MEAN WELL HDR-100 Series 85 to 100W Ultra Slim Step Shape DIN Rail Instructions
- June 3, 2024
- MEAN WELL
Table of Contents
MEAN WELL HDR-100 Series 85 to 100W Ultra Slim Step Shape DIN Rail Instructions
Features
Ultra slim design with 70mm(4SU) width
- Universal input 85~264VAC(277VAC operational)
- No load power consumption<0.3W
- lsolation class Ⅱ
- Pass LPS (Limited power source) for Blank type
- DC output voltage adjustable
- Protections : Short circuit / Overload / Over voltage
- Cooling by free air convection (working temperature:-30~+70°C)
- DIN rail TS-35/7.5 or 15 mountable
- Over voltage category Ⅲ
- LED indicator for power on
- 3 years warranty
Applications
- Household control system
- Building automation
- lndustrial control system
- Factory automation
- Electro-mechanical apparatus
Description
HDR-100 is one economical ultra slim 100W DlN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 70mm(4SU) in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 85VAC to 264VAC(277VAC operational) and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. HDR-100 is designed with plastic housing that it can effectively prevent user from electric hazards. With working efficiency up to 90%, the entire series can operate at the ambient temperature between -30℃ and 70℃ under air convection. The complete protection functions and relevant certificates for home automations and industrial control apparatus (lEC62368-1,UL508, UL62368-1, BS EN/EN61558-2-16)make HDR-100 a very competitive power supply solution for household and industrial applications.
Model Encoding
Type
|
Description
|
Note
---|---|---
Blank
|
92W max, Pass LPS with a narrower output adjustable range
|
ln stock
N
| 100W max, Non-LPS with a wider output adjustable range|
ln stock
SPECIFICATION
MODEL| HDR-100-12| HDR-100-12N| HDR-100-15|
HDR-100-15N| HDR-100-24| HDR-100-24N| HDR-100-48|
HDR-100-48N
---|---|---|---|---|---|---|---|---
OUTPUT| DC VOLTAGE| 12V| 15V| 24V| 48V
RATED CURRENT| 7.1A| 7.5A| 6.13A| 6.5A| 3.83A| 4.2A| 1.92A| 2.1A
CURRENT RANGE| 0 ~ 7.1A| 0 ~ 7.5A| 0 ~ 6.13A| 0 ~ 6.5A| 0 ~ 3.83A| 0 ~
4.2A| 0 ~1.92A| 0 ~ 2.1A
RATED POWER| 85.2W| 90W| 92W| 97.5W| 92W| 100.8W| 92.2W| 100.8W
RIPPLE & NOISE (max.) **Note.2| 120mVp-p| 120mVp-p| 150mVp-p| 240mVp-p
VOLTAGE ADJ. RANGE| Pass LPS| 12 ~ 13V| 15 ~ 17V| 24 ~
25.5V| 48 ~ 48.7V
Non LPS| 12~ 13.8V| 13.5 ~ 18V| 21.6 ~ 29V| 43.2 ~ 55.2V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 500ms, 60ms/230VAC 500ms, 60ms/115VAC at full
load
HOLD UP TIME (Typ.)| 30ms/230VAC 12ms/115VAC at full load
INPUT| VOLTAGE RANGE| 85 ~ 264VAC (277VAC operational ) 120
~ 370VDC (390VDC operational )
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 88%| 89%| 90%| 90%
AC CURRENT (Typ.)| 3A/115VAC 1.6A/230VAC
INRUSH CURRENT (Typ.)| COLD START 35A/115VAC 70A/230VAC
PROTECTION| OVERLOAD| HDR-100 : 102 ~ 110% rated output power ;
HDR-100-xxN : 105 ~ 150% rated output power
Hiccup mode when output voltage <50%, recovers automatically after fault
condition is removed Constant current limiting within 50% ~100% rated output
voltage, recovers automatically after fault condition is removed
OVER VOLTAGE| 14.2 ~ 16.2V| 18.8 ~ 22.5V| 30 ~ 36V| 56.5 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
ENVIRONMENT| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃) RH non-condensing
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X,
Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE| 2000 meters
OVER VOLTAGE CATEGORY| Ⅲ; According to EN61558, EN50178,EN60664-1,
EN62477-1; altitude up to 2000 meters
| SAFETY STANDARDS| UL62368-1, UL508, TUV BS EN/EN61558-2-16, BS
EN/EN61558-1, IEC62368-1, EAC TP TC 004, BSMI CNS14336-1 approved; Design
refer to TUV BS EN/EN62368-1
WITHSTAND VOLTAGE| I/P-O/P:4KVAC
ISOLATION RESISTANCE| I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032(CISPR32), CNS13438| Class B
Radiated| BS EN/EN55032(CISPR32), CNS13438| Class B
Harmonic Current (Note 5)| BS EN/EN61000-3-2| Class A
SAFETY &**
EMC
(Note 5 )
| Voltage Flicker| BS EN/EN61000-3-3| ——-
EMC IMMUNITY| BS EN/EN55024, BS EN/EN61000-6-2, BS EN/EN61204-3
Parameter| Standard| Test Level /Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, criteria A
EFT/Burest| BS EN/EN61000-4-4| Level 3, criteria A
Surge| BS EN/EN61000-4-5| Level 4,2KV/L-N, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, criteria A
Voltage Dips and interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30%
dip 25 periods,
>95% interruptions 250 periods
OTHERS| MTBF| 856.5K hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 709054.5mm (WHD)
PACKING| 0.27Kg; 48pcs/14Kg/1.06CUFT
NOTE|
- All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
- Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor.
- Tolerance : includes set up tolerance, line regulation and load regulation.
- Harmonic current test at 90% load for HDR-100-xxN.
- The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMl testing of component power supplies.” (as available on http://www.meanwell.com)
- The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
Derating Curve VS Ambient Temperature
Output Derating VS Input Voltage
Mechanical Specification
(Unit: mm , tolerance ± 0.5mm)
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Terminal Pin No. Assignment
Pin No.
| Assignment| Pin No.| Assignment
---|---|---|---
1
|
AC/L
|
3,4
|
-V
2| AC/N| 5,6|
+V
Installation Manual
Please refer to : http://www.meanwell.com/manual.html
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>