INSTRUCTION

Please read the following before installing your Surge Protective Device:

  • Verify the system voltage and configuration on the label is appropriate for the application.
  • Risk of Electric Shock – Installation and maintenance should be performed by qualified personnel only.
  • Disconnect from energized circuits before installing or servicing.
  • Safety rules and regulations applicable to all devices connected to power lines should always be followed. National standards and safety regulations must be followed.
  • The external mechanical integrity of the device must be checked before installation. Products with visible damage should not be installed.
  • Its use is only permitted within the limits shown and stated in these installation instructions. Opening or tampering with the device invalidates the warranty.
  • Connecting leads shall be kept as short as possible, without loops and not exceed 0.5m in total length per SPD.
  • The minimum distance of the SPD from any grounded conductive surface at which the SPD can be installed is 0 mm.
  • This is open type SPD intended for installation within a suitable enclosure in accordance with the National Electrical Code, ANSI/NFPA 70.

PROTECTION CONFIGURATIONS

DIMENSIONS

EATON AG II IT DN120xxR AC Surge Protection
Device-2

For UL Listed products left G Conductor Terminal is covered/closed

TECHNICAL DATA

TECHNICAL DATA| Product name| AG II IT DN120xxR| AG II IT DN240xxR| AG II IT DN277xxR| AG II IT DN400xxR| AG II IT DN600xxR
---|---|---|---|---|---|---
Uo /Un| AC (50-60Hz)| 120 V + 10%| 240 V + 6%| 277 V + 10%| 400V + 10%| 600 V

  • 10%
    UC/MCOV| AC| 150V| 300V| 350V| 480V| 750V
    Up| 1250 V| 1500 V| 1750 V| 2300 V| 3400 V
    VPR| 600 V| 900 V| 1000 V| 1500 V| 2500 V
    In (8/20)| 20 kA| 20 kA| 20 kA| 20 kA| 20 kA
    In (8/20) (per UL 1449)| 20 kA| 20 kA| 20 kA| 20 kA| 20 kA
    Imax (8/20)| 50 kA| 50 kA| 50 kA| 50 kA| 35 kA
    ISCCR / Backup fuse (per IEC 61643-11)| 50 kA / 250A gG fuse 25 kA / 315A gG fuse| 50 kA / 250A gG fuse 25 kA / 315A gG fuse| 50 kA / 250A gG fuse 25 kA / 315A gG fuse| 50 kA / 250A gG fuse 25 kA / 315A gG fuse| 50 kA / 250A gG fuse 25 kA / 315A gG fuse
    SCCR (per UL 1449)| 200 kA| 150 kA| 200 kA| 200 kA| 200 kA
    IPE| ≤ 0.400 mA| ≤ 0.400 mA| ≤ 0.400 mA| ≤ 0.400 mA| ≤ 0.400 mA
    Ta| -40 ºF to +158 ºF / 185 ºF per UL 1449 [-40 ºC to +70 ºC / 85 ºC per UL 1449]
    RH| 5 %…95 %
    Mounting| 35mm DIN rail, EN 60715
    Altitude (max)| 13123 ft [4000 m]
    Location / Number of ports / IP| Indoor / 1 / 20 (built-in)
    Warranty| 1 year
    Terminals:
    (solid, stranded) 18 mm| ø min 14 AWG / ø max 6 AWG per UL 1449 [ø min 1.5 mm2 / ø max 35 mm2]
     (flexible) 18 mm| ø min 14 AWG / ø max 6 AWG per UL 1449 [ø min 1.5 mm2 / ø max 35 mm2]
    RC push in (solid)   10 mm| ø min 30 AWG / ø max 10 AWG per UL 1449 [ø min 0.25 mm2 / ø max 1.5 mm2 ]

REMOTE CONTACT STATES

RC contact(s) states 11- 12 11-14
SPD module(s) functional / installation is protected Closed Geschlossen Open

Offen

SPD module(s) unplugged or non-functional| Open

Offen

| Closed Geschlossen

BACKUP FUSE

Protection against short circuit

NOTE: If the ISCCR is declared higher than 50kA up 100 kA use 160A gG fuse.

Conductor Dimensioning

PLUG REPLACEMENT

Step 1: Unlock

Step 2: Pull module out

03.2022a / All Rights Reserved
For more information, please contact the Eaton Technical Resource Center at 1-800-809-2772, option 4, option 2. You may submit inquiries via email to spd@eaton.com and you can find more information at eaton.com/aegis.