data Log function and set to turn of UPS or OS condition etc.

Shutdown Setting Block

Function| Function Describe
OS Shutdown When Power Failure| Set the O.S shutdown operation after Power Failure
OS Shutdown When Battery Low| Set the O.S shutdown operation after Battery Low
OS Shutdown When Battery Low than Cap.| Set the O.S shutdown operation after Battery Low than Cap.

OS Shutdown Type

| O.S shutdown options

1. Shutdown

2. NonShutdown

3. Hibernate

When Power Failure, OS Shutdown Buffer Time| Set the Buffer Time for O.S shutdown operation after Power Failure
When Battery Low, OS Shutdown Buffer Time| Set the Buffer Time for O.S shutdown operation after Battery Low

When Battery Capacity is less or equal

| Set the Buffer Time for O.S shutdown operation after Battery Capacity is less or equal
-OS Shutdown Buffer Time|  
---|---

When Utility Recovered

| When utility Recovered

O.S system can be set to: OS Continues Shutdown OS Cancels Shutdown UPS can be set to:

Turn off UPS None

UPS Output Shutdown Delay After the Buffer Time| Set time interval from Windows shut- down to UPS turn-off
Data Record Settings Block
Function| Function Describe
Record Interval (Per Secs)| Set Record timer interval

Day of data retention(days)

| Set data storage retention(days) of the record list.

The data base will be not deleted if set to 0

Additional Settings Block
Function| Function Describe

Additional Function

| PowerMaster will collect additional data(e.g., Output Current, Battery Volta- ge…etc.) from UPS ,if Enable Additional function

Please check with your distributor to see if UPS has support

Autonomy Time Function

| PowerMaster will collect Autonomy Time information, if Enable Autonomy Time function

Please check with your distributor to see if UPS has support

Battery Life Function

| PowerMaster will collect Battery Life in- formation, if Enable Battery Life function Please check with your distributor to see if UPS has support
Export Setting| Export Setting save to below folder /usr/ local/powermaster/UPS/
Import Setting| Select the Setting file which you want and Import the Settings to PowerMaster

Communication Settings

Ablerex Power Master-fig15

Allows user to select and set the connecting RS-232/USB or Remote etc.

Function Function Describe
Protocol Standard:

Communicate with UPS via Com Port/USB Remote:

The “ Remote “ is for connecting the PowerMaster, which installed on another computer, and the IP address should be the master PC, which connected UPS.

Connect IP| Please refer to above describe
Com Port| Setting Serial port path (e.g.: /dev/ttyXRUSB0)
Communication Interface| Select which Interface of UPS to be communicated
Total unit of UPS| Setting amount of unit
Baud Rate| Setting Baud Rate of UPS
UPS #1| Setting UPS name

About

Ablerex Power Master-fig16

It displays copyright and version information of PowerMaster.

Ablerex Electronics Italy srl
Viale Milanofiori
Strada 6 · Palazzo N1
20089 Rozzano (MI)
[email protected]
Tel. +39 02 36696420
www.ablerex.eu

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Ablerex User Manuals

Related Manuals