TRANE PTEG0701GAA Packaged Terminal Air Conditioner PTAC Instruction Manual
- May 15, 2024
- Trane
Table of Contents
- PTEG0701GAA Packaged Terminal Air Conditioner PTAC
- Product Specifications:
- Product Usage Instructions:
- Safety Instructions:
- Environmental Concerns:
- Field Wiring and Grounding:
- Personal Protective Equipment (PPE):
- Fire Safety:
- Q: Can I install the unit myself?
- Q: What should I do if I detect a refrigerant leak?
- Q: How often should maintenance be performed on the unit?
PTEG0701GAA Packaged Terminal Air Conditioner PTAC
“`html
Product Specifications:
-
Model: ProSpaceTM Packaged Terminal Air Conditioner (PTAC)
-
AC/Heat Pump with Electric Heat
-
Voltage Options:
-
208/230 Volts: PTEG0701GAA, PTHG0701GAA, PTEG0901GAA,
PTHG0901GAA, PTEG1201HAA, PTHG1201HAA, PTEG1501HAA,
PTHG1501HAA -
265 Volts: PTEG0702GAA, PTHG0702GAA, PTEG0902GAA, PTHG0902GAA,
PTEG1202HAA, PTHG1202HAA, PTEG1502HAA, PTHG1502HAA
-
Product Usage Instructions:
Safety Instructions:
Only qualified personnel should install and service the
equipment. Follow all safety warnings and precautions mentioned in
the manual.
Environmental Concerns:
R32 refrigerant is used, which is environmentally friendly with
low greenhouse warming potential. Handle with care to prevent
damage or injury.
Field Wiring and Grounding:
All field wiring must be performed by qualified personnel to
avoid fire and electrocution hazards. Follow NEC and local
electrical codes for proper installation.
Personal Protective Equipment (PPE):
Wear proper PPE to protect against electrical, mechanical, and
chemical hazards. Follow instructions in the manual and on
equipment tags.
Fire Safety:
Avoid exposing the refrigerant to open flames or ignition
sources to prevent fire hazards.
Frequently Asked Questions (FAQ):
Q: Can I install the unit myself?
A: Installation should only be done by qualified personnel to
ensure safety and proper functioning of the equipment.
Q: What should I do if I detect a refrigerant leak?
A: If you suspect a refrigerant leak, immediately ventilate the
area, turn off the unit, and contact a qualified technician for
assistance.
Q: How often should maintenance be performed on the unit?
A: Regular maintenance is essential for optimal performance.
Follow the maintenance schedule outlined in the manual or consult a
professional for guidance.
“`
Installation, Operation, and Maintenance
ProSpaceTM Packaged Terminal Air Conditioner (PTAC)
R32 AC/Heat Pump with Electric Heat
208/230 Volts: PTEG0701GAA PTHG0701GAA PTEG0901GAA PTHG0901GAA PTEG1201HAA PTHG1201HAA PTEG1501HAA PTHG1501HAA
265 Volts: PTEG0702GAA PTHG0702GAA PTEG0902GAA PTHG0902GAA PTEG1202HAA PTHG1202HAA PTEG1502HAA PTHG1502HAA
SAFETY WARNING
Only qualified personnel should install and service the equipment. The
installation, starting up, and servicing of heating, ventilating, and air-
conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an
unqualified person could result in death or serious injury. When working on
the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
July 2023
PTAC-SVX004A-EN
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the
earth’s naturally occurring stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified chemicals that may affect
the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon
(CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs).
Not all refrigerants containing these compounds have the same potential impact
to the environment. Trane advocates the responsible handling of all
refrigerants.
In contrast to common refrigerants, R32 does no harm to the ozonosphere and
has a significantly lower greenhouse warming potential when compared to
previous refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the
environment, our customers, and the air conditioning industry. All technicians
who handle refrigerants must be certified according to local rules. For the
USA, the Federal Clean Air Act (Section 608) sets forth the requirements for
handling, reclaiming, recovering and recycling of certain refrigerants and the
equipment that is used in these service procedures. In addition, some states
or municipalities may have additional requirements that must also be adhered
to for responsible management of refrigerants. Know the applicable laws and
follow them.
WARNING
Unit Contains R32 Refrigerant!
Failure to follow proper procedures can result in equipment damage or personal
injury.
A2L
This unit contains R32 refrigerant which is flammable and odorless. Read the
Installation, Operation and Maintenance manual before using this unit. Read
the Installation and Service manual before installing or servicing this unit.
WARNING
Safety Hazard!
· Children aged 8 years and above and persons with reduced physical, sensory,
or mental capabilities or lack of experience and knowledge are allowed to use
this unit only if they are supervised and instructed on how to use the unit in
a safe way and understand the hazards involved.
· Children are not permitted to play with this unit.
· Children should not clean or maintain the unit without supervision.
· Keep children from playing or climbing on the air conditioner.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field
wiring MUST be performed by qualified personnel. Improperly installed and
grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these
hazards, you MUST follow requirements for field wiring installation and
grounding as described in NEC and your local/ state/national electrical codes.
