E E ELEKTRONIK EE160 Humidity and Temperature Sensor
E+E Elektronik Ges.m.b.H. does not accept warranty and liability claims
neither upon this publication nor in case of improper treatment of the
described products.
The document may contain technical inaccuracies and typographical errors. The
content will be revised on a regular basis. These changes will be implemented
in later versions. The described products can be improved and changed at any
time without prior notice. © Copyright E+E Elektronik Ges.m.b.H. All rights
reserved.
EMC note USA (FCC):
This equipment has been tested and found to comply with the limits for a Class
A digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
EMC note Canada (ICES-003):
CAN ICES-3 (A) / NMB-3 (A)
General
This user manual serves for ensuring proper handling and optimal functioning of the device. The user manual shall be read before commissioning the equipment and it shall be provided to all staff involved in transport, installation, operation, maintenance and repair. The user manual may not be used for the purposes of competition without the written consent of E+E Elektronik® and may not be forwarded to third parties. Copies may be made for internal purposes. All information, technical data and diagrams included in these instructions are based on the information available at the time of writing.
Disclaimer
The manufacturer or his authorized agent can be only be held liable in case of
willful or gross negligence. In any case, the scope of liability is limited to
the corresponding amount of the order issued to the manufacturer. The
manufacturer assumes no liability for damages incurred due to failure to
comply with the applicable regulations, operating instructions or the
specified operating conditions. Consequential damages are excluded from the
liability.
Explanation of Symbols
This symbol indicates safety information.
It is essential that all safety information is strictly observed. Failure to
comply with this information can lead to personal injuries or damage to
property. E+E Elektronik® assumes no liability if this happens.
This symbol indicates instructions.
The instructions shall be observed in order to reach optimal performance of
the device.
Safety Instructions
General Safety Instructions
- The device and mainly the filter cap shall not be exposed to unnecessary mechanical stress.
- When replacing the filter cap make sure not to touch the sensing elements.
- The device must be operated with the filter cap on at all times.
- Installation, electrical connection, maintenance and commissioning shall be performed by qualified personnel only.
- Use the EE160 only as intended and observe all technical specifications.
- Do not use EE160 in explosive atmosphere or for measurement of aggressive gases.
- Do not apply the nominal voltage to the RS485 data lines.
- This device is not appropriate for safety, emergency stop or other critical applications where device malfunction or failure could cause injury to human beings.
Intended Use
The EE160 is intended for the humidity (RH) and temperature (T) measurement in
HVAC applications. The use of the EE160 in any other way than described in
this manual bears a safety risk for people and the entire measurement
installation and is therefore not allowed. The manufacturer cannot be hold
responsible for damages as a result of incorrect handling, installation, and
maintenance of the equipment.
Please note:
For accurate measurement it is essential that the temperature of the sensing
probe and mainly of the sensing head is same as the temperature of the air to
measure. Avoid mounting the EE160 sensor in a way which creates temperature
gradients along the probe. In order to avoid damage to the instrument or
health hazards, the measuring equipment must never be manipulated with tools
that are not specifically described in this manual. The sensor may only be
utilized in accordance with the conditions defined in the technical data.
Otherwise, measurement inaccuracies will occur and equipment failures cannot
be ruled out The steps recommended by the manufacturer for installation,
inspections and maintenance work must be observed and carried out for the
safety of the user and for the functionality of the equipment. Unauthorized
product modification leads to loss of all warranty claims. This may be
accomplished only with an explicit permission of E+E Elektronik®!
Mounting, Start-up and Operation
The EE160 humidity and temperature sensor has been produced under state of the
art manufacturing conditions, has been thoroughly tested and has left the
factory after fulfilling all safety criteria. The manufacturer has taken all
precautions to ensure safe operation of the device. The user must ensure that
the device is set up and installed in a manner that does not have a negative
effect on its safe use. The user is responsible for observing all applicable
safety guidelines, local and international, with respect to safe installation
and operation on the device. This user manual contains information and
warnings that must be observed by the user in order to ensure safe operation.
