EATON AG II IT DN120xxR AC Surge Protection Device Instruction Manual
- June 3, 2024
- EATON
Table of Contents
EATON AG II IT DN120xxR AC Surge Protection Device
Eaton Corporation, 1000 Eaton Boulevard, Cleveland, OH 44122, United States
© 2022 by Eaton, www.eaton.com
INSTRUCTION
Please read the following before installing your Surge Protective Device:
- Verify the system voltage and configuration on the label is appropriate for the application.
- Risk of Electric Shock – Installation and maintenance should be performed by qualified personnel only.
- Disconnect from energized circuits before installing or servicing.
- Safety rules and regulations applicable to all devices connected to power lines should always be followed. National standards and safety regulations must be followed.
- The external mechanical integrity of the device must be checked before installation. Products with visible damage should not be installed.
- Its use is only permitted within the limits shown and stated in these installation instructions. Opening or tampering with the device invalidates the warranty.
- Connecting leads shall be kept as short as possible, without loops and not exceed 0.5m in total length per SPD.
- The minimum distance of the SPD from any grounded conductive surface at which the SPD can be installed is 0 mm.
- This is open type SPD intended for installation within a suitable enclosure in accordance with the National Electrical Code, ANSI/NFPA 70.
PROTECTION CONFIGURATIONS
DIMENSIONS
For UL Listed products left G Conductor Terminal is covered/closed
TECHNICAL DATA
TECHNICAL DATA| Product name| AG II IT DN120xxR| AG II IT
DN240xxR| AG II IT DN277xxR| AG II IT DN400xxR| AG II IT
DN600xxR
---|---|---|---|---|---|---
Uo /Un| AC (50-60Hz)| 120 V + 10%| 240 V + 6%| 277 V + 10%| 400V + 10%| 600 V
- 10%
UC/MCOV| AC| 150V| 300V| 350V| 480V| 750V
Up| 1250 V| 1500 V| 1750 V| 2300 V| 3400 V
VPR| 600 V| 900 V| 1000 V| 1500 V| 2500 V
In (8/20)| 20 kA| 20 kA| 20 kA| 20 kA| 20 kA
In (8/20) (per UL 1449)| 20 kA| 20 kA| 20 kA| 20 kA| 20 kA
Imax (8/20)| 50 kA| 50 kA| 50 kA| 50 kA| 35 kA
ISCCR / Backup fuse (per IEC 61643-11)| 50 kA / 250A gG fuse 25 kA / 315A gG fuse| 50 kA / 250A gG fuse 25 kA / 315A gG fuse| 50 kA / 250A gG fuse 25 kA / 315A gG fuse| 50 kA / 250A gG fuse 25 kA / 315A gG fuse| 50 kA / 250A gG fuse 25 kA / 315A gG fuse
SCCR (per UL 1449)| 200 kA| 150 kA| 200 kA| 200 kA| 200 kA
IPE| ≤ 0.400 mA| ≤ 0.400 mA| ≤ 0.400 mA| ≤ 0.400 mA| ≤ 0.400 mA
Ta| -40 ºF to +158 ºF / 185 ºF per UL 1449 [-40 ºC to +70 ºC / 85 ºC per UL 1449]
RH| 5 %…95 %
Mounting| 35mm DIN rail, EN 60715
Altitude (max)| 13123 ft [4000 m]
Location / Number of ports / IP| Indoor / 1 / 20 (built-in)
Warranty| 1 year
Terminals:
(solid, stranded) 18 mm| ø min 14 AWG / ø max 6 AWG per UL 1449 [ø min 1.5 mm2 / ø max 35 mm2]
(flexible) 18 mm| ø min 14 AWG / ø max 6 AWG per UL 1449 [ø min 1.5 mm2 / ø max 35 mm2]
RC push in (solid) 10 mm| ø min 30 AWG / ø max 10 AWG per UL 1449 [ø min 0.25 mm2 / ø max 1.5 mm2 ]
REMOTE CONTACT STATES
RC contact(s) states | 11- 12 | 11-14 |
---|---|---|
SPD module(s) functional / installation is protected | Closed Geschlossen | Open |
Offen
SPD module(s) unplugged or non-functional| Open
Offen
| Closed Geschlossen
BACKUP FUSE
Protection against short circuit
NOTE: If the ISCCR is declared higher than 50kA up 100 kA use 160A gG fuse.
Conductor Dimensioning
PLUG REPLACEMENT
Step 1: Unlock
Step 2: Pull module out
03.2022a / All Rights Reserved
For more information, please contact the Eaton Technical Resource Center at
1-800-809-2772, option 4, option 2. You
may submit inquiries via email to spd@eaton.com and
you can find more information at eaton.com/aegis.
References