©2023 Trane
PTAC-SVX004A-EN
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death
or serious injury. Technicians, in order to protect themselves from potential
electrical, mechanical, and chemical hazards, MUST follow precautions in this
manual and on the tags, stickers, and labels, as well as the instructions
below:
· Before installing/servicing this unit, technicians MUST put on all PPE
required for the work being undertaken (Examples; cut resistant
gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing). ALWAYS refer to
appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
· When working with or around hazardous chemicals, ALWAYS refer to the
appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and
Labelling of Chemicals) guidelines for information on allowable personal
exposure levels, proper respiratory protection and handling instructions.
· If there is a risk of energized electrical contact, arc, or flash,
technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other
country-specific requirements for arc flash protection, PRIOR to servicing the
unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT
PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND
EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
WARNING
Fire Hazard!
Failure to follow this warning could result in serious injury, death, or
property damage. Though the flammability of the refrigerant is low, it can be
ignited by fire. Do NOT expose the refrigerant to open flames or any other
ignition source.
PTAC-SVX004A-EN
Warnings, Cautions, and Notices
WARNING
Safety Precautions!
Failure to follow the safety precautions could result in serious injury,
death, or property damage. Before installing and operating the unit, observe
the following safety precautions.
· Install, operate, and store the unit in a room with a floor area larger than
43ft2 (4m2).
· Store the unit in a room where there are no continuously operating ignition
sources (i.e., open flames, an operating gas appliance, or an operating
electric heater).
· Store the unit in a well-ventilated area with a room size that matches to
the room area specified for operation.
· Store the unit carefully to prevent mechanical damage.
· Ducts connecting to this unit should not have an ignition source.
· Keep any required ventilation openings clear of obstruction.
· Do not pierce or burn this unit.
· Be aware that refrigerants may not contain an odor.
· Do not use means to accelerate the defrosting process or to clean this unit.
Only use what is recommended by the manufacturer.
· Any servicing on this unit must be performed only as recommended by
manufacturer.
· If repair is necessary, contact an authorized service center only. Any
repairs carried out by unqualified personnel may be dangerous.
· Compliance with local and national building codes shall be observed.
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
· All Trane personnel must follow the company’s Environmental, Health and
Safety (EHS) policies when performing work such as hot work, electrical, fall
protection, lockout/ tagout, refrigerant handling, etc. Where local
regulations are more stringent than these policies, those regulations
supersede these policies.
· Non-Trane personnel should always follow local regulations.
3
Warnings, Cautions, and Notices
WARNING
Cancer and Reproductive Harm!
This product can expose you to chemicals including lead and bisphenol A (BPA),
which are known to the State of California to cause cancer and birth defects
or other reproductive harm. For more information go to www.P65Warnings.ca.
gov.
Copyright
This document and the information in it are the property of Trane, and may not
be used or reproduced in whole or in part without written permission. Trane
reserves the right to revise this publication at any time, and to make changes
to its content without obligation to notify any person of such revision or
change.
Trademarks
All trademarks referenced in this document are the trademarks of their
respective owners.
4
PTAC-SVX004A-EN
Table of Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . . 6
Model Number Description . . . . . . . . . . . . . . . . . 7
Air Conditioners with Electric Heat . . . . . . . . . 8
Heat Pumps with Electric Heaters. . . . . . . . . . . 9
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10 Power Connection Options . . . . . . . . . . . . . . . 10 All Units . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Grounding . . . . .
. . . . . . . . . . . . . . . . . . . . . 10 Voltage Supply . . . . . . . . .
. . . . . . . . . . . . . . . . . 10 Cord/Connected Units . . . . . . . . . .
. . . . . . 10 Power Cord Protection . . . . . . . . . . . . . . . 11
Refrigerant System Diagrams . . . . . . . . . . . . . 12 PTHG Cooling, Heat
Pump, Auxiliary Electric Heat. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 12 PTEG Cooling and Electric Heat . . . . . . . . . . . 12
Electrical Wiring Diagrams . . . . . . . . . . . . . . . . 13 Electrical
Wiring Diagrams for 208V/ 230V and 265 . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 13
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14 Trane Wall Sleeve and Grille. . . . . . . . . . . . . . 14 Considerations
for Use of Existing Sleeves . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 14 Installing the Chassis into Wall Sleeve . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 15
System Configuration . . . . . . . . . . . . . . . . . . . . . 16 Adjusting
Air Direction- Only for Duct Installations . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 16 DIP Switches . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 16 Keypad Configuration. . . . . . . . . . . . . . . . . . . .
17
Auxillary Controls . . . . . . . . . . . . . . . . . . . . . . . . . 18 Wiring
the Wall Thermostat . . . . . . . . . . . . . . 18 Energy Management Input
(Front Desk Control). . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 19 Intelligent Self-Checking Control . . . . . . . . . . 19
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Control Buttons and Functions . . . . . . . . . . . . 20 LED Display and
Digital Display . . . . . . . . . . . 20 LEDs . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 20 Digital Display . . . . . . . . . . . . . .
. . . . . . . . . 20 Mode Functions . . . . . . . . . . . . . . . . . . . . .
. . . . 21 Cooling Mode Functions. . . . . . . . . . . . . . 21 Heating Mode
Functions. . . . . . . . . . . . . . 21 Operating the Remote Control . . . . .
. . . . . . . 23 Changing Batteries in the Remote Control. . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . 24
Care and Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . 25 Front
Panel and Case . . . . . . . . . . . . . . . . . . . . 25 Outdoor Coil . . . .
