victron energy 200-200A GX Digital Multi Control 200 200A GX User Guide
- May 15, 2024
- victron energy
Table of Contents
200-200A GX Digital Multi Control 200 200A GX
User Guide Digital Multi Control
Digital Multi Control 200/200A GX
rev 00 – 10/2023
This manual is also available in
HTML5.
Safety instructions
General
- Review the included documentation for instructions before using this product.
- This product has been tested in accordance with international standards. Only use this product for the intended purpose or application.
- Never use the product in locations with a gas or dust explosion danger.
Installation
- Always refer to the installation section in this manual before applying power to the equipment.
- Ensure that the environmental conditions are suitable for the operation of this product. Never operate the product in the rain or a dusty environment.
Transport and storage
- When storing or transporting this product, ensure all leads are disconnected.
- There is no liability for transport damage in non-original packaging.
- Store the product in a dry location.
- Storage temperature must be between -20°C and 60°C.
Introduction
The Digital Multi Control 200/200A GX enables remote monitoring and control of
inverter/charger systems in stand-alone, parallel, and 2- or 3-phase
configurations. It seamlessly integrates with the helm, dashboard or control
panel of your vessel, vehicle, or
home system.
Note: “System” refers to interconnected inverter/chargers through RJ45
UTP cables.
2.1. Compatibility
The control panel is compatible with these inverter/charger models:
- MultiCompact.
- MultiPlus, MultiPlus-II and MultiPlus-II GX.
- Quattro and Quattro-II.
- EasySolar and EasySolar-II GX.
- Legacy (pre-VE.Bus) Multi, MultiCompact, MultiPlus and Quattro (2008 and earlier).
2.2. Quick start guide
Installing the Digital Multi Control panel is straightforward. Simply connect
the control panel to the inverter/charger system using an RJ45 UTP
Cable. In most cases, no
further setup is needed.
For expedited installation instructions, find your system type in the list
below and click the appropriate link:
System types:
- MultiPlus system with 1 AC source [4].
- Quattro system with 2 AC sources [4].
- MultiPlus system with 2 AC sources and transfer switch [4].
- MultiPlus system with 2 AC sources [4].
- Legacy pre-VE.Bus systems [12].
For comprehensive details about the control panel, including features,
configuration, and operational information, consult the complete manual.
2.3. What’s in the box
- Digital Multi Control 200/200A GX.
- Four mounting screws.
Features
3.1. System connectivity
The control panel integrates with the inverter/charger system, consisting of a
single or multiple Inverter/chargers configured as a in stand-alone, parallel,
and 2- or 3-phase system.
3.2. Power mode switch
The switch can be used to turn the inverter/charger system on, off or to
charger-only mode.
3.3. LEDs
Eight LEDs replicate the inverter/charger LEDs.
Note that if the panel is connected to an inverter/charger model with only
three LEDs, the full eight LED indications will be shown.
The LEDs auto-adjust to a lower brightness in low-light conditions.
3.4. Display
The 7-segment display primarily shows the AC input current and, if applicable,
displays the AC input source or VE.Bus error codes.
3.5. AC input control
The control panel’s knob adjusts the AC input current limit. This is useful
for mobile setups that connect to various AC sources with different circuit
breaker current ratings.
The adjustment range is synchronised with the inverter/charger system range.
For instance, when connected to an inverter/ charger with 16A feed-through
capacity, the AC input range remains within 16A. If linked to five of these
units in parallel, it is scaled up to 80A.
If an AC input range below the feed-through capacity of the inverter/charger
is required, a custom upper threshold can be configured. Refer to the Upper AC
input limit 1 to 4 [8] chapter.
If needed, a fixed AC current can be specified in the inverter/charger
settings, which then cannot be modified by the remote panel. Refer to the
Current limit overruled by remote [8] chapter.
3.6. Multiple AC inputs
The control panel automatically adapts to systems that have multiple AC
inputs, as is the case with a Quattro or an extended VE.Bus systems.
When switching between the different AC inputs, the display alternates between
showing the AC current limit value and the input name (AC2, AC3, etc.). For
AC1, only the current limit will be shown.
The display remembers the last used AC current limit value for each input.
