EATON AG II IT DN120xxR AC Surge Protection Device Instruction Manual

June 3, 2024
EATON

EATON LOGO

EATON AG II IT DN120xxR AC Surge Protection Device

Eaton Corporation, 1000 Eaton Boulevard, Cleveland, OH 44122, United States
© 2022 by Eaton, www.eaton.com

INSTRUCTION

Please read the following before installing your Surge Protective Device:

  • Verify the system voltage and configuration on the label is appropriate for the application.
  • Risk of Electric Shock – Installation and maintenance should be performed by qualified personnel only.
  • Disconnect from energized circuits before installing or servicing.
  • Safety rules and regulations applicable to all devices connected to power lines should always be followed. National standards and safety regulations must be followed.
  • The external mechanical integrity of the device must be checked before installation. Products with visible damage should not be installed.
  • Its use is only permitted within the limits shown and stated in these installation instructions. Opening or tampering with the device invalidates the warranty.
  • Connecting leads shall be kept as short as possible, without loops and not exceed 0.5m in total length per SPD.
  • The minimum distance of the SPD from any grounded conductive surface at which the SPD can be installed is 0 mm.
  • This is open type SPD intended for installation within a suitable enclosure in accordance with the National Electrical Code, ANSI/NFPA 70.

PROTECTION CONFIGURATIONS

DIMENSIONS

EATON AG II IT DN120xxR AC Surge Protection
Device-2

For UL Listed products left G Conductor Terminal is covered/closed

TECHNICAL DATA

TECHNICAL DATA| Product name| AG II IT DN120xxR| AG II IT DN240xxR| AG II IT DN277xxR| AG II IT DN400xxR| AG II IT DN600xxR
---|---|---|---|---|---|---
Uo /Un| AC (50-60Hz)| 120 V + 10%| 240 V + 6%| 277 V + 10%| 400V + 10%| 600 V

  • 10%
    UC/MCOV| AC| 150V| 300V| 350V| 480V| 750V
    Up| 1250 V| 1500 V| 1750 V| 2300 V| 3400 V
    VPR| 600 V| 900 V| 1000 V| 1500 V| 2500 V
    In (8/20)| 20 kA| 20 kA| 20 kA| 20 kA| 20 kA
    In (8/20) (per UL 1449)| 20 kA| 20 kA| 20 kA| 20 kA| 20 kA
    Imax (8/20)| 50 kA| 50 kA| 50 kA| 50 kA| 35 kA
    ISCCR / Backup fuse (per IEC 61643-11)| 50 kA / 250A gG fuse 25 kA / 315A gG fuse| 50 kA / 250A gG fuse 25 kA / 315A gG fuse| 50 kA / 250A gG fuse 25 kA / 315A gG fuse| 50 kA / 250A gG fuse 25 kA / 315A gG fuse| 50 kA / 250A gG fuse 25 kA / 315A gG fuse
    SCCR (per UL 1449)| 200 kA| 150 kA| 200 kA| 200 kA| 200 kA
    IPE| ≤ 0.400 mA| ≤ 0.400 mA| ≤ 0.400 mA| ≤ 0.400 mA| ≤ 0.400 mA
    Ta| -40 ºF to +158 ºF / 185 ºF per UL 1449 [-40 ºC to +70 ºC / 85 ºC per UL 1449]
    RH| 5 %…95 %
    Mounting| 35mm DIN rail, EN 60715
    Altitude (max)| 13123 ft [4000 m]
    Location / Number of ports / IP| Indoor / 1 / 20 (built-in)
    Warranty| 1 year
    Terminals:
    (solid, stranded) 18 mm| ø min 14 AWG / ø max 6 AWG per UL 1449 [ø min 1.5 mm2 / ø max 35 mm2]
     (flexible) 18 mm| ø min 14 AWG / ø max 6 AWG per UL 1449 [ø min 1.5 mm2 / ø max 35 mm2]
    RC push in (solid)   10 mm| ø min 30 AWG / ø max 10 AWG per UL 1449 [ø min 0.25 mm2 / ø max 1.5 mm2 ]

REMOTE CONTACT STATES

RC contact(s) states 11- 12 11-14
SPD module(s) functional / installation is protected Closed Geschlossen Open

Offen

SPD module(s) unplugged or non-functional| Open

Offen

| Closed Geschlossen

BACKUP FUSE

Protection against short circuit

NOTE: If the ISCCR is declared higher than 50kA up 100 kA use 160A gG fuse.

Conductor Dimensioning

PLUG REPLACEMENT

Step 1: Unlock

Step 2: Pull module out

03.2022a / All Rights Reserved
For more information, please contact the Eaton Technical Resource Center at 1-800-809-2772, option 4, option 2. You may submit inquiries via email to spd@eaton.com and you can find more information at eaton.com/aegis.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals