TRANE Foundation 3 to 5 Tons Packaged Rooftop Units Cooling and Gas/Electric User Manual

June 3, 2024
Trane

TRANE-logo

TRANE Foundation 3 to 5 Tons Packaged Rooftop Units Cooling and

Gas/Electric

TRANE-Foundation-3-to-5-Tons-Packaged-Rooftop-Units-Cooling-and-Gas-
Electric-product

Model Number/Used With

  • EBC Packaged Cooling, Electric Heat (Optional)
  • GBC Packaged Cooling, Gas Heat

SAFETY WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air- conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

3 to 5 tons of packaged rooftop performance data

Nominal Size (Ton) 3 4 5

Cooling Performance (a)
Gross Cooling Capacity| 37,000| 51,100| 59,000
AHRI Net Cooling Capacity| 36,000| 49,500| 57,500
Nominal Airflow CFM / AHRI Rated CFM| 1200 / 1200| 1600 / 1600| 2000 / 1600
EER(b) / EER2(c)| 12 / 10.6| 12 / 10.6| 12 / 10.6
Seasonal Energy Efficiency Ratio (SEER)(d) / (SEER2)(c)| 14 / 13.4| 14 / 13.4| 14 / 13.4
Gas Heating Performance
Low Heat (Input/Output) – (Btu/h)| 72,000 /

57,600

| 72,000 /

57,600

| 72,000 /

57,600

Medium Heat (Input/Output) – (Btu/h)| 100,000 /

80,000

| 115,000 /

92,000

| 115,000 /

92,000

Other Information
Net Weight (Lbs) – Gas Heat| 524| 566| 586
Net Weight (Lbs) – Electric Heat| 473| 516| 536
Filters – Type Furnished| Throwaway| Throwaway| Throwaway
Number and Size Recommended| (4) 16x16x2| (4) 16x16x2| (4) 16x16x2

  • Cooling Performance is rated at 95°F ambient, 80°F entering the dry bulb, and 67°F entering the wet bulb.
  • EER is rated at AHRI conditions and in accordance with AHRI standard 210/240-2017.
  • EER2 and SEER2 is rated at AHRI conditions and calculated in accordance with AHRI Standard 210/240-2023 at airflow and net cooling capacity not shown.
  • Seasonal Energy Efficiency Ratio (SEER) is rated in accordance with AHRI standard 210/ 240 and DOE test procedures.

List of Options

Note:
Most Factory Installed Options are available for downflow air discharge units only. Verify with the ordering system for availability.

Factory Installed Options Field Installed Options
Barometric Relief(a) (Downflow Low Leak Economizer Only) Barometric Relief

(Standard and Low Leak Economizer, Downflow and Horizontal Configuration)
Complete Coat™ Microchannel Condenser Coil| Crankcase Heater
Condensate Overflow Switch| Demand Control Ventilation with CO2 Sensor
Economizer (Downflow)(a)| Economizer (Horizontal)
Electric Heaters| Frostat™
Low Leak Economizer – Downflow| Low Ambient Kit
Manual Outside Air Dampers| Low Leak Economizer – Horizontal
Motorized Outside Air Dampers| LP Conversion Kit
Oversized Motor| Powered Exhaust
Reference or Comparative Enthalpy Economizer| Remote Potentiometer
Stainless Steel Heat Exchanger with 10 Year Warranty| Roof Curb
Through the Base Electrical Access| Thermostat
Through the Base Gas Piping| Tool-less Hail Guard
Unit Mounted Non-Fused Disconnect Switch(b)|

  • Some field set up required.
  • Must be ordered with Through-the-Base Electrical option.

Unit MCA and MOP electrical data

(standard indoor fan motor – cooling or gas heat)

E/GBC Volts MCA (a) MOP

036

| 208–230| 19.5| 25
460| 10.5| 15
575| 6.8| 15
380(b)| 10.0| 15

048

| 208–230| 23.6| 35
460| 11.0| 15
575| 8.1| 15
380(b)| 13.0| 20

060

| 208–230| 26.4| 40
460| 12.9| 20
575| 9.2| 15
380(b)| 13.6| 20

  • Values do not include Power Exhaust accessory.
  • Unit will operate reliably at 400 Vac.

Unit indoor fan data

E/GBC Volts Standard (HP – RPM) Oversized (HP – RPM)

036

| 208-230|

1 – 1725

|

2 – 1725

460
575
380(a)

048

| 208-230|

1 – 1725

|

2 – 1725

460
575
380(a)

060

| 208-230|

1 – 1725

|

2 – 1725

460
575
380(a)

  • Unit will operate reliably at 400 Vac.

Unit dimensional data

  3 to 5 Tons
Unit Length UL 76.814 in.
Unit Width UW 47.934 in.
Unit Height UH 42.004 in.
Curb Length CL 70.871 in.
Curb Width CW 41.983 in.
Supply Length SL (a) 21.060 in.
Supply Width SW (a) 14.000 in.
Return Length RL (a) 32.188 in.
Return Width RW (a) 14.430 in.
  • Dimensions are for curb openings and not duct inserts. Reference the product catalog for duct insert dimensions.

TRANE-Foundation-3-to-5-Tons-Packaged-Rooftop-Units-Cooling-and-Gas-
Electric-fig-1

Trane and American Standard create comfortable, energy-efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.

Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

RT-PRC083E-EN 05 Dec 2022 Supersedes RT-PRC083D-EN (Mar 2020).