- Mounting, start-up, operation and maintenance of the device may be performed by qualified staff only. Such staff must be authorized by the operator of the facility to carry out the mentioned activities.
- The qualified staff must have read and understood this user manual and must follow the instructions contained within.
- All process and electrical connections shall be thoroughly checked by authorized staff before putting the device into operation.
- Do not install or start-up a device supposed to be faulty. Make sure that such devices are not accidentally used by marking them clearly as faulty.
- A faulty device may only be investigated and possibly repaired by qualified, trained and authorized staff. If the fault cannot be fixed, the device shall be removed from the process.
- Service operations other than described in this user manual may only be performed by the manufacturer.
Environmental Aspects
Products from E+E Elektronik® are developed and manufactured in compliance
with all relevant environmental protection requirements. Please observe local
regulations for the device disposal. For disposal, the individual components
of the device must be separated according to local recycling regulations. The
electronics shall be disposed of correctly as electronics waste.
Scope of Supply
Product Description
General
The EE160 probe is optimized for cost effective, accurate measurement of
relative humidity (RH) and temperature (T) in building automation. The
measured data is available on
- two voltage or current (2-wire) outputs
- the RS485 interface with BACnet MS/TP or Modbus RTU protocol
- a passive T output
Both, the wall mount and the duct mount model come with an IP65 / NEMA 4X enclosure which provides minimal installation costs and reliable protection against contamination and condensation. The encapsulated electronics and the E+E sensor coating ensure long-term stable and accurate measurements. The user can set the RS485 interface parameters, the output scaling and perform one or two point adjustment for RH and T with an optional configuration adapter and the free EE-PCS Product Configuration Software.
Dimensions
Electrical Connection
T-passive connection for M8TxA3/M8TxA6
LED indication for EE160-M1TxJ3:
- Green LED – information on normal operation mode: on = everything OK
- flashing = the main board does not recognize the measurement electronics inside the sensing probe
- off = no power supply or main board failure
Blue LED – information during setup with EE-PCS Product Configuration Software and the configuration adapter
- on = adapter connected to EE160 and PC, no communication with EE-PCS
- flashing = communication in progress with EE-PCS
- off = adapter not connected to EE160 and PC
Setup and Adjustment
The EE160 is ready to use and does not require any configuration by the user. The factory setup of EE160 corresponds to the type number ordered. Please refer to the data sheet at www.epluse.com/EE160. The user can change the factory setup with the help ofthe EE-PCS Product Configuration Software and the USB configuration adapter. Besides the output scaling the user can change the communication settings for digital interface and perform one or two point adjustment for humidity and temperature. EE160-M1TxJ3 (digital output) Using the USB configuration adapter HA011066 and the EE-PCS Product Configuration Software
Please note : The EE160 may not be connected to any additional power supply when using the USB configuration adapter.
EE160-MxTxAx (analogue output)
Using the EE-PCA Product Configuration Adapter with cable and the EE-PCS
Product Configuration Software
Please note: The EE160 must be powered when using the EE-PCA kit.
Bus Termination
If required, the RS485 bus termination can be realized with 120 ohm resistor,
jumper on the board.
EE-PCS Product Configuration Software
To use the software for performing adjustments and changes in settings, please
proceed as follows:
- Download the EE-PCS Product Configuration Software from www.epluse.com/configurator and install it on the PC.
- Connect the EE160 to the PC using the USB configuration adapter or the EEE-PCA product configuration adapter, respectively.
- Start the EE-PCS software.
- Follow the instructions on the EE-PCS opening page for scanning the ports and identifying the connected device.
- Click on the desired setup or adjustment mode from the main EE-PCS menu on the left and follow the online instructions of the EE-PCS
Address Setting
Address Switch
Address setting via EE-PCS Product Configuration Software: All DIP switches at position 0 → address has to be set via EE-PCS
- Modbus (Slave device): factory setting EE160: 245 (permitted values: 1…247).