3.7. Generator support with external transfer switch
For a system with a MultiPlus together with an external transfer switch, the
control panel can be configured to allow the AC current to be changed while
the system is connected to the grid but has a fixed AC current limit when
connected to a generator.
The panel sends the current limit to the inverter/charger system as set via
the knob. If the screw terminals on the panel’s back are short-circuited, a
preset current limit is sent instead, and “GEN” is displayed.
To enable this, connect the screw connector terminals to an externally
controlled switch, typically the auxiliary relay of an external transfer
switch. For setup, refer to the Generator current limit [8] chapter.
This feature is not relevant to a standard Quattro setup, which does not need
an external transfer switch, and a fixed generator AC input limit can be
configured in the Quattro.
System types
This chapter describes the different inverter/charger system types that the
control panel can connect to.
4.1. MultiPlus system with 1 AC source
Setup is easy, simply connect the control panel to the VE.Bus system (refer to
the Inverter/charger connection [5] chapter), and it will automatically adapt
to the system. No adjustments are required unless you want to restrict the
operator’s maximum AC current setting. For this refer to the Upper AC input
limit 1 to 4 [8] chapter.
4.2. Quattro system with 2 AC sources
If your system contains one or more Quattros, setup is easy. Simply connect
the control panel to the VE.Bus system (refer to the Inverter/charger
connection [5] chapter), and it will automatically adapt to the system.
You probably will not need to adjust any settings in the control panel. In a
Quattro setup, the AC1 input takes precedence over the AC2 input. By default,
the AC2 input current limit can be overridden by the remote panel, while the
AC1 input current limit remains fixed (this can be altered in the Quattro
settings).
A common setup involves connecting a generator to the AC1 input and grid power
to the AC2 input. While the generator runs, the control panel shows “AC1,” and
the know can not alter the AC1 input current limit. Once the generator stops
and shore power is
active, the panel toggles between “AC2” and the AC current value. Turning the
knob will alter the AC2 input current limit.
To cap the maximum settable current, adjust the “Upper shore limit for AC
input 2” parameter. For details, see the Upper AC input limit 1 to 4 [8]
chapter, and refer to the Special display feature [8] chapter to stop the
display from toggling between “AC2” and the AC input current value.
4.3. MultiPlus system with 2 AC sources and transfer switch
When using an external transfer switch (VE Transfer Switch) with a MultiPlus
inverter/charger system, the switch dictates which AC source is utilised –
either generator or grid power. However, the control panel itself is not aware
of the chosen AC source.
To ascertain the transfer status, the control panel features a screw connector
on its backside. Normally, the panel sends the AC current set point from the
knob to the inverter/charger system. But, by short-circuiting the screw
terminals, the panel displays “GEN” and sends a preset AC current limit to the
inverter/charger system.
For connection advice refer to the External transfer switch connection [5]
chapter and for configuration instructions, refer to the Generator current
limit [8] chapter.
4.4. MultiPlus system with 2 AC sources
To create a system with multiple AC inputs, you can use multiple MultiPlus
units and configure them as such, using the “VE.Bus System Configurator”
software tool. While such a system is feasible, it is advisable to first
explore using Quattros. From the control panel’s perspective, building a
system with Quattros or MultiPlus units does not make a difference. For
further guidance, refer to the Quattro system with 2 AC sources [4]
subchapter.
Installation
To install the control panel, you will need the following:
- Use an RJ45 UTP cable to connect the control panel to the inverter/charger. The cable is available in a variety of lengths (30cm to 30m) and is not included with the control panel.
- If you are utilising the generator support [3] functionality, two wires are required to connect the control panel to the transfer switch. Use wires with a thickness between 0.25 and 1.0mm². These wires are not included with the control panel.
- If the panel cannot be recess mounted, a ERROR: The requested URL could not be retrieved wall mounting box might be needed.
5.1. Mounting
There are three ways to mount the panel:
- Front recess – attach the metal plate to the front of the surface using four screws (incuded). Then, place the panel on the metal plate. See the below image.
- Rear recess – Secure the panel from behind with four M5 screws or bolts (not included). The metal plate is not used. See the below image.
- Wall mount – Use the ERROR: The requested URL could not be retrieved. Follow its installation guide.
For control panel
dimensions and mounting hole locations, refer to the Dimensions [14] chapter.
