SKYDANCE DT-B DALI AC Triac Dimmer Instruction Manual

June 8, 2024
SKYDANCE

SKYDANCE-DT-B-DALI-AC-Triac-Dimmer-logo

SKYDANCE DT-B DALI AC Triac Dimmer

SKYDANCE-DT-B-DALI-AC-Triac-Dimmer-product-image

DALI AC Triac Dimmer
Model No.: DT-B
1DALI address / 1 Channel output / Trailing edge

Features

  • AC phase-cut misfit DALI dimmer, one DALI address, one channel output.
  • Trailing edge dimmer.
  • The minimum brightness is adjustable.
  • In accordance with DALI standard protocol 101, 102, 205 (IEC 62386) and in compliance with DALI products from other international incorporation.
  • DALI address can be automatically assigned by DALI master.
  • To dim and switch single color dimmable LED lamps, traditional incandescent and halogen lights.
  • Over-heat protection, Overload protection, recover automatically.

Technical Parameters

Input and Output

Input voltage| 100-240VAC
Output voltage| 100-240VAC
Output current| Max 1.5A
Output power| 150-360W

Environment

Operation temperature Ta: -30 OC ~ +55 OC
Case temperature (Max.) Ta: +70 OC
IP rating IP20

Package

Size| L75x W75 x H40mm
Gross weight| 0.981kg
Warranty
Warranty| 5 years

Compatible Load Types

Load Type Maximum Load Remarks
Dimmable LED lamps 200W @ 220V
100W @ 110V Due to variety of LED lamp designs, maximum number of LED lamps

is further dependent on power factor result when connected to dimmer.
Triac Dimmable LED drivers| 200W @ 220V
100W @ 110V| Maximum permitted number of drivers is 200W divided by driver nameplate power rating, and make sure the surge current is no more than 2 times 65A.
Incandescent lighting, HV Halogen lamps| 400W @ 220V

200W @ 110V

|

Mechanical Structures and Installations

SKYDANCE-DT-B-DALI-AC-Triac-Dimmer-02

Wiring Diagram

SKYDANCE-DT-B-DALI-AC-Triac-Dimmer-03

Caution:
Please carefully ensure all wire connections and polarities are correct and secure before applying power, otherwise this controller will be damaged.
Note: When calculating the maximum number of load lamps or drivers, the input power or input current parameters of a single lamp or driver must be used, the output power parameters can not be used.
In addition, the maximum surge current of the dimmer is 65A, the sum of surge current of multiple dimmable LED drivers should not exceed 2 times. otherwise, the product will be overloaded and damaged.

Operation

Minimum brightness setting

The minimum brightness of the device can be set or deleted by press the “SET” button on the dimmer.

  • Recall minimum brightness:
    Short press “SET ” button on the dimmer, LED indicator ash one, the light output the minimum brightness.

  • Setting minimum brightness:
    Adjust the brightness to a desired minimum level, then press and hold down the “SET ” button 2s until the LED indicator ash one, the current brightness is set as the minimum brightness.
    The light can only be dimmable between this minimum brightness and maximum brightness.

  • Delete minimum brightness:
    Adjust the brightness to maximum level, then press and hold down the “SET ” button 2s until the LED indicator ash one, the minimum brightness setting is deleted.

DALI address assigned by DALI masters
DALI address can also be assigned by DALI Master controller automatically.
Please refer to user manuals of compatible DALI Masters for specific operations.

Safety & Warnings

  • DO NOT install with power applied to device.
  • DO NOT expose the device to moisture.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals