Ablerex ESP 400, ESP 600 Active Power Filters Instruction Manual

June 12, 2024
Ablerex

Ablerex ESP 400, ESP 600 Active Power Filters Instruction Manual

Ablerex ESP 400, ESP 600 Active Power Filters Instruction
Manual

Features

  • Hot-swappable power modules that are easy to install make the architecture highly scalable.
  • Their modularity, high current rating and the option of connecting them in parallel up to 2400A makes them versatile.
  • ESP is available in two versions, 4 or 6 modules for 60A, 80A or 100A, which can also be used in a mixed configuration within the same system.
  • Maximum performance with 3-level DSP technology.
  • Their compact, high-power-density design optimises space.
  • Multi-purpose: one model covers all three-phase systems (3-wire or 4-wire).
  • Correction of all harmonics (up to the 51st) with a response time of less than 1 ms.
  • No overload effect.
  • Selective mode to select the harmonics to be corrected.
  • Phase balancing of three-phase loads.
  • Open loop or closed loop installation.
  • A single control module manages up to 8 power modules.
  • All parameters are under control via the 7” colour touch screen display that shows: voltage and current waveforms, frequency spectrum, parameters and events.
  • Events and parameters can be downloaded to a removable SD card.
  • Advanced communication: dry contacts (3 in and 1 out), USB, RS485 Modbus, RJ45 Ethernet, programmable email alarm.
  • Multiple languages can be selected.

Open/closed loop control External CT xxxx/1 xxxx/5
Ablerex ESP 400, ESP 600 Active Power Filters Instruction
Manual
Closed Loop Control

External CT xxxx/1 xxxx/5
Ablerex ESP 400, ESP 600 Active Power Filters Instruction
Manual
Open Loop Control

User-friendly user interface
The 7” colour touch screen display can be used to set all parameters, read the event log file and download data to a removable SD card.
It can also show the voltage and current waveforms, before and after enabling the ESP, along with a frequency spectrum bar graph.
Ablerex ESP 400, ESP 600 Active Power Filters Instruction
Manual

Harmonic and PF correction that can be verified on the display
ESP not only actively corrects harmonic currents up to the 51st order, but also improves the inductive or capacitive power factor with a response time of less than 1 ms. The benefits can be seen easily on the display.
Ablerex ESP 400, ESP 600 Active Power Filters Instruction
Manual
Before
THDi%=30%,PF=0.81
Ablerex ESP 400, ESP 600 Active Power Filters Instruction
Manual
After
THDi%=4.3%,PF=1.0

ESP active filters with a modular structure can correct any type of harmonic contamination to protect the system from faults (e.g. on transformers, capacitors, etc.), BNwhile also improving the power factor.

MODEL ESP 400 ESP 600
SIZE (A) 400 600
POWER MODULE (A) 60-80-100
ELECTRICAL SPECIFICATIONS Rated voltage 400 V +15%, -20%; 480V +10%, -20%
Phases Three-phase
Frequency 50/60 ±3 Hz
Harmonic correction From the 2nd to the 51st
Power factor correction Capacitive and inductive (selectable)
Load balancing Between two phases and between phase and neutral
Response time 25 µs
ENVIRONMENTAL PARAMETERS Operating temperature -10°C to +40°C with no

derating
Relative humidity| <95%
Altitude (a.s.l.)| <1000 m with no derating, >1000 m with 1% derating for every 100 m
Audible noise at 1 m.| <63 dBA
GENERAL| Dimensions (WxDxH) mm| 600x900x1500| 600x900x1950
Weight (kg)*| 150| 196
Protection class| IP21
Connections| 4-wire/3-wire
Installation| Floor standing
Type| Modular
Parallel connection up to (A)| 2400
Max. no. of modules per system (60 or 80 A in a mixed configuration)| Up to 4| Up to 6
Max. parallel systems| 6| 4
TA configuration| Source side TA: closed loop control – load side TA: open loop control
CONNECTIVITY| Built-in communication ports| USB, RS-485 ModBus RTU, EPO Ethernet port and dry contact relays (1 in/3 out)
User interface| 7’’ colour LCD touch screen display
Software| Data monitoring and storage software
REGULATIONS| Standards| EN61000-3-4, IEEE 519-1992, EN60146, EN50178; UL508, EN61000-6-4, EN55011, CISPR 11, IEC 61000-3-12, IEC 61000-3-11,IEC 61000-6-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4,IEC 62477-1, IEC 61000-4-5, IEC 61000-4-6,EN 61000-4-8, EN61000-4-34
Marking| CE, UKCA

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>