5.2. Inverter/charger connection
Use a regular straight UTP cable with RJ45 connectors to connect the control
panel to the inverter/charger or the inverter/charger system. If there are
multiple units, connect the control panel to any unit with an available unused
RJ45 port.
Note: In the case of a pre-VE.Bus multiple unit system, connect the
control panel to the master unit.
5.3. External transfer switch connection
If an external transfer switch is used, connect its auxiliary relay to the
screw connector terminals on the control panel’s backside.
When the auxiliary relay is open, the AC current limit can be adjusted by the
control panel knob. If the auxiliary relay is closed, the control panel sends
a preset generator AC current limit to the inverter/charger system. The
auxiliary relay is controlled by the external transfer switch.
Configuration
6.1. Setup menu
Configuration procedure:
-
To enter the configuration mode, press the button on the back of the control panel for about 4 seconds until the bottom LED in the right column starts blinking, indicating that the first parameter can be changed.
-
To change the value of a parameter, turn the knob until the displayed value is as required.
-
Press the configuration button to advance to the next parameter.
-
Pressing the configuration button, after the last parameter is selected, will exit configuration mode and activate all parameters.
So even if only one parameter needs adjustment, you will have to go through all parameters. -
When the configuration button is pressed, or during configuration, the inverter/charger(s) will switch to “Inverter only” mode.
The lower three LEDs in the left column on the control panel indicate which parameter is being adjusted according to the table below:
Menu item | LEDs | Parameter | Default | Range |
---|---|---|---|---|
1 | Scaling factor | 0 | 0 – 9 | |
2 | Generator current (A) | 16 | 0 – 198 | |
3 | Upper AC current limit for AC1 input (A) | 254 | 0 – 254 | |
4 | Upper AC current limit for AC2 input (A) | 254 | 0 – 254 | |
5 | Upper AC current limit for AC3 input (A) | 254 | 0 – 254 | |
6 | Upper AC current limit for AC4 input (A) | 254 | 0 – 254 |
= LED is off, = LED is blinking, = LED is on
6.2. Scaling factor
** This parameter only applies to pre-VE.Bus systems. Leave it at its
default value of 1 for VE.Bus systems.
For legacy pre-VE.Bus systems, refer to the Pre-VE.Bus scaling factor [12]
chapter.
6.3. Generator current limit
** This parameter only applies when an external transfer switch is used and
has no impact otherwise.
The generator AC current limit can be adjusted within the range of 0 to 198A,
with increments of 2A.
When configuring the generator AC current limit, be aware that not all
generators can operate at full load. Particularly, smaller 3000 rpm generators
from certain brands can overheat during extended full-load operation, and the
maximum current should be less than the rated maximum, while the AC current
limit for 1500 rpm generators can be set higher.
- For 3000 rpm generators, set to 70% of their rated maximum.
- For 1500 rpm generators, set to 90% of their rated maximum.
6.4. Upper AC input limit 1 to 4
To prevent overly high AC input current limits, the control panel provides an
upper AC input limit adjustment. For instance, when dealing with large or
multiple inverter/chargers working in parallel, the maximum feed-through
current might exceed the AC supply or circuit breaker capacity. Modifying the
upper AC input current limit ensures the shore current limit remains within a
specific range.
An extended VE.Bus system can have up to four AC inputs. Yet, a basic VE.Bus
MultiPlus system has one AC input. As such, only the upper limit for AC input
1 needs to be configured. The other AC input limits can be safely ignored.
6.4.1. Special display feature
Consider this scenario:
You have an inverter/charger system with two AC inputs, namely generator and
shore power. You want to prioritise the generator over shore power. You
connect the generator to AC input 1 and shore power to AC input 2. You do not
want the user to alter the generator AC input limit, so in the
inverter/charger settings, you disable the “overruled by remote” setting for
AC input 1, and enable it for AC input 2.
The control panel will behave as follows:
- When the generator is active, the control panel displays “AC1”.
- When the generator stopped and shore power is active, the panel alternates between displaying “AC2” and the current limit for
AC2. Yet, this alternating display might not match your preferences.
