Trane Technologies BAYECON203AA-AB-A Horizontal Economizer and Rain Hood Installation Guide
- October 30, 2023
- Trane Technologies
Table of Contents
18-HE84D1-1D-EN
Installer’s Guide
Horizontal Economizer & Rain Hood
BAYECON203AA-AB-A Horizontal Economizer and Rain Hood
Model: | Used with: |
---|---|
BAYECON203AA/AB/AC | *WCZ, YCZ, DCZ – 024, 036 |
BAYECON204AA/AB/AC | *WCZ, YCZ, DCZ – 048, 060 |
BAYRLAY006A | (Required with WCZ & DCZ models) |
WARNING: HAZARDOUS VOLTAGE – DISCONNECT POWER BEFORE SERVICING
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL
CODES
IMPORTANT — This Document is customer property and
is to remain with this unit. Please return to service information pack upon
completion of work.
General
The economizer is a multi-damper design. It inserts into the return air stream
and is connected to the unit low voltage supply through wire leads. The
economizer is fully accessible through an access panel.
IMPORTANT: After the Economizer installation you must install an air
filter rack ordered separately. Use:
BAYFLTR101B for WCZ, YCZ, DCZ – 024, 036
BAYFLTR201B for WCZ, YCZ, DCZ – 048, 060
When the economizer is installed in WCZ & DCZ models, relay accessory kit
BAYRLAY006A is required. Refer to Figure 7 on page 7 to make your relay wiring
connections in the Control Box.
Identify Economizer Kit Contents
Refer to Figure 2 on page 3 to identify the kit contents.
Inspect Contents
You must report damage and make claims to the transport-station company
immediately. Report missing parts to your supplier immediately and replace
with authorized parts only.
WARNING
ELECTRIC SHOCK HAZARD
Open and lock out all unit disconnects prior to accessory installation or
unit maintenance, to prevent injury or death from electrical shock or contact
with moving parts.
WARNING
SAFETY HAZARD
Do not remove end covers from Economizer actuator; the spring-return assembly
may release and cause personal injury.
CAUTION
Use care when inserting the economizer in the return air compartment, to
prevent damaging the foil faced insulation.
Install Economizer Kit
-
Remove Power
Disconnect and verify that power is off. -
Remove Access Panels
Remove these three (3) access panels (see Figure 1, page 3):
• Control/Heat access panel
• Blower access panel
• Coil access panel -
BAYRLAY006A Installation (Required for WCZ & DCZ units only, for *YCZ units skip to step 4)
-
Remove wire harness that came attached to the BAYECON Logic Module being installed.
IMPORTANT: Do NOT remove the resistors from the
Logic Module. Also, Do NOT remove the YL & YL/BK wires connected to SO and + on the Logic Module -
Locate the ICMC Board in the upper left hand corner of the unit control box and the DFC board in the upper center of the unit control box. See Figure 5, page 5.
-
Using the existing holes in the back of the unit control box, mount the relay bracket assembly using the 2 screws supplied with the BAYRLAY006A Kit. See Figure 5, page 5.
-
Route the BAYRLAY006A wire harness attached to the relays to the logic module as shown in Figure 3 on page 4.
-
Connect the BAYRLAY006A to the economizer Logic Module and make the field connections as shown in Figure 7 on page 7.
Install Economizer Assembly
-
Apply two gaskets to horizontal economizer mounting flanges. See Figure 2 on page 3.
-
a. Small Cabinet – BAYECON203AA/AB/AC (WCZ, YCZ, DCZ – 024, 036)
Set the horizontal economizer over the horizontal return air opening on the unit. The notches in the bottom flange of the economizer clear the two existing screws below the return air opening of the unit.
2b. Medium Cabinet – BAYECON204AA/AB/AC (WCZ, YCZ, DCZ – 048, 060)
Apply a gasket to the economizer and slide the topflange of the economizer under the lip between the top and bottom sections of the unit. Mate the notches on the top flange of the economizer with the existing screws between the top and bottom sections of the unit. The notches on the bottom flange of the economizer clear the two existing screws below the return air opening of the unit. -
Drill three (3) 9/64” holes through the mating holes in the top flange of economizer and into the unit. Then, drive three (3) #10 sheet metal screws to secure the top.