. . . . . . . . . . . . . . . . . . . . . . . . 25 Base Pan. . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . 25 Air Filter . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . 25
Service Installation . . . . . . . . . . . . . . . . . . . . . . . . 26
Disassembling the Unit . . . . . . . . . . . . . . . . . . . . 27
Temperature and Resistance Charts . . . . . . . 31
Troubleshooting and Resources . . . . . . . . . . . 33 Troubleshooting Error
Codes and Malfunctions . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33 Technicians Guidelines . . . . . . . . . . . . . . . . . . 36 Resources. .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
PTAC-SVX004A-EN
5
General Information
The ProSpaceTM Packaged Terminal Air Conditioners and heat pumps provide a
high standard of quality in performance, workmanship, durability and
appearance as they heat and cool the occupied air space year round.
This manual provides information for ease of installation, operation and
maintenance. All models are designed for throughthewall installation.
Separate installation instructions are included with all accessory components.
Read this manual completely and carefully before starting any work. Write down
the model and serial
number on the space provided on the product registration card. The model and
serial number can be located on the serial number plate attached to the unit.
These numbers are required for any service work.
Important: Ensure that this manual is left with the owner for future
reference. Observe all local codes and ordinances. Observe all governing codes
and ordinances. These instructions must be saved for local inspector’s use. Be
sure to leave these instructions with the owner.
Table 1. Operating Temperature Range:
Maximum Cooling Maximum RC Heating Maximum Electric Heating
Indoor Side DB/WB (°F/°C) 80/67 (26.7/19.4) 80/- (26.7/-) 77/- (25/-)
Outdoor Side DB/WB (°F/°C) 115/75 (46.1/23.9) 75/65 (23.9/18.3) 77/- (25/-)
· Ambient temperature range (indoor temperature) for cooling is 64-80°F (18-26.7°C), · Ambient temperature range (outdoor temperature) for cooling is 64-115°F (18-46.1°C), · Ambient temperature range (indoor temperature) for heat pump is 41-80°F (5-26.7°C), · Ambient temperature range (outdoor temperature) for Electric Heating is 19-77°F (-7-25°C). · Ambient temperature range (outdoor temperature) for heat pump is 55-75°F (13-23.9°C),
6
PTAC-SVX004A-EN
Model Number Description
Use the following to determine the correct model number:
P T E G 0 7 0 2G AA
Product Family PT = Packaged Terminal Unit
Heating Methods E = Cooling with Electric Heat H = Heat Pump with Electric
Heat
Development Sequence F = R410A Refrigerant G = R32 Refrigerant
Size and Cooling 070 = 7,000 Btu 090 = 9,000 Btu 120 = 12,000 Btu 150 = 15,000
Btu
Electrical Voltage 1 = 208/230 Vac 2 = 265 Vac
Electric Heat Size G = Maximum of 3.5 kW H = Maximum of 5.0 kW
Design Sequence AA = First AB = Second
PTAC-SVX004A-EN
7
Air Conditioners with Electric Heat
8
Performance Units PTEG0701GAA PTEG0702GAA PTEG0901GAA PTEG0902GAA PTEG1201HAA PTEG1202HAA PTEG1501HAA PTEG1502HAA
Trade Name:
Style/Function:
Cooling Capacity:
Btu/h
Electric Heat
Power Input
W
Only:
Rated Input
(Electric Heat +
W
Fan Motor)
EER:
Dehumidifying Vol:
Application Area:
(Btu/h)/ W
Pint/h
ft2
Electrical
ProSpaceTM Cooling Only w/
Heaters 7,200/7,400
2,450(2,010)/ 3,450(2,830)
2,500(2,040)/ 3,500(2,860)
13.3
1.69
108-172
ProSpaceTM Cooling Only w/
Heaters 7,500
2,450/3,450
2,500/3,500
13.3 1.69 108-172
ProSpaceTM Cooling Only w/
Heaters 9,900/10,200
2,450(2,010)/ 3,450(2,830)
2,500(2,040)/ 3,500(2,860)
12.5
2.11
129-194
ProSpaceTM Cooling Only w/
Heaters 10,000
2,450/3,450
2,500/3,500
12.5 2.11 129-194
ProSpaceTM Cooling Only w/
Heaters
12,100/12,300
2,450(2,010)/ 3,450(2,830)/ 5,000(4,090) 2,500(2,040)/ 3,500(2,860)/
5,050(4,130)
11.8/11.6
2.75
172-258
ProSpaceTM Cooling Only w/
Heaters 12,300
2,450/3,450/ 5,000
2,500/3,500/ 5,050
11.6
2.75
172-258
ProSpaceTM
Cooling Only w/ Heaters
14,400/14,700
2,450(2,010)/ 3,450(2,830)/ 5,000(4,090) 2,500(2,040)/ 3,500(2,860)/
5,050(4,130)
10.6/10.4
ProSpaceTM Cooling Only w/
Heaters 14,800
2,450/3,450/ 5,000
2,500/3,500/ 5,050
10.6
3.17
3.17
226-334
226-334
Rated Voltage: V~
208/230
265
208/230
265
208/230
265
208/230
265
Rated Frequency:
Hz
60
60
60
60
60
60
60
60
Phases:
Cooling Power Current:
A
Power Cord:
Features
Sound Pressure Level (L/H):
Airflow Volume (L/H):
dB (A) CFM
Warranty:
1
2.6/2.4 Refer to Table 2
and Table 3.
1
2.1 Refer to Table 2
and Table 3.
46/50
46/50
282/312
5-Year Parts/5Year Sealed System Replacement
282/312
5-Year Parts/5Year Sealed System Replacement
1
3.9/3.6 Refer to Table 2
and Table 3.
46/50
282/330 5-Year Parts/5-
Year Sealed System
Replacement
1
3.2 Refer to Table 2
and Table 3.
46/50
282/330 5-Year Parts/5-
Year Sealed System
Replacement
1
5.0/4.7 Refer to Table 2
and Table 3.
50/53
306/341 5-Year Parts/5-
Year Sealed System
Replacement
1
4.0 Refer to Table 2
and Table 3.
1
6.5/6.0 Refer to Table 2
and Table 3.
1
5.3 Refer to Table 2
and Table 3.
50/53
50/53
50/53
306/341
5-Year Parts/5Year Sealed System Replacement
306/341
5-Year Parts/5Year Sealed System Replacement
306/341
5-Year Parts/5Year Sealed System Replacement
Specifications
Dim of Package (L x W x H):
Inch
45 x 25 x 19
45 x 25 x 19
45 x 25 x 19
45 x 25 x 19
45 x 25 x 19
45 x 25 x 19
45 x 25 x 19
45 x 25 x 19
Net Weight:
lb
110
110
110
110
115
115
115
115
PTAC-SVX004A-EN
Refrigerant:
Refrigerant Charge:
lb
R-32 1.1
R-32 1.1
R-32 1.1
R-32 1.1
R-32 1.3
R-32 1.3
R-32 1.2
R-32 1.1
9
PTAC-SVX004A-EN
Performance Units PTHG0701GAA
Trade Name:
Style/Function:
Cooling Capacity:
Btu/h
Heating Capacity:
Btu/h
Electric Heat
Power Input W Only:
Rated Input
(Electric Heat + W Fan Motor)
EER:
(Btu/h)/ W
Dehumidifying Vol:
Pint/h
Application Area:
ft2
Electrical
ProSpaceTM Heat Pump w/
Heaters 7,200/7,400
5,800/6,000
2,450(2,010)/ 3,450(2,830)
2,500(2,040)/ 3,500(2,860)
13.0
1.69
108-172
Rated Voltage: V~
Rated Frequency:
Hz
208/230 60
Phases:
Cooling Power Current:
A
Heating Power Current:
A
Power Cord:
Features
Sound Pressure Level (L/H):
Airflow Volume (L/H):
dB (A) CFM
Warranty:
Specifications
Dim of Package (L x W x H):
Net Weight:
Inch lb
1 2.6/2.4 2.3/2.1 Refer to Table 2 and Table 3.
46/50
282/312 5-Year Parts/5-
Year Sealed System
Replacement
45 x 25 x 19 112
Refrigerant:
R32
Refrigerant Charge:
lb
1.7
PTHG0702GAA
ProSpaceTM Heat Pump w/
Heaters
7,300
PTHG0901GAA
ProSpaceTM Heat Pump w/
Heaters
9.400/9,700
6,000
8,200/8,500
2,450/3,450
2,450(2,010)/ 3,450(2,830)
2,500/3,500
2,500(2,040)/ 3,500(2,860)
13.0 1.69
12.1 2.11
108-172
129-194
265
208/230
60
60
1
1
2.1
3.9/3.6
1.8
Refer to Table 2 and Table 3.
3.2/3.1
Refer to Table 2 and Table 3.
46/50
46/50
282/312
5-Year Parts/5Year Sealed System Replacement
282/330
5-Year Parts/5Year Sealed System Replacement
45 x 25 x 19 112 R32 1.7
45 x 25 x 19 115 R32 1.5
PTHG0902GAA ProSpaceTM
Heat Pump w/ Heaters 9,800 8,600
2,450/3,450
2,500/3,500
12.1 2.11 129-194
265 60 1 3.1 2.6 Refer to Table 2 and Table 3.
46/50 282/330 5-Year Parts/5Year Sealed System Replacement
45 x 25 x 19 115 R32 1.5
PTHG1201HAA
ProSpaceTM Heat Pump w/
Heaters
11,900/12,100
PTHG1202HAA
ProSpaceTM Heat Pump w/
Heaters
12,000
10,700/10,900
2,450(2,010)/ 3,450(2,830)/ 5,000(4,090) 2,500(2,040)/ 3,500(2,860)/
5,050(4,130)
11.8/11.6
2.75
10,700
2,450/3,450/ 5,000
2,500/3,500/ 5,050
11.6
2.75
172-258
172-258
208/230
265
60
60
1
1
4.9/4.6
4.0
4.3/4.1
Refer to Table 2 and Table 3.
3.5
Refer to Table 2 and Table 3.
50/53
50/53
306/341
5-Year Parts/5Year Sealed System Replacement
306/341
5-Year Parts/5Year Sealed System Replacement
45 x 25 x 19 119 R32 1.8
45 x 25 x 19 119 R32 1.8
PTHG1501HAA ProSpaceTM
Heat Pump w/ Heaters
14,200/14,600
13,300/13,800 2,450(2,010)/ 3,450(2,830)/ 5,000(4,090) 2,500(2,040)/
3,500(2,860)/ 5,050(4,130)
10.4
3.17
226-334
208/230
60
1 6.5/6.0
5.9/5.6 Refer to Table 2
and Table 3.