To resolve this:
A simpler approach is to show just the current limit value when AC input 2 is
active. This is enough to indicate the switch to shore power. To achieve this,
set all but one of the upper AC input limit parameters to zero. In this
example, the limits for AC1, AC3 and
AC4 should be set to zero. This adjustment eliminates the unwanted alternating
behavior.
6.5. Current limit overruled by remote
This setting exists in the inverter/charger. When enabled, the control panel
can modify the AC input current limit, and when disabled, it can not.
In the case of a Quattro, both inputs have an “overruled by remote” setting
and are independently configurable.
For details on configuring “overruled by remote,” consult the inverter/charger
manual.
6.6. Configuration example
Two examples are given to help you understand the setting of the parameters.
Two VE.Bus Multis 16A/230V + 4kVA gen. (3000 rpm) + external transfer switch.
Because this is a VE.Bus system, the scaling factor does not need to be set.
A 4kVA generator can supply a maximum current of 17.4A. Using a 70% safety
margin, we will set the generator current to 12A.
To set the configuration, do the following:
- Press and hold the configuration button until the bottom LED in the left column starts flashing. This means you entered the configuration mode, and you can change the scaling factor. As said, this parameter can be ignored in the case of VE.Bus Multis.
- Press the button to go to the next setting. The lower left LED will turn on, indicating that the generator current can be set.
- Turn the knob until the display indicates 12.
- Press the button to advance to the “Upper Shore limit for AC input 1” setting.
- If you want the maximum shore current the operator can set to be lower than 32A, you can change this value.
- Since the next 3 parameters (Upper Shore limit for AC input 2, 3 and 4) do not need to be configured, you can press the button 4 times to step through the settings and finalise the configuration.
Operation
The control panel controls and monitors the inverter/charger system.
The control panel is active as soon as the inverter/charger system is switched
on.
ID | Description |
---|---|
A | Charger LEDs: mains on, bulk, absorption and float. |
B | Light sensor, used to automatically dim the LED brightness. |
C | Inverter LEDs: inverter on, overload, low battery and temperature. |
D | Display, showing the AC input current limit, AC source or VE.Bus errors. |
E | AC current limiter knob, use to adjust the AC input current limit. |
F | On / off / charger-only switch, use to turn the inverter/charger on, off or |
to charger-only mode.
7.1. Turning the system on and off
Use the switch on the control panel to switch the system on, off or to
charger-only operation.
7.2. Adjusting AC input current limit
Adjust the AC current limit using the control knob. The display shows the set
limit, and in case of multiple AC inputs, the display also shows the active AC
input source (AC2, AC3, AC4).
When PowerAssist is enabled in the inverter/charger system, a minimum AC input
current limit value applies. See the table below.
If set below this value, the inverter/charger stops charging, opens its
internal transfer relay, disconnects from the AC supply and starts inverting.
Current limits adjust in 0.5A steps under 10A, and 1A steps over 10A. For
instance, an 11.1A limit rounds to 12A.
The control panel prevents setting a limit below the inverter/charger system’s
minimum AC current. If the AC input current limit needs to be set to 0A (below
the inverter/charger’s limit), quickly turn the knob anticlockwise. The
control panel display shows 0.0,
and the inverter/charger(s) will stop charging and start inverting. Turn
clockwise to revert back to the minimum AC current limit.
AC voltage (V) rating| Power (VA) rating| Minimum configurable AC
current limit (A)
---|---|---
120| 2000| 5.5 – 8.4
3000| 7.5 – 9.5
5000| 13.0 – 13.4
10000| 18.5
230| 500 – 1200| 2.4
1600| 2.4 – 2.8
2000| 2.4 – 4.5
3000| 3.0 – 4.5
5000| 3.9 – 6.4
8000| 7.6 – 10.5
10000| 8.6 – 10.5
15000| 10.1 – 14.5
*) The exact value depends on the inverter/charger model. Refer to the “Minimum input current limits” spreadsheet, located in the
“VE.Bus (Multies, Inverters and Quattros)” folder in the firmware section on
the Victron
Professional
website.
7.3. LED brightness
For your comfort, the light sensor auto-adjusts LED brightness. As ambient light drops the LEDs dim to a more comfortable level and save power.
Backward compatibility with legacy pre-VE.Bus units
The control panel is backwards compatible with legacy (pre-VE.Bus)
inverter/chargers running firmware versions 15xxyyy, 17xxyyy, and 18xxyyy. The
transition from pre-VE.Bus to VE.Bus occurred from late 2007 to mid-2008.