-
Drill three (3) 9/64” engagement holes on each side of the economizer. Then, drive three (3) #10 sheet metal screws into each side of the economizer to the unit.
-
Mount the Mixed Air sensor to the left Blower partition using two sheet metal screws. See Figure 4, page 4. The Yellow and Yellow/Black wires will connect to the Economizer wiring harness in a later step. Install any economizer options at this time per instructions provided with the sensor.
-
Apply a gasket to the Rain Hood flanges. See Figure 2, page 3.
-
Place the Rain Hood over the horizontal return air opening of the economizer. See Figure 2, page 3. Use the #10 sheet metal screws provided to attach the hood to the economizer.
-
Route the main wiring harness. From the Economizer assembly, route the main wiring harness to the Mixed Air sensor and to the Control Box. See Figure 3, page 4.
-
Connect the two (2) Mixed Air Sensor wires (pulled from harness) to the mating pigtail wires (with female quick connects) from the Mixed Air Sensor.
-
In the Control Box, locate the ICMC Board in the upper left hand corner of the Control Box. Find the YL/RD and YL wires in the 12 pin connector. Leaving enough length of these wires so that the ends going to the ICMC Board can be stripped, cut these wires in two. Strip the cut end of the wires going to the ICMC Board and connect to economizer wires as per hookup diagrams on pages 6 and 7. Cap the ends of the Yellow and Yellow/Red wires not being hooked up. Secure all wires with wire ties so that there is no interference with any moving parts in the unit.
-
In the Control Box, complete the wiring connections per the appropriate wiring diagram on pages 6 and 7. Secure all wires so that there is no interference with any moving parts in the unit.
CAUTION
Be certain to cap the ends of the cut YL/RD and YL wires that are not being connected to an accessory or the unit to reduce the risk of a short. -
Attach the return duct to the economizer.
-
Power the economizer and run the checkout procedure on page 8. Make desired adjustments to the controller: set the minimum occupied damper position, set the outside air (if enthalpy used).
-
Replace the unit Coil access panel, the Blower access panel, and the Control Box access panel.
Sequence Of Operation – Units Equipped With Honeywell W7459 Logic
NOTE: A (G) signal is required for the economizer to operate.
As shipped, the economizer will not operate when there is a signal for Heating
Modes utilizing gas heat.
Fan Only (G): When the thermostat sends a signal for fan only (G), the
economizer will open to the minimum position setting regardless of the outdoor
air conditions and the indoor blower will operate at approximately 50%
airflow.
Heating (W1), (W2), (Y1, Y2 on Heat Pump or Dual Fuel Models): When the
thermostat sends a signal for auxiliary heat (G) +(W1) or first stage heat (G)
- (Y1,Y2), the economizer will open to the minimum position setting. When the
ambient temperature may be below 70F, the economizer will not fully open to
the economizing position, when there is a signal for heat. In order to receive
fresh air and open the dampers to the minimum position setting, you must
provide a G signal to the unit from the thermostat or comfort control being
used.
FREE COOLING NOT AVAILABLE: When the outdoor air conditions are not sufficient for “Free Cooling” the Economizer will open to the minimum position setting only and the unit will function.
FREE COOLING AVAILABLE:
1 st Stage Cooling (Y1) + (O for Heat Pumps and Dual Fuel models): When outdoor air conditions are sufficient for “Free Cooling” and the thermostat sends a signal for 1st stage cooling (G) + (Y1) + (O for Heat Pumps and Dual Fuel models), the economizer will modulate accordingly and the indoor blower will run at approximately 70% airflow.
2nd Stage Cooling (Y1) + (Y2) + (O for Heat Pumps and Dual Fuel models): When outdoor air conditions are sufficient for “Free Cooling” and the thermostat sends a signal for 2nd stage cooling (G) + (Y1) + (Y2) + (O for Heat Pumps and Dual Fuel models), the economizer will modulate accordingly, the compressor will operate on low speed, and the indoor blower will operate at 100% airflow.
Unit “OFF” Mode
When the economizer is not receiving a 24V signal to the TR terminal, or if power is disconnected to the unit, the dampers will be fully closed to the outside air and fully open to the return air.
NOTE: Free Cooling refers to the process of circulating unconditioned outside air, without operating the compressor, to cool the structure.