50/53
306/341 5-Year Parts/5-
Year Sealed System
Replacement
45 x 25 x 19
120 R32
1.9
PTHG1502HAA ProSpaceTM
Heat Pump w/ Heaters 14,500
13,300
2,450/3,450/ 5,000
2,500/3,500/ 5,050
10.4 3.17 226-334
265 60 1 5.3 4.7 Refer to Table 2 and Table 3.
50/53
306/341 5-Year Parts/5-
Year Sealed System
Replacement
45 x 25 x 19 120 R32 1.8
Heat Pumps with Electric Heaters
Electrical
WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury. When it is
necessary to work with live electrical components, have a qualified licensed
electrician or other individual who has been properly trained in handling live
electrical components perform these tasks.
WARNING
Power Cord!
If the SUPPLY CORD is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard.
All Units
Important: Follow NEC and local electrical codes when installing electrical
supply wiring. The following is only shown as a sample.
Use recommended wire size (Table 1) and install a single-branch circuit. All
units are designed to operate off only one (1) single branch circuit.
Note: Only use copper conductors. Branch circuit wire is single circuit from
main box. AWG wire sizes are based on copper wire at a 140°F (60°C)
temperature rating.
Table 2. Common Branch Circuit Wire Sizes
Nameplate Amps
AWG Wire Size
7.0 to 12
14
12.1 to 16
12
16.1 to 24
10
Power Connection Options
Appropriate power cord accessory kit is determined by the voltage and the
amperage of the branch circuit, based on the unit amperage requirements (for
example, electric heater size). This unit ships without a power cord (or hard
wire kit). An accessory power cord must be ordered to connect the unit to the
outlet.
Notes:
· Ensure the outlet matches the appropriate prong configuration on the plug.
It should be within reach of the service cord. All wiring, including
installation of the receptacle, must be in accordance with the NECTM and all
local codes, ordinances and regulations. National codes require the use of an
arc fault or leakage current detection device on all 208/230V power cords.
· For 265V units, if power cord accessory option is selected, then the cord is
only 18″ long and must plug into the accessory electrical 265V sub-base.
Grounding
For safety and protection, the unit is grounded through the service cord plug
or through separate ground wire provided on hard wired units. Ensure that the
branch circuit or general purpose outlet is grounded.
Voltage Supply
Check voltage supply at outlet. For satisfactory results, the voltage range
must always be within the ranges specified on the data information plate.
Power cord does not ship with the unit. The cord to order is determined by the
unit voltage and the desired electric heat capacity.
Cord/Connected Units
The 250 Vac field supplied outlet must match the plug for standard 208/230V
units and be within reach of the service cord.
Note: Do NOT use 30 amp cord with sizes 07 and 09 units.
Table 3. Electric Heater and Cord Information, PTEG and PTHG Sizes 07 and 09
Voltage:
230 Vac(a)
Amps:(b)
15
20
15
Heater Size:
2.5 kW
3.5 kW
2.5 kW
Plug Layout:
G
G
G
W
265 Vac
20 3.5 kW
G W
NEMA Plug:
6-15P
6-20P
7-15P
Cord #:
PWR00286
PWR00288
PWR00287
(a) The 250 Vac field supplied outlet must match the plug for standard 208/230V units and be within reach of the service cord. (b) Do Not use 30 amp cord with sizes 07 and 09 units.
7-20P PWR00289
10
PTAC-SVX004A-EN
Table 4. Electric Heater and Cord Information, PTEG and PTHG Sizes 12 and 15
Voltage: Amps:
230 Vac
15
20
30
15
Heater Size: Plug Layout:
2.5 kW
G
3.5 kW
G
5.0 kW
G
2.5 kW
G W
265 Vac 20
3.5 kW
G W
Electrical
30 5.0 kW
G W
NEMA Plug:
6-15P
6-20P
6-30P
7-15P
7-20P
7-30P
Cord #(a) :
PWR00286
(a) Power cord does not ship with the unit.
PWR00288
PWR00290
PWR00287
PWR00289
PWR00291
Power Cord Protection
The power cord for 230/208V units provide protection from fire. The unit power
automatically disconnects when unsafe conditions are detected. Power to the
unit can be restored by pressing the reset button on plug head. Upon
completion of unit installation for 230/208V models, an operational check
should be performed using the TEST/RESET buttons on the plug head.
Note: Models with 265V do not incorporate this feature because they require use of an electrical subbase accessory. Connection to a wall socket is not permitted for 265V units. All 265V units must be hard wired using the hard wire kit or make use of the plug-in receptacle in the standard subbase.
PTAC-SVX004A-EN
11
Refrigerant System Diagrams
PTHG Cooling, Heat Pump, Auxiliary Electric Heat
PTEG Cooling and Electric Heat
12
PTAC-SVX004A-EN
Electrical Wiring Diagrams
Symbol WH YE RD YEGN VT GN BN BU BK OG CAP COMP
Color/ Name White Yellow Red Yellow/Green Violet Green Brown Blue Black Orange
Jumper cap Compressor
Grounding Wire
Electrical Wiring Diagrams for 208V/230V and 265
The electrical schematic diagram pictured below is subject to change. Please
reference the wiring diagram on the unit.
