E E ELEKTRONIK EE820 CO2 Sensor User Manual
- June 9, 2024
- E E ELEKTRONIK
Table of Contents
YOUR PARTNER IN SENSOR TECHNOLOGY
User Manual
EE820 – CO₂ Sensor for Demanding Applications
Find this document and further product information on our website at
www.epluse.com/ee820.
SCOPE OF SUPPLY
- EE820 Sensor according to ordering guide
- Mounting set (screws and rowl plugs / screw anchors)
- Cable gland (only for EE820-HVxxxE1xxx with cable gland)
- M12x1 cable connector for self assembly (only for option AC2)
- Test report according to DIN EN 10204-2.2
ACCESSORIES / SPARE PARTS
ACCESSORIES (see datasheet “Accessories”): USB configuration adapter
Product configuration software
EE820-FAC Forced air circulation module, without cover
M12x1 cable connector for self assembly
Connection cable M12x1 socket – flying leads
• 1.5 m (3.3 ft)
• 5 m (16.4 ft)
• 10 m (32.8 ft)
Protective cap for female M12 connectors
Protective cap for male M12 connectors
Power supply adapter| HA011066
EE-PCS (free download: www.epluse.com/ee820)
HA011302
HA010707
HA010819
HA010820
HA010821
HA010781
HA010782
V03
---|---
SPARE PARTS:
EE820-COVER Cover complete with filter and mounting screw (HA011303)
CAUTION
- The sensor shall not be exposed to extreme mechanical or thermal stress.
- For use in polluted, dirty environment is essential to close tightly the sensor cover as well as the cable glad or conduit adapter in order to avoid pollution ingress into the enclosure.
- This device is not appropriate for safety, emergency stop or other critical applications where device malfunction or failure could cause injury to human beings.
DIMENSIONS
VALUES IN MM / INCH
EE820 with M12 plug does not require any wiring inside the device. The
external mounting holes allow the device to be mounted without opening the
front cover. The mating M12x1 cable plug for self assembly is included in the
scope of supply. Please see EE820 data sheet for optional M12 plugs and
cables.
EE820 with cable gland: Use a matching wrench to install the cable gland (in
the scope of supply) onto the EE820 enclosure.
EE820 with conduit connection for the North American market: use a flat
screwdriver to knock open the blind, carefully, in order to avoid damaging the
electronics inside the enclosure. The conduit adapter is not included in the
scope of supply. The M16x1.5 opening for the cable gland shall be tightly
closed using the blind plug included in the scope of supply.
ELECTRICAL CONNECTION
Important note:
The manufacturer cannot be held responsible for personal injuries or damage to
property as a result of incorrect handling, installation, wiring, power supply
and maintenance of the device.
EE820 WITH M12 PLUG ¹)
EE820 WITH CABLE GLAND
- M12x1cable connector for self assembly is included in the scope of supply
- Very important: for failure-free operation and performance according to the specs the supply GND and the measurement GND must be wired separately.
TECHNICAL DATA
Measurands
Measurement principle| Dual wavelength non-dispersive infrared technology
(NDIR)
---|---
Measuring range| 0…2 000 / 5 000 / 10 000 ppm
Accuracy at 25 °C (77 °F)
and 1 013 mbar (14.7 psi)| 0…2 000 ppm: < ± (50 ppm +2 % of mv) mv = measured
value
0…5 000 ppm: < ± (50 ppm +3 % of mv)
0…10 000 ppm: < ± (100 ppm +5 % of mv)
Response time t63, typ.| 300 s
Temperature dependency, typ.| ± (1 + CO2 concentration [ppm] / 1 000) ppm/°C
(-20…45 °C) (-4…113 °F)
Sample rate| Approx. 15 s
Output
Analogue
0…2 000 / 5 000 / 10 000 ppm| 0 – 10 V
4 – 20 mA| -1mA < IL < 1 mA
RL < 500 Ω| RL= load resistance
---|---|---|---
General
Power supply class 1)| 24 V AC ±20%
15 – 35 V DC
---|---
Current consumption, typ.| 15 mA + output current
Current peak, max.| 350 mA for 0.3 s (analogue output)
Warm up time2)| < 5 min
Enclosure material| Polycarbonate, UL94 V-0 approved
Protection rating| IP54
---|---
Electrical connection| Screw terminals 2.5 mm² or M12 plug
Electromagnetic compatibility| EN 61326-1 EN 61326-2-3 Industrial Environment
FCC Part 15 ICES-003 Class B
Working conditions| -20…60 °C (-4…140 °F) 0…100 %RH (non-condensing)
Storage conditions| -20…60 °C (-4…140 °F) 0…95 %RH (non-condensing)
- USA & Canada class 2 supply required, max. supply voltage 30 V DC
- For performance according to specification
SETUP AND ADJUSTMENT
The EE820 is ready to use and does not require any configuration by the user.
