victron energy Phoenix VE.Direct Safety Plug Inverter User Manual

June 9, 2024
victron energy

Phoenix VE.Direct Safety Plug Inverter
User Manual

IMPORTANT SAFETY INSTRUCTIONS – SAVE THESE INSTRUCTIONS!

In general
Please read the documentation supplied with this product first, so that you are familiar with the safety signs en directions before using the product.
This product is designed and tested in accordance with international standards. The equipment should be used for the designated application only.
Warning – These servicing instructions are for use by qualified personnel only. To reduce the risk of electric shock, do not perform any servicing other than that specified in  the operating instructions unless you are qualified to do so.

WARNING: ELECTRIC SHOCK HAZARD
The product is used in conjunction with a permanent energy source (battery). Input and/or output terminals may still be dangerously energized, even when the equipment is  switched off. Always disconnect the battery before carrying out maintenance or servicing the product.
The product has no internal user-serviceable components. Do not remove the front plate or operate the product if any panels have been removed. All servicing must be  undertaken by qualified personnel.
Please read the installation instructions in the installation manual before installing the equipment.
This is a Safety Class I product (supplied with a protective grounding terminal). The chassis must be grounded. A grounding point is located on the outside of the product.  Whenever it is likely that the grounding protection has been damaged, the product must be turned off and secured against unintended operation; please contact qualified service staff.
The AC output is isolated from the DC input and the chassis unless the unit is equipped with a Ground Fault Circuit Interrupter (GFCI). Units with a GFCI have AC output  neutral connected to chassis inside the device by default. A qualified installer should check this connection since it is necessary for the GFCI to function properly. Local  regulations may require a true neutral. In this case one of the AC output wires must be connected to the chassis, and the chassis must be connected to a reliable ground.  Please note that a true neutral is needed to ensure correct operation of an earth leakage circuit breaker.
Ensure that the equipment is used under the correct ambient conditions.
Never operate the product in a wet or dusty environment.
Never use the product where there is a risk of gas or dust explosions.
Ensure there is adequate free space (10 cm) for ventilation around the product and check that the ventilation vents are not blocked.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they  have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
Use of an attachment not recommended or sold by the marine unit manufacturer may result in a risk of fire, electric shock, or injury to persons.

Description

VE.Direct communication port
The VE.Direct port can be connected to:

  • A computer (VE.Direct to USB interface cable needed)
  • Apple and Android smartphones, tablets and other devices (VE.Direct to Bluetooth Smart dongle needed)

Fully configurable

  • Low battery voltage alarm trip and reset levels
  • Low battery voltage cut-off and restart levels, or Dynamic Cut-off
  • Output voltage 210 – 245 V
  • Frequency 50 Hz or 60 Hz
  • ECO mode on/off and ECO mode sense level

Monitoring
Battery voltage, AC Output voltage, load indicator, alarms

Proven reliability
The full bridge with toroidal transformer topology has proven its reliability over many years.
The inverters are short circuit proof and protected against overheating, whether due to overload or high ambient temperature.

High start-up power
Needed to start loads such as power converters for LED lamps, filament lamps or electric tools.

ECO mode
When in ECO mode, the inverter will switch to standby when the load decreases below a preset value. It will switch on and check every few seconds, adjustable, if the load has increased again.

Remote on/off connector
A remote on/off switch can be connected to a two-pole connector or between battery plus and the left hand contact of the two pole connector.

LED diagnosis
A red and a green LED indicate inverter operation and status of the different protections.

To transfer the load to another AC source: the automatic transfer switch
For our low power inverters we recommend our Filax Automatic Transfer Switch. The Filax features a very short switchover time (less than 20 milliseconds) so that  computers and other electronic equipment will continue to operate without disruption.

Available with different output sockets
Schuko, UK (BS-1363), AU/NZ (3112) or IEC-320 (male plug included)

Installation

3.1 Location of the inverter

  1. Ceiling mounting (inverted).
  2. Base mounting.
  3. Vertical wall mounting, fan at bottom.
  4. Vertical wall mounting, fan on top.Horizontal wall mounting.

Not recommended OK
OK (beware of small objects falling through the ventilation openings on top).
Not recommended OK

For best operating results, the inverter should be placed on a flat surface. To ensure a trouble free operation of the inverter, it must be used in locations that meet the  following requirements:
a) Avoid any contact with water. Do not expose the inverter to rain or moisture.
b) Do not place the unit in direct sunlight. Ambient air temperature should be between -20 °C and 40 °C (humidity < 95 % non condensing). Note that in extreme situations  the inverter’s case temperature can exceed 70 °C.
c) Do not obstruct the airflow around the inverter. Leave at least 10 centimetres clearance around the inverter. When the inverter is running too hot, it will shut down. When  the inverter has reached a safe temperature level the unit will automatically restart again.

