GARO G4-63C 63 Amp Type C Main Overcurrent Device Instructions

June 5, 2024
GARO

G4-63C 63 Amp Type C Main Overcurrent Device
Instruction Manual

|
---|---

Technical data Circuit Breaker

Rated voltage 230V, 230/400V, 400V, 60VDC
Rated current C:63A,
Rated frequency 50/60Hz
Shock resistance 30g.min. 2 shocks, t = 13ms
Rated short-circuit capacity 10 kA
Energy limiting class 3; B,C
Tripping characteristic C
Back-up fuse 100A gG
Index of protection IP 20 (IP 40)
Terminals 1-25mm2, max 2.5Nm
Mechanical endurance 20000 op.c.
Electrical endurance 20000 op.c. (InS32A), 10000 op.c. (In>32A)
Ambient temperature max. -25°C … +55°C
Storage temperature max. -40°C … +70°C
Build-in width 18 mm/pol
Insulating class B
Overvoltage category III
Mounting on the rail EN 60715
Sealing possibility YES
Terminal cover & Lock device Available
Standards EN 60898, IEC 60898, EN 60947-2

Technical Data Enclosure

• Degree of Protection: IP65
• Resistance to Impact: IK08
• Auto-extinguishing degree: HB (UL94)
• Test of resistance to glow wire: 650° C
• Ball Pressure Test: 70° C

The enclosure does not have
N+E terminals

Supplier established within EU/Ombud etablerad in EG
Supplier of equipment /Materielslag: Consumer unit/Normcentral
Trade Mark/ Varumärke: GARO
Type Designation / Typbeteckning: G… , GX…, GM…, K…, NUM … , NIM … , NUM.GM …, NUM.GT …, NUM.L …, NEM .. , NCI…, NCID …, NCU …, NCUP … CDN…  and / och GCUT
We hereby declare that our product fulfills the requirements of following EC directives

The Low Voltage Directive (LVD) 2014/35/EU.
Electromagnetic compatibility (EMC) 2004/108/EU.
RoHS Directive (RoHS) 2011/65/EU.
No electromagnetic compatibility (EMC) immunity or emission tests are required on the assembly.
The following harmonized standards (latest edition) or technical specifications which comply with good engineering practice in safety matters in force within the EU have been used in the design:
The equipment conforms completely with the above-stated harmonized standards or technical specifications.

Or/Eller
The equipment confirms only partially with the above-stated harmonized standards or technical specifications but complies with good practice in safety matters in force within the EU.
We have product surveillance according to CENELEC’s harmonized requirements, and documents CCA-201. GARO G4-63C 63 Amp Type C Main Overcurrent Device -