E E ELEKTRONIK EE850 CO2 Humidity and Temperature Duct Mount Sensor User Manual
- June 9, 2024
- E E ELEKTRONIK
Table of Contents
YOUR PARTNER IN SENSOR TECHNOLOGY
EE850 CO2 , Humidity and Temperature
Duct Mount Sensor
User Manual
EE850 CO2 Humidity and Temperature Duct Mount Sensor
E+E Elektronik Ges.m.b.H. does not accept warranty and liability claims
neither upon this publication nor in case of improper treatment of the
described products.
The document may contain technical inaccuracies and typographical errors. The
content will be revised on a regular basis. These changes will be implemented
in later versions. The described products can be improved and changed at any
time without prior notice.
© Copyright E+E Elektronik Ges.m.b.H.
All rights reserved.
EMC note USA (FCC):
This equipment has been tested and found to comply with the limits for a Class
A digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
EMC note Canada (ICES-003):
CAN ICES-3 (A) / NMB-3 (A)
General
This user manual serves for ensuring proper handling and optimal functioning
of the device. The user manual shall be read before commissioning the
equipment and it shall be provided to all staff involved in transport,
installation, operation, maintenance and repair. The user manual may not be
used for the purposes of competition without the written consent of E+E
Elektronik® and may not be forwarded to third parties. Copies may be made for
internal purposes. All information, technical data and diagrams included in
these instructions are based on the information available at the time of
writing.
Please find this document and further product information on our website at
www.epluse.com/ee850
Disclaimer
The manufacturer or his authorized agent can be only be held liable in case of
willful or gross negligence. In any case, the scope of liability is limited to
the corresponding amount of the order issued to the manufacturer. The
manufacturer assumes no liability for damages incurred due to failure to
comply with the applicable regulations, operating instructions or the
specified operating conditions. Consequential damages are excluded from the
liability.
1.1 Explanation of Symbols
This symbol indicates safety instructions.
The safety instructions have to be carried out unconditionally. If
disregarded, loss, injury, or damage may be inflicted to people or property.
In any case E+E Elektronik® Ges.m.b.H. cannot be hold responsible.
This symbol indicates attention.
The note should be observed to achieve an optimum and safe operation of the
equipment.
1.2 Safety Instructions
1.2.1 General Safety Instructions
- Avoid any unnecessary mechanical stress and inappropriate use.
- The device shall not be exposed to extreme thermal stress.
- Installation, electrical connection, maintenance and commissioning shall be performed by qualified personnel only.
Please note:
The EE850 is not appropriate for safety, emergency stop or other critical
applications where device malfunction or failure could cause injury to humans
and other living beings.
1.2.2 Intended Use
The EE850 is intended for CO2, humidity (RH) and temperature (T) measurement
in ducts. Its typical application is in demand controlled ventilation and
building automation. Due to its wide measuring ranges and its insensitiveness
to pollution, the EE850 can be employed in demanding climate and process
control as well.
The sensor is available with two different probe lengths and analogue and
digital outputs. The analogue outputs can be current or voltage outputs and
provide the measured alues as well as the calculated value for the dew point
temperature (Td). The RS485 interface with Modbus RTU or BACnet MS/TP protocol
also supplies other calculated parameters such as absolute humidity (dv),
mixing ratio (r), water vapour partial pressure (e) or enthalpy (h).
The use of the EE850 in any other way than described in this manual bears a
safety risk for people and the entire measurement installation and is
therefore not allowed. The manufacturer cannot be hold responsible for damages
as a result of incorrect handling, installation, and maintenance of the
equipment.
In order to avoid damage to the instrument or health hazards, the measuring
equipment must never be manipulated with tools that are not specifically
described in this manual.
The sensor may only be utilized in accordance with the conditions defined in
the technical data. Otherwise, measurement inaccuracies will occur and
equipment failures cannot be ruled out.
The steps recommended by the manufacturer for installation, inspections and
maintenance work must be observed and carried out for the safety of the user
and for the functionality of the equipment.