3.2 Connection to the battery
In order to utilize the full capacity of the product, batteries with sufficient capacity and battery cables with sufficient cross section should be used. See table:

| 12/250| 24/250| 48/250| 12/375| 24/375| 48/375
---|---|---|---|---|---|---
Minimum battery cap.| 30 Ah| 20 Ah| 10 Ah| 40 Ah| 30 Ah| 15 Ah
Internal DC fuse| 2 x 30A| 30 A| 25A| 2 x 40 A| 40 A| 25 A
Fuse type (Mfr.: Littelfuse)| ATOF
32 V| ATOF
32 V| FKS
80 V| ATOF
32 V| ATOF
32 V| FKS
80 V
Fuse replaceble| no| no| no| no| no| no
Recommended DC cable cross-sect on (mm2)
0 — 1,5 m| 4 mm2| 2,5 mm2| 1,5 mm2| 6 mm2| 4 mm2| 2,5 mm2
1,5 — 3 m| 6 mm2| 4 mm2| 2.5 mm2| 10 mm2| 6 mm2| 4 mm2
| 12/500| 24/500| 48/500| 12/800| 24/800| 48/800
---|---|---|---|---|---|---
Minimum battery cap.| 60 Ah| 40 Ah| 20 Ah| 100 Ah| 50 Ah| 30 Ah
Internal DC fuse| 3 x 35 A| 2 x 25 A| 30A| 125A| 2 x 40 A| 2 x 20 A
Fuse type (Mfr.: Littelfuse)| ATOF
32 V| ATOF
32 V| FKS
80 V| MIDI
32 V| ATOF
32 V| FKS
80 V
Fuse replaceble| no| no| no| yes| no| no
Recommended DC cable cross-sect on (mm2)
0 — 1,5 m| 6 mm2| 6 mm2| 4 mm2| 16 mm2| 6 mm2| 4 mm2
1,5 -3 m| 10 mm2| 10 mm2| 6 mm2| 25 mm2| 10 mm2| 6 mm2
| 12/1200| 24/1200| 48/1200
---|---|---|---
Minimum battery cap.| 150 Ah| 60 Ah| 30 Ah
Internal DC fuse| 200 A| 100 A| 50 A
Fuse type (Mfr.:| MIDI| MIDI| MIDI
Littelfuse)| 32 V| 32 V| 58 V
Fuse replaceble| yes| yes| yes
0 — 1,5 m| 25 mm2| 10 mm2| 6 mm2
1,5 -3 m| 35 mm2| 16 mm2| 10 mm2

The inverters are fitted with an internal DC fuse (see table above for rating). If the DC cable length is increased to more than 1,5m, an additional fuse or DC circuit breaker  must be inserted close to the battery. Important note: for UL certified (NEMA GFCI) inverters it is mandatory to install a fuse or DC circuit breaker close to the battery,  even if the cable length is less than 1,5m.
Reverse polarity connection of the battery wires will blow the internal fuse and can damage the inverter. The internal fuse is not always replaceble (see table above).

3.3 Wire size for connecting the inverter chassis to ground
The earth conductor from the earth lug on the chassis to ground should have at least half the cross-section of the conductors used for the battery connection: see Appendix B.

3.4 Connection to the load
Never connect the output of the inverter to another AC source, such as a household AC wall outlet or a generator.
The inverter does not have a fuse in the AC output. The AC cabling is protected by a fast-acting current limiter in case of a short circuit and an overload detection mechanism which mimics the characteristics of a fuse (i.e. faster shutdown with larger overload). It is important to size your wiring properly based on the inverters’ power rating.

3.5 Connecting the inverter neutral output to the chassis/ground
The AC output is isolated from the DC input and the chassis. Local regulations may require a true neutral. In this case one of the AC output wires must be connected to the  chassis, and the chassis must be connected to a reliable ground: see appendix A.

3.6 Remote on/off connector
A remote on/off switch can be connected to the two-pole connector. Alternatively, the left-hand contact of the connector can be switched to battery positive: useful in  automotive applications, wire it to the ignition contact.
Note that also the front switch needs to set to either On or ECO for the inverter to start.

