Descriptions of Components

DELTA BX6.3_EX100 Battery Storage System - Figure 1

Object Qty Description
Delta BX6.3_EX100 1 Battery pack
,2, Quick Installation
Guide 1 The Instruction to provide the information of safety, installation

and specification.
| Wiring Cover| 1| Protective cover to prevent users from touching the power cable
| Wire| 3| To connect with BX6.3 series
| DC Cable| 2| DC String inputs

Warning

| Do not open this product or insert tools due to shock and fire hazard which may cause injury.
---|---
| When installing this product you must adhere to the following instructions:
● The product is intended to be installed and operated by qualified personnel or service personnel only.
● Do not power up the device before installation is complete.
● All circuit breakers must be in the OFF position before commencing installation.
| ● Do not install BX6.3_EX100 near or on flammable surfaces.
● Please mount BX6.3_EX100 tightly on a solid / smooth surface.
● Install BX6.3_EX100 in a location that prevents damage from flooding.
● Do not expose BX6.3_EX100 to ambient temperatures above 60°C or below -20°C.
● Operating or storing BX6.3_EX100 in temperatures outside its specified range might cause damage to BX6.3_EX100.
| Danger to life through electric shock
Potentially fatal voltage is applied to the unit during operation.
Voltage persists 60 seconds after disconnection of power supply.
Never open the unit. The unit contains no components that must be maintained or repaired by the operatoror installer.
Opening the housing will void the warranty.

Dimensions and Interface Overview

DELTA BX6.3_EX100 Battery Storage System - Figure 2

Installation

DELTA BX6.3_EX100 Battery Storage System - Figure 3

  • Please refer to regulation AS/NZS 5139:2019 for detail installation space requirement. To avoid extra fireproof cement sheeting installation requirement, it is recommended to keep at least 300mm between the wall and BX.

DELTA BX6.3_EX100 Battery Storage System - Figure 4

Insert Rawlplug

DELTA BX6.3_EX100 Battery Storage System - Figure 5

  1. Drill 4 holes with Φ16 mm diameter in dimension 490mm x 200mm.
  2. Insert Rawlplugs into the holes.
  3. Fix the foot of BX6.3_EX100 firmly.
  4. Tighten the nut to stretch the rawlplug.DELTA BX6.3_EX100 Battery Storage System - Figure 6
Conduit hole(mm) PF pipe(mm)
Φ34 Φ28

Technical Data

Type Li-ion
Battery Module Samsung SDI 41J (21700)
Nominal Battery Capacity 6.3 kWh
Usable Battery Capacity 6.17 kWh
Typical Voltage DC 200 V
Voltage Range DC 175 – 228 V
Min Output Voltage DC 175V
Max Output Voltage DC 228V
Depth of Discharge (DoD) 98%
Rated DC Power 3000VA
Max Charge/Discharge Current 25A
Dimensions (W x H x D) 520 × 600 × 230 mm
Operating temperature -10°C ~ 45°C
Weight 60 kg
Environmental category Indoor / Outdoor
Protection degree IP65 (Electronics)
Relative humidity 0% – 95% non-condensing.

Expanding the Battery Pack with DC(BT+/-) Cables

DELTA BX6.3_EX100 Battery Storage System -
Figure 8

DELTA ELECTRONICS, INC.
39 Sec. 2 HuanDong Road,
ShanHua Dist., Tainan City 74144,
Taiwan
TEL 886-6-5056565
FAX 886-6-5051919
http://www.deltaww.com