- BACnet (Master device): factory setting EE160: 2 (permitted values: 0…127).
- Example : Address is set via configuration software.
Address setting via DIP switch:
- Modbus (Slave device) : Setting the DIP switch to any other address than 0, overrules the Modbus address set via configuration software (permitted values: 1…247).
- BACnet (Master device): Setting the DIP switch to any other address than 0, overrules the BACnet address set via configuration software.
- BACnet Note : permitted values are 0…127. The 8th bit of the DIP switch is ignored (ID 127 = 0111 111).
- To set address 0 via DIP switch, the 8th bit shall be set to 1 ( ID 0 = 1000 0000).
- Example : Address set to 11 ( = 0000 1011 binary).
BACnet Setup
BACnet PICS is available for download at
www.epluse.com/ee160.
Digital Interface RS485 with Modbus RTU Protocol
Item | Factory settings | Selectable values (via EE-PCS) |
---|---|---|
Baud rate | 9 600 | 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 |
Data bits | 8 | 8 |
Parity | Even | None, odd, even |
Stop bits | 1 | 1, 2 |
Modbus address | 245 | 1…247 |
The recommended settings for multiple devices in a Modbus RTU network are 9600, 8, even, 1. The EE160 represents 1 unit load on an RS485 network. Device address, baud rate, parity and stop bits can be set via:
- EE-PCS Product Configuration Software, the USB configuration adapter HA011066. The EE-PCS can be downloaded free of charge from www.epluse.com/configurator
- Modbus protocol in the register 60001 (0x00) and 60002 (0x01). See Modbus Application Note AN0103 (available at www.epluse.com/ee160)
The serial number as ASCII-code is located in the register addresses 0x00…0x07 (16 bits per address). The firmware version is located in the register address 0x08 (bits 15…8 = major release; bits 7…0 = minor release). The sensor name is located in register address 0x09. The beforementioned registers can be read out with function code 0x03 or 0x04.
Please note : When reading the serial number or the sensor name, it is always necessary to read all 8 registers, even if the desired information requires less.
Please note : For obtaining the correct floating point values, both registers have to be read within the same reading cycle. The measured value can change between two Modbus requests, therefore, exponent and mantissa may get inconsistent
Communication settings (INTEGER 16 bit)
Parameter| Register number 1) [DEC]| Protocol address
2) [HEX]
Write register: function code 0x06
Modbus address| 1| 0x00
Modbus protocol settings 3)| 2| 0x01
- Register number starts from 1.
- Protocol address starts from 0.
- For Modbus protocol settings see Application Note Modbus AN0103 (available at www.epluse.com/EE160).
INFO (read register)
Parameter| Register number 1) [DEC]| Protocol address
2) [HEX]
Read register: function code 0x03 / 0x04
Serial number (as ASCII)| 1| 0x00
Firmware version| 9| 0x08
Sensor Name| 10| 0x09
- Register number starts from 1.
- Protocol address starts from 0.
Modbus Register Map
The measured data is saved as a 32 bit floating point values (data type FLOAT)
and as 16 bit signed integer values (data type INTEGER).
FLOAT 32 bit:
Parameter| Unit| Register number 1) [Dec]| Register
address 2) [HEX]
Read register: function code 0x03
Temperature T| °C, °F 3)| 26| 0x19
Relative humidity RH, Uw| % RH| 28| 0x1B
- Register number starts from 1.
- Register address starts from 0.
- The choice of measurement units (metric or non-metric) is done at the time of ordering, see the ordering guide in the EE160 data sheet. It is not possible to switch from metric to non-metric or vice versa by means of the EE-PCS
INTEGER 16 bit:
Parameter| Unit| Scale 1)| Register number 2)
[Dec]| Register address 3) [HEX]
Read register: function code 0x03
Temperature T| °C, °F 4)| 100| 301| 0x12C
Relative humidity RH, Uw| % RH| 100| 302| 0x12D
- Example : For scale 100, the reading of 2550 means a value of 25.5.
- Register number starts from 1.