IMPORTANT — Retain this wiring diagram; please return this document to service information pack upon completion of work.
IMPORTANT — Retain this wiring diagram; please return this document to service information pack upon completion of work.
IMPORTANT-Retain this wiring diagram; please return this document to service information pack upon completion of work.
IMPORTANT-Retain this wiring diagram; please return this document to
service information pack upon completion of work.
5A. Checkout – For Units with a Honeywell W7459 Control, Only. See 5B for
W7212
Operate the motor through its complete open-close stroke. If necessary,
release one of the previously tightened linkage connections to prevent damage.
Check for proper operation, making sure that the linkage does not bind and
that the motor travels smoothly throughout its fully open and closed position.
Table 1 describes how to drive the motor to the full open and full closed
positions (power connected). If there is excess length of linkage rod, cut it
to size. Make necessary minor adjustments until desired operation is obtained,
and tighten all nuts and set screws.
This motor checkout ensures that:
- The motor operates the load.
- The motor responds properly to the controller.
- The reis no binding of the linkage or motor stalling at any point of travel.
If motor does not operate properly, check for proper voltage or mechanical
binding in linkage or damper.
If questions arise regarding this product, contact your distributor or
representative.
Table 1. Motor Operation Checkout – W7459 Control Only
MODEL | DRIVE MOTOR OPEN | DRIVE MOTOR CLOSED | SPRING RETURN |
---|---|---|---|
M7415 | Power to TR and TR1, jumper T and T1 | Disconnect jumper at T or T1 and | |
disconnect P or P1, if connected | Disconnect power at TR and TR1 | ||
CONTROL CURVE | CONTROL POINT APPROX. F (C) AT 50% RH | ||
--- | --- | ||
A | A73 (23) | ||
B | B70 (21) | ||
C | C67 (19) | ||
D | D63 (17) |
Single enthalpy: The enthalpy changeover set point is set to return the outdoor air damper to minimum position when the enthalpy rises above its set point. The enthalpy set point scale markings, located on W7459, are A,B,C,D; see table for the corresponding control point. The factory installed R4 WHITE 620-ohm jumper must be in place across terminals + and SR.
Table 2. Enthalpy Checkout Procedure – W7459 Control
Checkout Procedure | Response |
---|---|
A | 1.Disconnect power at TR and TR1. |
2.Disconnect jumper P to P1.
3.Jumper TR to 1.
4.Jumper T1 to T.
5.If connected, remove C7400 Solid State Enthalpy Sensor from ter-minals SO
and +. Ensure factory-installed 620 ohm resistor is connected to terminals Sr
and +.
6.Apply power (24Vac) to terminals TR and TR1| LED is off.
Motor is in closed position.
B| 1. Disconnect factory-installed 620 ohm resistor from terminals Sr and +|
LED turns on, motor drives toward open.
C| 1.To simulate high and low enthalpy (single enthalpy sensor) reconnect
factory-installed 620 ohm resistor from terminals Sr and +. Connect 1.2K ohm
4074EJM Checkout Resistor across terminals So and +.|
2.Turn enthalpy setpoint potentiometer to “A”.| LED turns on, indicating low
enthalpy.
Motor drives toward open.
3.Turn enthalpy setpoint potentiometer to “D”.| LED turns off, indicating high
enthalpy.
Motor drives toward closed.
4.Disconnect the 1.2K ohm checkout resistor| —
D| 1.To verify sensor operation, reconnect the + lead of the outdoor enthalpy
sensor to the + terminal of W7459.|
2.Connect a DC multimeter between terminal So of the W7459A and terminal S of
the enthalpy sensor. See Fig. 11 (positive meter lead to terminal S of the
enthalpy sensor).| Multimeter indication is between 3 and 25 mA if sensor is
operating properly.
If multimeter indicates zero, the sensor may be wired backward.
3.When using differential enthalpy, check the return air enthalpy sensor by
connecting a DC multimeter between terminal Sr of the W7459A and terminal S of
the return air enthalpy sensor. (positive meter lead to terminal S of the
enthalpy sensor).| Multimeter indication is between 3 and 25 mA if sensor is
operating properly.
If multimeter indicates zero, the sensor may be wired backward.