Unauthorized product modification leads to loss of all warranty claims. This
may be accomplished only with an explicit permission of E+E Elektronik®
1.2.3 Installation, Start-up and Operation
The EE850 duct sensor has been designed and produced under state of the art
manufacturing conditions, has been thoroughly tested and has left the factory
after fulfilling all safety criteria. The manufacturer has taken all actions
to assure safe operation. The user has to make sure that the equipment is
positioned and installed in such a way that safe operation is not impaired.
The user is responsible for observing all applicable safety guidelines, local
and international, with respect to safe installation and operation on the
device.
This manual contains information and notes of caution, which have to be
followed by the user to assure safe operation.
- Mounting, electrical installation, putting into operation and maintenance may be performed by qualified personnel only. Such staff must be authorized by the operator of the facility to carry out the mentioned activities.
- The qualified staff must have read and understood this manual and must follow the instructions contained within.
- All process and electrical connections shall be thoroughly checked by authorized staff before putting the device into operation.
- Do not put damaged products into operation and protect them from accidental commissioning. Mark the damaged product as defective.
- A faulty device may only be investigated and possibly repaired by qualified, trained and authorized staff. If the fault cannot be fixed, the device shall be removed from the process.
- Service operations other than described in this user manual may only be performed by the manufacturer.
1.3 Environmental Aspects
Products from E+E Elektronik® are developed and designed due to consideration
of the importance of environmental protection. Therefore, disposal of the
product also should not lead to pollution of the environment.
**** Single-variety components must be separated before the transmitter is
disposed of. The electronic components must be collected and as electronic
scrap properly disposed of.
Scope of Supply
- EE850 sensor according ordering guide
- Cable gland
- Mounting flange + seal
- Mounting material
- Two self-adhesive labels for configuration changes (see user guide at www.epluse.com/relabeling)
- Test report according to DIN EN10204-2.2
- Quick guide
Product Description
3.1 General
Installed into a duct, a small amount of air flows through the divided probe
into the EE850 enclosure, where the CO2 sensing cell is located, and back into
the duct. The RH and T sensing elements are placed inside the probe.
Very important
For accurate measurement the cover of EE850 as well as the cable outlet –
cable gland or conduit adapter – must be closed tightly. This is essential for
avoiding ingress of air other than from the duct into the EE850 enclosure,
which would falsify the measurement.
Please note: The direction of air flow in the duct shall correspond to
the direction indicated with arrows on the EE850 cover. Depending on the EE850
version, the response time specified is only valid for direction marked with
the blue arrow with respect to the cable gland position. Air flow in the
opposite direction might lead to longer response time.
3.2 Installation
All values in mm / inch
EE850 with conduit connection for the North American market: use a flat
screwdriver to carefully break open the plastic knockout at the marked
location, in order to avoid damaging the electronics inside the enclosure.
The conduit adapter is not included in the scope of supply.
3.3 Electrical Connection
3.4 Setup and Adjustment
The EE850 is ready to use and does not require any configuration by the user.
The factory setup of EE850 corresponds to the type number ordered. For
ordering guide please see data sheet at
www.epluse.com/ee850.
If needed, the user can change the factory setup by using the optional USB
Configuration Adapter (HA011066) and the Product Configuration Software (EE-
PCS). One can change the CO2 output signal, the scaling of the outputs and
perform CO2, RH and T adjustment/calibration.
Please note: The EE850 may not be connected to any additional power supply
when using the USB Configuration Adapter (HA011066).
MODEL EE850-M10:
Select the CO2 output signal:
The output signal can be changed from voltage to current or vice-versa. Set
the output signal selection switch to I for current 4 – 20 mA output or to U
for voltage 0 – 10 V output. The original CO2 output range does not change and
the calibration data remains valid.
Example:
Factory setup: voltage output (U), output scale: 0 – 10 V = 0…10 000 ppm User
setup (after setting the output signal selection switch to I): current output
(I), output scale: 4 – 20 mA = 0…10 000 ppm.
MODELS EE850-M11 and EE850-M12:
Changing the CO2 and T output scale:
The scaling of the output can be changed by using USB Configuration Adapter
(HA011066) and Product Configuration Software (EE-PCS).