3.7 Configuration
The inverter is ready for use with the factory settings (see specifications), and can be configured with a computer (VE.Direct to USB interface cable needed), Apple and  Android smartphones, tablets and other devices (VE.Direct to Bluetooth Smart dongle needed).

Operation

4.1 LED definitions

Green LED Status Trouble shooting
**** Solid on Inverter on Red LED Off status OK

Red LED On or blinking:
The Inverter is still on, but will shut down when the condition gets worse. See red LED table for warning reason
Slow single pulse| ECO mode| If the inverter keeps switching on and off while there is a load connected, the load may be too small compared to the actual ECO mode settings. Increase the load or change ECO mode settings. (minimum ECO mode setting: 15 W)
Fast double pulse| Off and waiting| Inverter did shut down because of a protection. The inverter will restart automatically as soon as all alarm conditions are cleared. See red LED state for the shutdown reason.
Off| Inverter off| Red LED Off
Check the On/OWECO switch: it should be in On position or in ECO position.
Check Remote on/off connector.
Check DC cable connections and fuses.
Inverter fuse blown: the inverter has to be returned for service.
Red LED On or blinking
The inverter did shut down because of a protection. It will no longer automatically restart. The red LED indicates the reason for shutdown. Remove the cause and then restsst the inverter by switching it Off, and then back On.
Red LED| Definition| Trouble shooting
---|---|---
Solid on| Overload| Reduce load
Slow blink| Low batt.| Recharge or replace battery
Check DC cable connections
Check cable cross section as it may be insufficient. See section 4.3 Protections and automatic restarts for manual and automatic restart behavior.
Fast blink| High batt.| Reduce DC input voltage, check for faulty charger
Double pulse| High ternP.| Reduce load and/or move inverter to better ventilated area
**** Fast single pulse| High DC ripple| Check DC cable connections and cable cross section.

4.2 ECO Mode
Set the front switch to ECO mode to reduce the power consumption in no-load operation. The inverter will automatically switch off as soon as it detects that there is no load connected. It then switches on, briefly, every 2.5 seconds to detect a load. If the output power exceeds the set level, the inverter will continue to operate.
The default ECO mode wake-up minimum power is 15 Watt.
The default ECO mode search interval is 2.5 seconds
Note that the required ECO mode settings are heavily dependent on the type of load: inductive, capacitive, non-linear. Adjustment may be needed.

4.3 Protections and automatic restarts Overload
Some loads like motors or pumps draw large inrush currents in a start-up situation. In such circumstances, it is possible that the start-up current exceeds the over current trip  level of the inverter. In this case the output voltage will quickly decrease to limit the output current of the inverter. If the over current trip level is continuously exceeded, the  inverter will shut down: wait 30 seconds and then restart.
After three restarts followed by another overload within 30 seconds of restarting, the inverter will shutdown and remain off. The LEDs will signal shutdown due to overload. To restart the inverter,switch it Off, then On.

Low battery voltage (adjustable)
The inverter will shut down when the DC input voltage drops below the low battery shutdown level.
After a minimum delay of 30 seconds, the inverter will restart if the voltages rise above the low battery restart level.
After three restarts followed by a low battery shutdown within 30 seconds of restarting, the inverter will shutdown and stop retrying. The LEDs will signal low battery  shutdown. To restart the inverter, switch it Off, and then On, or recharge the battery: as soon as the battery has risen and then stays above the Charge detect level for 30  seconds, it will switch on.
See the Technical Data table for default low battery shutdown and restart levels. They can be changed with VictronConnect (computer or app).
Alternatively Dynamic Cut-off can be implemented, see https://www.victronenergy.com/live/ve.direct:phoenix-inverters-dynamic- cutoff

High battery voltage
Reduce DC input voltage and/or check for a faulty battery- or solar-charger in the system. After shutting down due to a high battery voltage, the inverter will first wait 30  seconds and then retry operation as soon as the battery voltage has dropped to acceptable level. The inverter will not stay off after multiple retries.

High temperature
A high ambient temperature or enduring high load may result in shut down to over temperature.
The inverter will restart after 30 seconds. The inverter will not stay off after multiple retries.
Reduce load and/or move inverter to better ventilated area.

High DC ripple
High DC ripple is usually caused by loose DC cable connections and/or too thin DC wiring. After the inverter has switched off due to high DC ripple voltage, it waits 30  seconds and then restarts.
After three restarts followed by a shutdown due to high DC ripple within 30 seconds of restarting, the inverter will shutdown and stops retrying. To restart the inverter,  switch it Off and then On.
Continuous high DC ripple reduces life expectancy of the inverter.