208/230V; PTEG0701 and PTEG0901 265V; PTEG0702 and PTEG0902
Circuit diagram:
OUTTUBE TEMP. SENSOR DAHT TEMP. SENSOR TUBE TEMP. SENSOR ROOM TEMP. SENSOR
OPTIONAL RECEIVER
CN1
RT4 RT3 RT2 RT1
RD WH BK BK 20K 20K 20K 15K
CN8 DISP1
AP2 CN1 CN9
CN3 CN4 CN10
X4
DISP2 DISP3 AP3
DISPLAY
ENERGY
WALL
MANAGEMENT THERMOSTAT II I
CONTROLLER OPTIONAL
TC I
OPTIONAL
X3 2 BU
YEGN M1 G
1 BK
3 WH 4 RD
FAN MOTOR
6 BN C2
BK
YEGN M2 BU
G
BN
FAN MOTOR RD C3 BN
POWER
L1(L)
BK
L2(N)
WH
(OPTIONAL)
GN(YEGN)
JUMP1
SUBBASE PLUG
(FOR 265V UNIT)
(OPTIONAL) JUMP2
B1 B2 B3 A1 A2 A3
X1 B1 B2 B3 A1 A2 A3
BK WHGN BU BK
G
L2 COMPAC-L K1
RD COCMPCOMP.
CN1
S
R
CN2
XT1 YE C1 BU
TR-OUT2
K2 I-HEAT-1 TR-OUT O-HEAT-1
BK
2 BU BU
1
TR-IN I-HEAT-2
RD
1
K3 O-HEAT-2
RD
5 7
FAN
N1 BU
6 KM1 5
AP1 L1
OFAN-H OFAN-L
HEAT1
WH BK RELAY
N1
BN
4
1
BK 1 2 XT2
BK
X2
HEATER
1 BK
EH1 1.0KW 5 RD
EH2 2.45KW 3 WH
EH3 1.55KW
BK
SAT2
SAT1
FUT BK
BK
C2:1uF OR 1.5uF C3:1.5uF OR 2uF OR 2.5uF
PTAC-SVX004A-EN
208/230V; PTEG1201 and PTEG1501 265V; PTEG1202 and PTEG1502
OPTIONAL RECEIVER
CN1
CN8 DISP1 X4
DISP2 DISP3 AP3 DISPLAY
Circuit diagram:
OUTTUBE TEMP. SENSOR DAHT TEMP. SENSOR TUBE TEMP. SENSOR ROOM TEMP. SENSOR
RT4 RT3 RT2 RT1
RD WH BK BK 20K 20K 20K 15K
CN1
AP2
CN9
CN3
CN4 CN10
ENERGY
WALL
MANAGEMENT THERMOSTAT II I
CONTROLLER OPTIONAL
TC I
OPTIONAL
X3 2 BU
YEGN M1 G
1 BK
3 WH 4 RD
FAN MOTOR
6 BN C2
BK
YEGN M2 BU
G
BN
FAN MOTOR RD C3 BN
POWER L1(L) L2(N)
SUBBASE (FOR 265V UNIT)
BK WH GN(YEGN)
PLUG
(OPTIONAL) JUMP1 (OPTIONAL)
JUMP2
B1 B2 B3 A1 A2 A3
X1 B1 B2 B3 A1 A2 A3
BK WHGNWHBU BK G
RD
L2 COMPAC-L K1
C COMP.
COMP
CN1
CN2 K4 I-HEAT-3 O-HEAT-3
WH
TR-OUT2
K2 I-HEAT-1 TR-OUT O-HEAT-1
BK
S
R
XT1 YE C1 BU
2
BU BU
1
TR-IN I-HEAT-2
RD
1
K3 O-HEAT-2
RD
X2 1 BK
HEATER
5 7
FAN
N1 BU
EH1 1.0KW 5 RD
AP1
L1
OFAN-H OFAN-L
HEAT1
N1
6 KM1 5
WH BK RELAY
BN
4
1
BK 1 2 XT2
BK
3
EH2 2.45KW WH
EH3 1.55KW
BK
SAT2
SAT1
FUT BK
BK
C2:1uF OR 1.5uF C3:1.5uF OR 2uF OR 2.5uF
208/230V; PTHG0701 and PTHG0901 265V; PTHG0702 and PTHG0902
Circuit diagram:
OUTTUBE TEMP. SENSOR DAHT TEMP. SENSOR TUBE TEMP. SENSOR ROOM TEMP. SENSOR
OPTIONAL RECEIVER
CN1
RT4 RT3 RT2 RT1
RD WH BK BK 20K 20K 20K 15K
CN8 DISP1
AP2 CN1 CN9
CN3 CN4 CN10
X4
DISP2 DISP3 AP3
DISPLAY
ENERGY
WALL
MANAGEMENT THERMOSTAT II I
CONTROLLER OPTIONAL
TC I
OPTIONAL
X3 2 BU
YEGN M1 G
1 BK
3 WH 4 RD
FAN MOTOR
6 BN C2
BK
YEGN M2 BU
G
BN
FAN MOTOR RD C3 BN
POWER L1(L) L2(N)
SUBBASE (FOR 265V UNIT)
BK
WH GN(YEGN)
PLUG
(OPTIONAL) JUMP1 (OPTIONAL)
JUMP2
B1 B2 B3 A1 A2 A3
X1 B1 B2 B3 A1 A2 A3 BK WHGN BU BK
G
COMPAC-L K1
L2
RD C COMP.