Example:
The initial scaling of the outputs is:| The output scale after the
change is:
---|---
CO2: 0 – 10 V = 0…10 000 ppm T:| CO2: 0 – 10 V = 400…8 000 ppm
0 – 10 V = 0…50 °C| T: 0 – 10 V = 40…100 °F
RH: 0 – 10 V = 0…100 %RH| Td: 0 – 10 V = -20…40 °C
Please note:
- After changing the factory setup (output signal and/or output scale) the original type number on the EE850 identification label loses its validity; it does not match any longer the device setup.
- The return to factory setup function of EE-PCS restores the original adjustment/calibration of the device, but does not affect the user setup for output signal and output scale.
The Product Configuration Software (EE-PCS) is available for free download at
www.epluse.com/configurator.
3.5 Digital Settings
3.5.1 Bus Termination Resistor
Hardware:
The bus termination shall be realized with the 120 Ω resistor (slide switch on
the board).
Very important:
For proper function the power supply must be strong enough to ensure supply
voltage within the specified range (see technical data) at any time and at all
devices in the bus. This is particularly relevant when using long and thin
cables which can cause high voltage drop. Please note that a single EE850
requires peak current of 350 mA.
3.5.2 Modbus Address Setting
Address setting via EE-PCS
Product Configuration Software:
All DIP switches at position 0 → address has to be set via PCS
Modbus (Slave device): factory setting EE850: 67 (permitted values: 1…247).
BACnet (Master device): factory setting EE850: 67 (permitted values: 0…127).
Example: Modbus address is set via configuration software.
Address setting via DIP
switch:
Modbus (Slave device): Setting the DIP switches to any other address than 0,
overrules the Modbus address set via configuration software (permitted values:
1…247).
BACnet (Master device): Setting the DIP switches to any other address than 0,
overrules the Modbus address set via configuration software.
BACnet Note: permitted values are 0…127.
The 8th bit of the DIP switches is ignored (Modbus adress 127 = 0111 111).
To set address 0 via DIP switches, the 8th bit shall be set to 1 (Modbus
adress 0 = 1000 0000).
Example: Modbus address set to 11 (= 0000 1011 binary).
3.5.3 BACnet Setup
Please see PICS (Product Implementation Conformance Statement) – available at
www.epluse.com/ee850.
3.5.4 Modbus Setup
Item | Factory settings | Selectable values (via EE-PCS) |
---|---|---|
Baud rate | 9 600 | 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 |
Data bits | 8 | 8 |
Parity | Even | None, odd, even |
Stop bits | 1 | 1, 2 |
Modbus address | 67 | 1…247 |
Tab. 1 Digital interface default settings
The recommended settings for multiple devices in a Modbus RTU network are
9600, 8, even, 1.
The EE850 represents 1/10 unit load on an RS485 network.
Device address, baud rate, parity and stop bits can be set via:
-
EE-PCS Product Configuration Software and the Modbus configuration adapter HA011066.
The EE-PCS can be downloaded free of charge from www.epluse.com/configurator -
Modbus protocol in the register 60001 (0x00) and 60002 (0x01).
See Modbus Application Note AN0103 (available on www.epluse.com/ee850)
The serial number as ASCII code is located in the register addresses 0x00…0x07
(16 bits per address).
The firmware version is located in the register address 0x08 (bits 15…8 =
major release; bits 7…0 = minor release). The beforementioned registers can be
read out with function code 0x03 or 0x04.
The measured data is saved as 32 bit floating point values (data type FLOAT)
and as 16 bit signed integer values (data type INTEGER).