- Register address starts from 0.
- The choice of measurement units (metric or non-metric) is done at the time of ordering, see the ordering guide in the EE160 data sheet. It is not possible to switch from metric to non-metric or vice versa by means of the EE-PCS.
Modbus Message Example
Example of Modbus RTU command for reading the temperature (float value) T = 23,290008 °C from the register 0x19
Device EE160; Modbus address 245 [0xF5] Reference document, chapter 6.3: www.modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdfSee Application Note Modbus AN0103 (available at www.epluse.com/ee160)
| Modbus address| Function code| Starting address Hi|
Starting address Lo| No. of register Hi| No. of register Lo|
CRC
---|---|---|---|---|---|---|---
Request [Hex]:| F5| 03| 00| 19| 00| 02| 01| 0F
| Modbus address| Function code| Byte count|
Register 1 value Hi| Register 1 value Lo| Register 2 value Hi|
Register 2 value Lo| CRC
Response Hex]:| F5| 03| 04| 51| F0| 41| BA| 98| 10
Decoding of floating point values: Floating point values are stored according IEEE754 standard. The byte pairs 1, 2 and 3, 4 are inverted as follows:
MMMMMMMM | MMMMMMMM | SEEEEEEE | EMMMMMMM |
---|---|---|---|
Byte 3 | Byte 4 | Byte 1 | Byte 2 |
Example:
Response [Hex] | Value in decimal |
---|---|
Byte 1 (Register 2 – Hi) | Byte 2 (Register 2 – Lo) |
– Hi)_ | Byte 4 (Register 1 – Lo) |
41 | BA |
RH / T Adjustment and Calibration
Definitions
- Calibration documents the accuracy of a measurement device. The device under test (specimen) is compared with the reference and the deviations are documented in a calibration certificate. During the calibration, the specimen is not changed or improved in any way.
- Adjustment improves the measurement accuracy of a device. The specimen is compared with the reference and brought in line with it. An adjustment can be followed by a calibration which documents the accuracy of the adjusted specimen.
Depending on the application and the requirements of certain industries, there might arise the need for periodical humidity calibration (comparison with a reference) or adjustment (bringing the device in line with a reference).
-
Calibration and adjustment at E+E Elektronik
Calibration and/or adjustment can be performed in the E+E Elektronik calibration laboratory. For information on the E+E capabilities in ISO or accredited calibration refer to www.eplusecal.com. -
Calibration and adjustment by the user
-
Depending on the level of accuracy required, the humidity reference can be:
-
Humor 20 Humidity Calibrator, refer to www.epluse.com.
-
Omniport30 handheld device, refer to www.epluse.com/omniport30.
-
Certified salt solutions, refer to www.epluse.com/ee160.
Cleaning of the sensing head:
Use in polluted environment might rise the need for cleaning the sensing head
and replacing the filter cap. In such a case refer to “Cleaning Instructions”
at www.epluse.com/ee160.
When employed in dusty, polluted environment:
- The filter cap shall be replaced once in a while with an E+E original one. A polluted filter cap causes longer response time of the device.
- If needed, the sensing head can be cleaned. For cleaning instructions refer to www.epluse.com/ee160.
While replacing the filter cap take very good care to not touch or rub the sensing element.
Accessories
Please also refer to the “Accessories“ data sheet.
Description
- E+E Product Configuration Software (Download: www.epluse.com/configurator) EE-PCS
- Power supply adapter V03
- Protection cap for 12 mm probe HA010783
- USB configuration adapter for EE160-M1TxJ3 (RS485) HA011066
- Product configuration adapter for EE160-MxTxAx (analogue output) see datasheet EE-PCA
Technical Data
- Traceable to international standards, administrated by NIST, PTB, BEV,… The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-times standard deviation). The accuracy was calculated in accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement)
- USA & Canada class 2 supply required, max. supply voltage 30 V DC.
HEADQUARTERS
E+E Elektronik Ges.m.b.H. Langwiesen 7 4209 Engerwitzdorf Austria