For pre-VE.Bus systems, the control panel operation and setup align with the
manual, except that the control panel does not automatically adapt to the
system. The default setting is for a standalone inverter/charger with a 16A
transfer switch, but if a different AC transfer current applies, the Scaling
factor [8] needs to be adjusted.
8.1. System examples pre-VE.Bus
Pre-VE.Bus system with 1 AC source:
The control panel must be scaled (matched to the system) when it is used with
pre-VE.Bus systems. This can be done by changing the “scaling factor”
parameter. For instructions, refer to the Scaling factor [8] chapter.
Once the scaling is accurately configured, proceed to set up any other
relevant parameters. For instructions, refer to the Configuration [7] chapter.
Pre-VE.Bus system with 2 AC sources:
For a pre-VE.Bus system with 2 AC sources, an external transfer switch (VE
Transfer Switch) is essential.
The control panel must be scaled (matched to the system) when it is used with
pre-VE.Bus systems. This can be done by changing the “scaling factor”
parameter. For instructions refer to the Scaling factor [8] chapter.
Once the scaling factor is configured, follow the installation process similar
to using a VE.Bus system with an external transfer switch. Refer to the
MultiPlus system with 2 AC sources and transfer switch [4] chapter for
instructions.
8.2. Configuration
Configuration is the same as described in this manual, with the exception that
a scaling factor needs to be set up.
To set up the scaling factor, see the next paragraph, and for configuration of
the remaining parameters, see the Configuration [7] chapter
8.2.1. Pre-VE.Bus scaling factor
*** This parameter only applies to pre-VE.Bus systems. Leave it at its
default value of 1 for VE.Bus systems.
The scaling factor aligns the control panel AC current with the system AC
current and is exclusive to pre-VE.Bus inverter/ chargers.
Begin by calculating the scaling factor as directed in this chapter.
Afterwards, move on to configuring the scaling factor. For guidance on
configuration, consult the Setup menu [7] chapter.
Scaling factor formula:
Scaling factor = (NrOfDevices DeviceType) – 1
- DeviceType: 1 = 16A unit, 2 = 30A unit.
- NrOfDevices: all units, including the master unit.
Examples:
- One 16A unit: Scaling factor is: (1 * 1) – 1 = 0
- Two 30A units in parallel: Scaling factor is: (2 * 2) – 1 = 3
- Four 30A units in parallel: Scaling factor is: (4 * 2) – 1 = 7
- Six 30A units in 3-phase (2 paralleled units per phase): Scaling factor is: (2 * 2) – 1 = 3
Important:
- When configuring a non-zero scaling factor in the control panel, do not specify the number of slaves in the VEConfigure software. Instead, set the slave count to zero.
- In a split-phase or 3-phase setup, the NrOfDevices reflects the number of devices per phase. So for a 3-phase system consisting of 6 units (2 per phase), the NrOfDevices is 2.
8.2.2. Configuration example pre-VE.Bus
Four pre-VE.Bus Multis 30A/120V + 13kVA gen. (1500 rpm) + external transfer
switch.
For this configuration, the scaling factor must be calculated. The NrOfDevices
is 4, the DeviceType is 2, so the scaling factor is (4 x 2) – 1 = 7.
A 13kVA generator 120V can supply a maximum current of 108.3A. Using a 90%
safety margin, we will set the generator current to 98A.
To set the configuration, do the following:
- Press and hold the configuration button until the bottom LED in the left column starts flashing. This means you entered the configuration mode, and you can change the scaling factor.
- Turn on the knob until the display indicates 7.
- Press the button to go to the next setting. The lower left LED will turn on, indicating that the generator current can be set.
- Turn on the knob until the display indicates 98.
- Press the button to advance to the “Upper Shore limit for AC input 1” setting.
- You probably want the maximum shore current the operator can set to be lower than 128A, so turn the knob until the display indicates a proper maximum shore current.
- Since the next 3 parameters (Upper Shore limit for AC input 2, 3 and 4) do not need to be configured, you can press the button 4 times to step through the settings and finalise the configuration.
Dimensions
|
---|---
|
Dimensions
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>