The factory setup of EE820 corresponds to the type number ordered. For
ordering guide please see data sheet at
www.epluse.com/ee820.
If needed, the user can change the factory setup by using the optional USB
Configuration Adapter (HA011066) and the Product Configuration Software EE-PCS
(available for free download at
www.epluse.com/configurator). One can
change CO2 output signal, scaling of the outputs, digital settings and perform
CO2 adjustment / calibration.
Note: The EE820 must not be connected to any additional power supply when
using the USB Configuration Adapter (HA011066).
CHANGING THE ANALOGUE OUTPUT SIGNAL:
The output signal can be changed from voltage to current or vice versa. Set
the output signal selection switch to I for current 4 – 20 mA output or to U
for voltage 0 – 10 V output. The original CO2 output range does not change and
the calibration data remains valid.
Example:
Factory setup: voltage output (U), output scale: 0 – 10 V = 0 – 5 000 ppm
User setup (after setting the output signal selection switch to I): current
output (I), output scale: 4 – 20 mA = 0 – 5 000 ppm.
CHANGING THE OUTPUT SCALE:
The scaling of the output can be changed by using the USB Configuration
Adapter (HA011066) and EE-PCS.
Example:
The initial scaling of the output is 4 – 20 mA = 0 – 5 000 ppm.
The output scale after the change can be 4 – 20 mA = 400 – 4 000 ppm.
Important:
- After changing the factory setup (output signal and / or output scale) the original type number on the EE820 identification label loses its validity; it does not match any longer the device setup.
- The return to factory setup function of EE-PCS restores the original adjustment/calibration of the device, but does not affect the user setup for output signal and output scale.
MAINTENANCE
Even in case of use in dirty and dusty environment, the electronics of EE820
are very well protected by the enclosure and the filter on the front cover. Do
not attempt in any way to clean the inside of the device.
In case of dirt deposits on the exterior of the device, this can be cleaned by
weeping it gently with a soft, light wet cloth. The enclosure must be closed
during the cleaning. Do not use solvent-based cleaning agents; these might
affect the enclosure and the labels. Do not attempt to clean the filter on the
front cover, as it would only lead to its faster clogging.
In a polluted environment, the filter on the EE820 front cover might get
clogged in a long run. Longer response time indicates a clogged filter. In
such case the entire front cover shall be replaced by an original new one (see
section Spare Parts).
Protection filters caps for M12 connector are available to preserve the
contacts of plug / socket in case of temporary removing of sensor (see section
accessories / spare parts).
USA
FCC notice:
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
installation manual, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to
which thereceiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
CANADIAN
ICES-003 Issue 5:
CAN ICES-3 B / NMB-3 B
INFORMATION
+43 7235 605 0 / info@epluse.com
Langwiesen 7 • 4209 Engerwitzdorf • Austria
Tel: +43 7235 605-0 • Fax: +43 7235 605-8
info@epluse.com •
www.epluse.com
LG Linz Fn 165761 t • VAT No. ATU44043101
Place of Jurisdiction: 4020 Linz • DVR0962759
BA_EE820 // v1.6 // Modification rights reserved
References
- Sensor Technology: Humidity, CO2, Flow & Temperature Measurement
- CO2 sensor for demanding applications