COMP
CN1
S
R
CN2
XT1 YE C1 BU
TR-OUT2
K2 I-HEAT-1 TR-OUT O-HEAT-1
BK
2 BU BU
1
TR-IN I-HEAT-2
RD
1
K3 O-HEAT-2 RD
5 7
FAN
N1 BU
AP1
L1
OFAN-H OFAN-L
HEAT1
N1 N2 4WAY
6 KM1 5
WH BK RELAY
BN
4
1
BK 1 2 XT2
BK
X2
HEATER
1 BK
EH1 1.0KW 5 RD
EH2 2.45KW 3 WH
EH3 1.55KW
BK
SAT2
SAT1
FUT BK
BK
C2:1uF OR 1.5uF C3:1.5uF OR 2uF OR 2.5uF
4YV 4-WAY VALVE
208/230V; PTHG1201 and PTHG1501 265V; PTHG1202 and PTHG1502
Circuit diagram:
OUTTUBE TEMP. SENSOR DAHT TEMP. SENSOR TUBE TEMP. SENSOR ROOM TEMP. SENSOR
OPTIONAL RECEIVER
CN1
RT4 RT3 RT2 RT1
RD WH BK BK 20K 20K 20K 15K
CN8 DISP1
AP2 CN1 CN9
CN3 CN4 CN10
X4
DISP2 DISP3 AP3
DISPLAY
ENERGY
WALL
MANAGEMENT THERMOSTAT II I
CONTROLLER OPTIONAL
TC I
OPTIONAL
X3 2 BU
YEGN M1 G
1 BK
3 WH 4 RD
FAN MOTOR
6 BN C2
BK
YEGN M2 BU
G
BN
FAN MOTOR RD C3 BN
POWER L1(L) L2(N)
SUBBASE (FOR 265V UNIT)
BK
WH GN(YEGN)
PLUG
(OPTIONAL) JUMP1 (OPTIONAL)
JUMP2
B1 B2 B3 A1 A2 A3
X1 B1 B2 B3 A1 A2 A3 BK WHGN WHBU BK
G
L2 COMPAC-L K1
RD COCMPCOMP.
CN1
CN2 K4 I-HEAT-3 O-HEAT-3
WH
TR-OUT2
K2 I-HEAT-1 TR-OUT O-HEAT-1
BK
S
R
XT1 YE C1 BU
2 BU BU
1
TR-IN I-HEAT-2
RD
1
K3 O-HEAT-2 RD
5 7
FAN
N1 BU
AP1
L1
OFAN-H OFAN-L
HEAT1
N1 N2 4WAY
6 KM1 5
WH BK RELAY
BN
4
1
BK 1 2 XT2
BK
X2
HEATER
1 BK
EH1 1.0KW 5 RD
3
EH2 2.45KW WH
EH3 1.55KW
BK
SAT2
SAT1
FUT BK
BK
C2:1uF OR 1.5uF C3:1.5uF OR 2uF OR 2.5uF
4YV 4-WAY VALVE
13
Installation
Trane Wall Sleeve and Grille
The image below shows the typical unit components that are ordered and
installed.
Important: Proper installation is the responsibility of the installer. Product
failure due to improper installation is not covered under warranty.
Note: To install the Trane Wall Sleeve and Grille, refer to the latest
installation instructions, PTACSVN028 and PTAC-SVN027.
Considerations for Use of Existing Sleeves
WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury. When it is
necessary to work with live electrical components, have a qualified licensed
electrician or other individual who has been properly trained in handling live
electrical components perform these tasks.
In applications when the unit is a replacement, it is recommended to use a
Trane sleeve. This unit can be retrofitted to other manufacturers similar
sleeves if outdoor unit airflow is not restricted or recirculated. Important:
Ensure the outdoor grille is installed on the
sleeve. For any sleeve retrofit applications, be sure that the foam seals
(factory installed on the tube sheets) provide a good seal between the grille
and outdoor coil tube sheets. These foam seals provide a barrier that stops
the inside air from mixing with the outside air (known as air recirculation).
Important: Inspect the wall sleeve thoroughly prior to installation. The
manufacturer does not assume responsibility for costs or damage due to defects
in the sleeve or for improper installation.
Remove any existing foam baffles installed on competitor’s outdoor grille.
General Electric Metal Wall Sleeve; interchangeable with ProSpace wall sleeve.
General Electric Plastic Wall Sleeve; remove bottom seal from plastic sleeve.
14
PTAC-SVX004A-EN
Installing the Chassis into Wall Sleeve
NOTICE
Equipment Damage!
Use spreader bars to prevent straps from damaging the unit. Install the bars
between lifting straps, both underneath the unit and above the unit to prevent
the straps from crushing the unit cabinet or damaging the finish.
1. Carefully remove shipping tape from the front panel and vent door.
Shipping tape
2. Remove shipping screw from the vent door, if present.
Installation
· All units require a cord or a hard-wired kit to be added to complete
electrical connection to the building. Follow the instructions provided with
those accessories.
4. Lift unit level and slide unit into wall sleeve until foam seal rests
firmly against front of wall sleeve.
5. Secure with four screws (supplied) through the unit flange holes.
3. Remove front panel. Consider the following electrical guideline before sliding the unit back into the wall.
6. Re-install front panel by first, hooking tabs over top rail of unit (1) and then pushing in on the bottom of the front panel until it snaps into place (2).