12 Volt
Phoenix Inverter
24 Volt 48 Volt| 12/250
24/250
48/250| 12/375
24/375
48/375| 12/500
24/500
48/500| 12/800
24/800
48/800
---|---|---|---|---
Cont. power at 25 °C (1)| 250 VA| 375 VA| 500 VA| 800 VA
Cont. power at 25 °C / 40 °C| 200 / 175 W| 300 / 260 W| 400 / 350 W| 650 / 560 W
Peak power| 400 W| 700 W| 900 W| 1500 W
Output AC voltage / frequency (adjustable)| 230 VAC or 120 VAC +/- 3 % 50 Hz or 60 Hz +/- 0.1 %
Input voltage range| 9.2 – 17 / 18.4 – 34.0 / 36.8 – 62.0 VDC
Low battery shut down (adjustable)| 9.3 / 18.6 / 37.2 VDC
Low battery restart & alarm (adjustable)| 10.9 / 21.8 / 43.6 VDC
Battery charged detect (adjustable)| 14.0 / 28.0 / 56.0 VDC
Max. efficiency| 87/88/88 %| 89/89/90 %| 90/90/91 %| 90/90/91 %
Zero-load power| 4.2/5.2/7.9 W| 5.6/6.1/8.5 W| 6/6.5/9 W| 6.5/7/9.5 W
Default zero-load power in ECO mode (default search interval: 2.5 s, adjustable)| 0.8/1.3/2.5 W| 0.9/1.4/2.6 W| 1 / 1.5 / 3 W| 1 / 1.5 / 3 W
ECO mode stop and start power setting| Adjustable
Protection (2)| a – f
Operating temperature range| -40 to +60 °C (fan assisted cooling)
(derate 1.25 % per °C above 40 °C)
Humidity (non-condensing)| max 95 %

ENCLOSURE

Material & Colour| Steel chassis and plastic cover (blue Ral 5012)
Battery-connection| Screw terminals
Maximum cable cross-section| 10 mm² / AWG8| 25/10/10 mm² / AWG4/8/8


Standard AC outlets

| 230 V: Schuko (CEE 7/4), IEC-320 (male plug included) UK (BS 1363), AU/NZ (AS/NZS 3112)
120 V: Nema5-15R, NEMA GFCI (2x Nema5-15R with GFCI)
Protection category| IP 21
Weight| 2.4 kg/5.3 lbs| 3.0 kg/6.6 lbs| 3.9 kg/8.5 lbs| 5.5 kg/12 lbs
Dimensions (hxwxd, mm) (hxwxd, inch)| 86x165x260
3.4×6.5×10.2| 86x165x260
3.4×6.5×10.2| 86x172x275
3.4×6.8×10.8| 105x216x305
4.1×8.5×12.1
(12 V model: 105x230x325)

ACCESSORIES

Remote on-off| Yes
Automatic transfer switch| Filax or Multi

STANDARDS

Safety| EN/IEC 60335-1 / EN/IEC 62109-1 / UL 458 (3)
EMC| EN 55014-1 / EN 55014-2
IEC 61000-6-1 / IEC 61000-6-3
Automotive Directive| ECE R10-4 EN 50498
1)  Nonlinear load, crest factor 3:1
3) UL 458 only for inverters with GFCI output socket
2)  Protection key:
a)  output short circuit
b)  overload
c) battery voltage too high
d)  battery voltage too low
e)  temperature too high
f) DC ripple too high
12 Volt
Phoenix Inverter
24 Volt 48 Volt| 12/1200
24/1200
48/1200
---|---
Cont. power at 25 °C (1)| 1200 VA
Cont. power at 25 °C / 40 °C| 1000 / 900 W
Peak power| 2400 W
Output AC voltage / frequency (adjustable)| 230 VAC or 120 VAC +/- 3 % 50 Hz or 60 Hz +/- 0.1 %
Input voltage range| 9.2 – 17 / 18.4 – 34.0 / 36.8 – 62.0 VDC
Low battery shut down (adjustable)| 9.3 / 18.6 / 37.2 VDC
Low battery restart & alarm (adjustable)| 10.9 / 21.8 / 43.6 VDC
Battery charged detect (adjustable)| 14.0 / 28.0 / 56.0 VDC
Max. efficiency| 92 / 94 / 94 %
Zero-load power| 8 / 9.5 / 10 W
Default zero-load power in ECO mode (default search interval: 2.5 s, adjustable)| 1 / 1.7 / 2.7 W
ECO mode stop and start power setting| Adjustable
Protection (2)| a – f
Operating temperature range| -40 to +60 °C (fan assisted cooling) (derate 1.25 % per °C above 40 °C)
Humidity (non-condensing)| max 95 %