FLOAT 32 bit
Parameter| Unit| Register number 1) [DEC]| Register address
2) [HEX]
Read register: function code 0x03
Temperature T| ° C| 1003| 0x3EA
° F| 1005| 0x3EC
Relative Humidity| %| 1021| 0x3FC
CO2 (average)| ppm| 1061| 0x424
CO2 (raw)| ppm| 1063| 0x426
Water vapour partial pressure| mbar| 1101| 0x44C
psi| 1103| 0x44E
Dew point temperature| °C| 1105| 0x450
°F| 1107| 0x452
Absolute humidity| g/m3| 1113| 0x458
gr/ft3| 1115| 0x45A
Mixing ratio| g/kg| 1121| 0x460
gr/lb| 1123| 0x462
Specific enthalpy| kJ/kg| 1125| 0x464
ft lb/lb| 1127| 0x466
BTU/lb| 1129| 0x468
Frost point temperature| °C| 1131| 0x46A
°F| 1133| 0x46C
- Register number starts from 1
- Register address starts from 0
INTEGER 16 bit
Parameter| Unit| Scale 3)| Register number 1) [DEC]|
Register address 2) [HEX]
Read register: function code 0x03
Temperature T| ° C| 100| 4002| 0xFA1
° F| 50| 4003| 0xFA2
Relative Humidity| %| 100| 4011| 0xFAA
CO2 (average)| ppm| 1| 4031| 0xFBE
CO2 (raw)| ppm| 1| 4032| 0xFBF
Water vapour partial pressure| mbar| 10| 4051| 0xFD2
| psi| 1000| 4052| 0xFD3
Dew point temperature| °C| 100| 4053| 0xFD4
| °F| 100| 4054| 0xFD5
Absolute humidity| g/m3| 10| 4057| 0xFD8
| gr/ft3| 10| 4058| 0xFD9
Mixing ratio| g/kg| 10| 4061| 0xFDC
| gr/lb| 10| 4062| 0xFDD
Specific enthalpy| kJ/kg| 1| 4063| 0xFDE
| ft lb/lb| 1| 4064| 0xFDF
| BTU/lb| 1| 4065| 0xFE0
Frost point temperature| °C| 100| 4066| 0xFE1
| °F| 100| 4067| 0xFE2
- Register number starts from 1
- Register address starts from 0
- Examples: For scale 100, the reading of 2550 means a value of 25.5. For scale 50, the reading of 2550 means a value of 51.
Communication settings (INTEGER 16 bit)
Parameter| Register number 1) [DEC]| Protocol address 2) [HEX]
Write register: function code 0x06
Modbus address 3)| 1| 0x00
Modbus protocol settings 4)| 2| 0x01
- Register number starts from 1.
- Protocol address starts from 0.
- If the Modbus adress is set via DIP switch the response will be NAK.
- For Modbus protocol settings see Application Note Modbus AN0103 (available at www.epluse.com).
INFO (read register)
Parameter| Register number 1) [DEC]| Protocol address 2) [HEX]
Read register: function code 0x03 / 0x04
Serial number (as ASCII)| 1| 0x00
Firmware version| 9| 0x08
- Register number starts from 1.
- Protocol address starts from 0.
3.5.5 Modbus RTU Example
Example of MODBUS RTU command for reading the CO2 (float value) CO2 =
1288,34375 ppm from the register 0x424
Device EE850; Modbus address 67 [0x43] Reference document, chapter 6.3:
http://www.modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdf
Request [Hex]: 43 03 04 24 00 02 8A 12
| Modbus address| Function code| Starting address Hi|
Starting address Lo| No. of register Hi| No. of register Lo|
CRC
---|---|---|---|---|---|---|---
Request [Hex]:| 43| 03| 04| 24| 00| 02| 8A| 12
Response [Hex]: 43 03 04 0B 00 44 A1 68 AB
| Modbus address| Function code| Byte count| Register 1
value Hi| Register 1 value Lo| Register 2 value Hi| Register 2
value Lo| CRC
---|---|---|---|---|---|---|---|---
Response [Hex]:| 43| 03| 04| 0B| 00| 44| A1| 68| AB
Decoding of floating point values:
Floating point values are stored according IEEE 754 standard. The byte
pairs 1, 2 and 3, 4 are inverted as follows:
MMMMMMMM | MMMMMMMM | SEEEEEEE | EMMMMMMM |
---|---|---|---|
Byte 3 | Byte 4 | Byte 1 | Byte 2 |
Example:
Response [Hex] | Decimal value |
---|---|
Byte 1 (Register 2 – Hi) | Byte 2 (Register 2 – Lo) |
Byte 4 (Register 1 – Lo) | |
44 | A1 |
Technical Data
Measurands
Measurement principle| Dual wavelength non-dispersive infrared technology
(NDIR)
---|---
Measuring range| 0…2 000 / 10 000 ppm
Accuracy at 25 °C (77 °F)| 0…2 000 ppm:| < ± (50 ppm + 2% of measured value)
and 1013 mbar (14.7 psi)| 0…10 000 ppm:| < ± (100 ppm + 5% of measured value)
Response time t63| < 100 s at 3 m/s (590 ft/min) air speed in the duct
Temperature dependency, typ.| ± (1 + CO2 concentration [ppm] / 1 000) ppm/°C,
for -20…45 °C (-4…113 °F)
Calibration interval1)| > 5 years
Measuring interval| Approx. 15 s
Temperature
Working range| -20…60 °C (-4…140 °F)
Accuracy at 20 °C (68 °F)| ±0.3 °C (±0.54 °F)
Response time t63| < 50 s
Relative Humidity
Working range| 0…95 %RH
Accuracy at 20 °C (68 °F)| ± 3 %RH (20…80 %RH)
Response time t63| < 10 s
Outputs
Analogue
CO2: 0…2000/10000 ppm| 0 – 10 V -1 mA < IL < 1 mA
4 – 20 mA RL < 500 0
T scale: according ordering guide RH scale: 0…100 %RH| 0 – 10 V -1 mA < IL < 1
mA
Digital Interface Protocol| RS485 (EE850 = 1/10 unit load)
Modbus RTU or BACnet MS/TP
Passive temperature, 2-wire
Wire resistance (terminal – sensor), typ.| T sensor type according ordering
guide 0.4 0
General
Power supply class IIIQ 2) | 24 VAC ± 20 % 15 – 35 V DC |
---|---|
Current consumption, typ. | 15 mA + output current |
Current peak, max. | 350 mA for 0.3 s (analogue output) |
150 mA for 0.3 s (RS485 interface)
Minimum air speed in the duct| 1 m/s (196 ft/min)
Enclosure material| Polycarbonate, UL94 V-0 approved
Protection rating| Enclosure: IP65 / NEMA 4X Probe: IP20
Cable gland| M16 x 1.5
Electrical connection| Screw terminals max. 2.5 mm2 (AWG 14)
Electromagnetic compatibility| EN 61326-1 EN 61326-2-3 Industrial Environment
FCC Part 15 Class A ICES-003 Class A
Working and storage conditions| -20…60 °C (-4…140 °F) 0…95 %RH, non-condensing
- Under normal operating conditions
- USA & Canada class 2 supply required, max. supply voltage 30 V DC
HEADQUARTERS
E+E Elektronik Ges.m.b.H.
Langwiesen 7
4209 Engerwitzdorf Austria
Tel.: +43 7235 605-0
E-mail: info@epluse.com
Web: www.epluse.com| SUBSIDIARIES
E+E Elektronik China
18F, Kaidi Financial Building,
No.1088 XiangYin Road
200433 Shanghai
Tel.: +86 21 6117 6129
E-mail: info@epluse.cn| E+E Elektronik France
47 Avenue de l‘Europe
92310 Sèvres
Tel.: +33 4 74 72 35 82
E-mail: info@epluse.fr
---|---|---
E+E Elektronik Germany
Obere Zeil 2
61440 Oberursel
Tel.: +49 6171 69411-0
E-mail: info@epluse.de| E+E Elektronik Italy
Via Alghero 17/19
20128 Milano (MI)
Tel.: +39 02 2707 86 36
E-mail: info@epluse.it
E+E Elektronik USA
333 East State Parkway
Schaumburg, IL 60173
Tel.: +1 847 490 0520
E-mail: office@epluse.com| E+E Elektronik
Korea
Suite 2001, Heungdeok IT
Valley Towerdong, 13,
Heungdeok 1-ro, Giheung-gu
16954 Yongin-si, Gyeonggi-do
Tel.: +82 31 732 6050
E-mail: info@epluse.co.kr
References
- Sensor Technology: Humidity, CO2, Flow & Temperature Measurement
- Sensor Technology: Humidity, CO2, Flow & Temperature Measurement
- konfigurationsaenderung_e_11.indd