Table 3. Temp vs. OHM Values for MAS (Mixed Air Sensor)
Temp vs. OHM for MAS (Mixed Air Sensor)
Temp FT | TEmp C | R(K OHMS) | DC Volts |
---|---|---|---|
33.8 | 1 | 9.576 | 3.910 |
35.6 | 2 | 9.092 | 3.882 |
37.4 | 3 | 8.636 | 3.894 |
39.2 | 4 | 8.204 | 3.863 |
41.0 | 5 | 7.796 | 3.829 |
42.8 | 6 | 7.412 | 3.790 |
44.6 | 7 | 7.048 | 3.749 |
46.4 | 8 | 6.705 | 3.713 |
48.2 | 9 | 6.380 | 3.674 |
50.0 | 10 | 6.073 | 3.634 |
51.8 | 11 | 5.782 | 3.590 |
53.6 | 12 | 5.507 | 3.550 |
55.4 | 13 | 5.247 | 3.507 |
57.2 | 14 | 5.000 | 3.420 |
59.0 | 15 | 4.767 | 3.373 |
60.8 | 16 | 4.545 | 3.328 |
62.6 | 17 | 4.335 | 3.283 |
64.4 | 18 | 4.136 | 3.239 |
66.2 | 19 | 3.948 | 3.180 |
68.0 | 20 | 3.769 | 3.157 |
69.8 | 21 | 3.599 | 3.118 |
71.6 | 22 | 3.437 | 3.08 |
73.4 | 23 | 3.284 | 3.034 |
75.2 | 24 | 3.138 | 3.007 |
77.0 | 25 | 3.000 | 2.971 |
78.8 | 26 | 2.869 | 2.932 |
80.6 | 27 | 2.744 | 2.896 |
82.4 | 28 | 2.625 | 2.860 |
84.2 | 29 | 2.512 | 2.824 |
86.0 | 30 | 2.404 | 2.787 |
87.8 | 31 | 2.301 | 2.75.0 |
89.6 | 32 | 2.204 | 2.714 |
91.4 | 33 | 2.111 | 2.676 |
93.2 | 34 | 2.023 | 2.639 |
95.0 | 35 | 1.938 | 2.600 |
96.8 | 36 | 1.858 | 2.561 |
98.6 | 37 | 1.781 | 2.526 |
100.4 | 38 | 1.708 | 2.484 |
5B. CHECKOUT – For Units with a Honeywell W7212 Control, Only. See 5A for W7459
CHECKOUT AND TROUBLESHOOTING
Checkout requires a 9V battery, 620 ohm, 1.2K ohm, 5.6K ohm, and 6.8K ohm
resistors. Use Table 4 and Fig. 12 for checkout.
CAUTION
Equipment Damage Hazard.
Excessive force can damage potentiometer controls.
Use a small screwdriver when adjusting enthalpy changeover and minimum damper
position controls.
Table 4. Checkout for W7212, W7213, W7214 Economizer Connected to Honeywell Actuator
Step | Checkout Procedure | Proper Response |
---|---|---|
1. | CHECKOUT PREPARATION FOR ECONOMIZING ONLY | |
Disconnect power at TR and TR1 | All LED are off; Exhaust Fan contacts are open |
Disconnect devices at P and P1
Jumper P to P1 (defaults to on board MIN POS potentiometer).
Place 5.6K ohm resistor across T and T1 (Blue sleeve-provides input to
economizer that the MAT is between 50-55F).
Jumper TR to 1 (call for cooling from the thermostat).
W7212 only jumper TR to N (places economizer in occupied mode).
If connected, remove C7400 Enthalpy Sensor from terminals So and +.
Connect 1.2K ohm, from 4074EJM Checkout Resistor kit, (purple sleeve) across
terminals So and + (makes OA enthalpy high).
Place 620 ohm resistor (white sleeve) across SR and + (makes return enthalpy
lower than OA).
Set MIN POS and DCV MAX potentiometers fully CCW.
Tum DCV setpoint potentiometer mid position (this sets the DCV ventilation at
approximately 1000 ppm).
Tum exhaust potentiometer to mid position (motor will be approximately 50%
open when the exhaust fan contacts make).
Set enthalpy potentiometer to D.
W7214 only Jumper TR to 0.
Apply power (24 Vac) to terminals TR and TR1
Table 4. Checkout for W7212, W7213, W7214 Economizer Connected to Honeywell Actuator (Cont.)