ENCLOSURE


Material & Colour| Steel chassis and plastic cover (blue Ral 5012)
Battery-connection| Screw terminals
Maximum cable cross-section| 35/25/25 mm² / AWG2/4/4
Standard AC outlets| 230 V: Schuko (CEE 7/4), IEC-320 (male plug included) UK (BS 1363), AU/NZ (AS/NZS 3112) 120 V: Nema5-15R, NEMA GFCI (2x Nema5-15R with GFCI)
Protection category| IP 21
Weight| 7.7 kg/17 lbs
Dimensions (hxwxd, mm) (hxwxd, inch)| 117x232x327
4.6×9.1×12.9
(12 V model: 117x232x367)

ACCESSORIES


Remote on-off| Yes
Automatic transfer switch| Filax or Multi

STANDARDS


Safety| EN/IEC 60335-1 / EN/IEC 62109-1 / UL 458 (3)
EMC| EN 55014-1 / EN 55014-2
IEC 61000-6-1 / IEC 61000-6-3
Automotive Directive| ECE R10-4 EN 50498
1)  Nonlinear load, crest factor 3:1
3) UL 458 only for inverters with GFCI output socket
2)  Protection key:
a)  output short circuit
b)  overload
c) battery voltage too high
d)  battery voltage too low
e)  temperature too high
f) DC ripple too high

Front and rear view

Example of front view:

Example of rear view with Schuko outlet:

Example of rear view with NEMA GFCI outlet:

Mounting instructions

Mount the inverter with four screws vertically up- or downwards or horizontally up- or downwards (as indicated in Figure 1) against a sturdy wall or horizontally on a suitable  ground surface (as indicated in Figure 2). Keep at least 4 inches (10 cm) clearance with respect to other apparatus/objects. Beware that IP21 only applies to the lower mounting method depicted in Figure 2; otherwise IP20 is applies. Do not mount the inverter upside down to a surface.

Appendix A

Connecting the inverter neutral output to the chassis/ground
The AC output is isolated from the DC input and the chassis. Local regulations may require a true neutral. In this case one of the AC output wires must be connected to the  chassis, and the chassis must be connected to a reliable ground. Inside the inverter a provision has been made to be able to connect the neural and the chassis; the way to do  this is explained below.
Please be sure to disconnect the battery when connecting the neutral to protective earth (PE).
An internal PE wire, which is used to connect the neutral and the chassis, is accessible after removing the plastic cover. A Torx T10 screwdriver is needed to loosen the four  screws which hold the plastic cover.
In the pictures below the two possible connections of the PE wire are shown:

For the 250 VA, 375 VA and 500 VA inverters:

  1. Neutral floating
    Position of the PE wire (indicated by arrow):

  2. Neutral connected to protective earth
    Position of the PE wire (indicated by arrow):

For the 800 VA and 1200 VA inverters:
For these inverters the earth wire from the chassis can be either connected to FJ1 (neutral floating) or to FJ2 (neutral connected to earth/chassis). The labels FJ1 and FJ2 are  printed on the circuit board. The default position is FJ1, i.e. neutral is floating.

Appendix B
Wire size for connecting the inverter chassis to ground
The earth conductor from the earth lug on the chassis to ground should have at least half the cross-section of the conductors used for the battery connection. The maximum  conductor size that fits the earth lug is 25 mm². Use the table below to find the correct cross-section for the earth conductor.

Cable cross-section


to battery| to protective earth
1.5 mm²| ≥ 0.75 mm²
2.5 mm²| ≥ 1.5 mm²
4 mm²| ≥ 2.5 mm²
6 mm²| ≥ 4 mm²
10 mm²| ≥ 6 mm²
16 mm²| ≥ 10 mm²
25 mm²| ≥ 16 mm²
35 mm²| 25 mm²

Victron Energy Blue Power
Distributor:………………………………………..
Serial number: …………………………………….
Version : 06
Date : April 19th, 2022

Victron Energy B.V.
De Paal 35 | 1351 JG Almere
PO Box 50016 | 1305 AA Almere | The Netherlands
General phone : +31 (0)36 535 97 00
E-mail : sales@victronenergy.com
www.victronenergy.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

victron energy User Manuals

Related Manuals