Step | Checkout Procedure | Proper Response |
---|---|---|
2. | DIFFERENTIAL ENTHALPY | |
Execute stop one, Checkout Preparation. | — | |
Turn DCV MAX to mid position. |
Place 620 ohm resistor across ; and + (white sleeve resistor makes OA enthalpy
low).|
Place 1.2K ohm resistor across SR and + (purple sleeve resistor makes RA
enthalpy high).| Free cool LED turn on; motor drives to approximately 45
degrees (half) open.
Remove 620 ohm resistor from So and +.| Free cool LED turn off; motor drives
closed
3.| SINGLE ENTHALPY
Execute stop one, Checkout Preparation.| —
Turn DCV MAX to mid position.|
Set enthalpy potentiometer to A (fully CCW).| Free cool LED turns on; motor
drives to approximately 45 degrees (half) open.
Set enthalpy potentiometer to D or E for W7212C (fully CW).| Free cool LED
turns off; motor drives dosed.
4.| DCV AND EXHAUST|
Execute step one, Checkout Preparation.| —
LED for both DCV and Exhaust should be off.|
Turn DCV MAX to mid position.| Motor drives to mid position, 45 degrees open.
Turn MIN POS fully CW.| Motor drives fully open.
Turn MIN POS and DCV MAX to fully CCW.| Motor drives closed.
Turn DCV MAX to mid position.
Connect 9V battery positive to AQ and negative to AQ1.| LED for both DCV and
Exhaust turn on. Actuator drives to 45 degrees open.
Remove jumper from N terminal (economizer goes into not occupied mode).| Motor
remains at 45 degrees open.
Adjust DCV MAX towards CW.| Motor will move to position set by DCV MAX pot.
Adjust DCV MAX to fully CCW.| Motor will drive closed.
Reconnect jumper to N terminal.|
Adjust DCV MAX and MIN POS pots.| Motor will drive to the most open position
of the pots.
Adjust DCV MAX and MIN POS pots to fully CCW.|
Remove power from N terminal adjust MIN POS towards CW.| Motor should not
move.
Adjust DCV MAX towards CW.| Motor will move to position set by DCV MAX pot.
5| MINIMUM AND MAXIMUM POSITION
Execute stop one, Checkout Preparation.| —
Connect 9V battery positive to AQ and negative to AQ1. Adjust DCV MAX
potentiometer to mid position.| DCV LED turns on. Actuator drives to 45
degrees open.
Turn DCV maximum position potentiometer to fully CCW.| Actuator drives fully
closed.
Turn minimum position potentiometer to midpoint.| Actuator drives to 45
degrees open.
Turn minimum position potentiometer fully CW.| Actuator drives fully open.
Turn MIN POS to fully CCW.| Actuator drives fully closed.
W7212: Remove jumper from TR and N.| Actuator drives fully closed.
W7214: Jumper TR to O.
6.| MIXED AIR INPUT
Execute stop one, Checkout Preparation.| —
Turn DCV MAX to mid position; set enthalpy potentiometer to A.| Free cool LED
turns on.
Actuator drives to 45 degrees open.
Remove 5.6K ohm resistor (green sleeve) and place jumper from T and T1.|
Actuator drives to 45 degrees open.
Remove jumper from T and T1 and leave open.| Actuator drives fully closed.
About Trane and American Standard Heating and Air Conditioning
Trane and American Standard create comfortable, energy efficient indoor
environments for residential applications.
For more information, please visit www.trane.com or
www.americanstandardair.com
The manufacturer has a policy of continuous data improvement and it reserves
the right to change design and specifications without notice. We are committed
to using environmentally conscious print practices.
18-HE84D1-1D-EN 09 Sep 2022
Supersedes 18-HE84D1-1C-EN (May 2022)
© 2022
Documents / Resources
|
Trane Technologies BAYECON203AA-AB-A Horizontal Economizer and Rain
Hood
[pdf] Installation Guide
BAYECON203AA-AB-AC, BAYECON203AA-AB-A Horizontal Economizer and Rain Hood,
Horizontal Economizer and Rain Hood, Economizer and Rain Hood, Rain Hood,
BAYECON204AA-AB-AC, BAYRLAY006A
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>