PTAC-SVX004A-EN
15
System Configuration
Adjusting Air Direction- Only for Duct Installations
1. Remove front panel. Louver screws
Louver screws 2. Remove louver screws that hold the louver insert in
place on the back side of the front panel.
The auxiliary DIP switch controls are located behind the front panel and
through an opening below the control panel. To access, you must remove the
front panel. The DIP switches are accessible without opening the control box.
Important: Electrical power supply must be
disconnected from unit to apply DIP switch changes. Note: Factory settings for
DIP switches will be in the DOWN position. Refer to the following for the
functionality of each DIP switch position.
Figure 1. DIP switch/wall thermostat enable
DIP Switches
3. Turn louver insert and rotate it 180°.
4. Replace louver insert.
5. Replace screws and the front panel.
DIP Switches
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious
injury. Disconnect all electric power, including remote disconnects before
servicing. Follow proper lockout/tagout procedures to ensure the power can not
be inadvertently energized. Verify that no power is present with a voltmeter.
Table 5. DIP Switch Descriptions
DIP Switch Number
1: Electric Heating Only/Emergency Heat. This setting is typically used for
Emergency Heating.
Up
Electric Heat Only
2: Wall Thermostat Enable. A wired wall thermostat can be connected to the
unit. The DIP switch must be adjusted accordingly in order to allow the wall
thermostat control of the unit. When unit is in wall thermostat mode, the
control panel is disabled.
3: Energy Saver DIP Switches. Allows the fan to operate in continuous or cycle
mode while the unit is in heating or cooling mode. DIP Switch 3: Continuous
and allows the fan to run continuously, circulating air even when the
temperature setting has been satisfied. DIP Switch.
Wall Thermostat Enable
Fan Continuous Run for Heating.
12 345 67
Freeze Guard Setpoint Limit 2 Setpoint Limit 1 Fan CON/CYC for Cooling/ Energy
Saver: Cooling Fan CON/CYC for Heating Energy Saver: Heating Wall Thermostat
Enable Electric Heat Only for Heat Pumps
Down Heat Pump
Control Panel Enable
Fan Cycle for Heat
Default Down
Down
Remarks
For only heat pump units.
Down
16
PTAC-SVX004A-EN
System Configuration
Table 5. DIP Switch Descriptions (continued)
DIP Switch Number
Up
4: Energy Saver DIP Switches. Allows the fan to cycle ON and OFF with the
compressor or electric heater. The fan stops a short time after the
temperature setting is satisfied. This is the most efficient mode for
electrical usage.
5/6: Setpoint Temperature Limits. Provides a range of temperature control.
Fan Cycle for Cool.
Up/Up 68°F to 75°
F (20°C to
24°C)
Up/Down 63°F to 80°
F (17°C to
28°C)
Down
Fan Continuous Run for Cooling
Down/Up 65°F to
78°F (18°C to
26°C)
Default Down
Down/ Down 61°F to 86°
F (16°C to
30°C)
Down/ Down
7: Room Freeze Protection. If the unit senses a room temperature below 40°F (4.44°C), the fan motor and electric strip heat turns ON and warms the room to 50° F (10°C). The fan stops a short time after the temperature is satisfied.
Freeze Guard Disable
Freeze Guard Enable
Down
Remarks
Configurations 5 and 6 combine to select set point range. When setpoint limit
set, display always shows full range.
Keypad Configuration
The Trane ProSpace can be customized by configuring the keypad.
1. To enter the keypad configuration screen, first power up the unit.
2. Within the 30 seconds after power-up press and hold both the fan speed and
Cooler button for five (5) seconds.
Note: If waiting more than 30 seconds after powerup, you cannot access the
keypad configuration. Power down and power up the unit again to restart the
process.
3. To scroll through the available options, press and release the fan speed
button to select the keypad configurations. The stored value displays.
4. To exit the configuration screen, press the mode button or after 30
seconds, the unit will automatically exit the configuration screen.
5. To modify configuration settings, press and release simultaneously, either
the Setpoint and Warmer button or Setpoint and Cooler button . Choose from the
following four (4) options:
· Fahrenheit/Celsius Display Switch; changes between degrees Fahrenheit (F,
default) and Celsius (C) on the display.
· Indoor Air Temperature Sensor Biasing for Cooling Mode; adjusts the room air
temperature reading when in cooling mode (not normally required).
· Indoor Air Temperature Sensor Biasing for Heating Mode; adjusts the room air
temperature reading when in heating mode (not normally required).
· Indoor Temperature Display; changes between showing the setpoint or desired
temperature during heating and cooling modes (SP, default) or displaying the
actual room temperature during heating and cooling modes (AA).
Selecting SP displays the desired setpoint temperature during heating and
cooling modes, regardless of what the actual temperature is in the room .
Selecting AA displays the room temperature during heating, cooling, and fan-
only modes
Changing the mode button to either heating or cooling modes displays the
setpoint for 10 seconds. After the 10 seconds, the room temperature displays.
Depressing the ON-OFF when the unit is OFF, and the last mode was either
cooling or heating, the setpoint displays for 10 seconds before displaying the
room temperature.
Depressing either Warmer button or Cooler button during heating and cooling
mode displays the setpoint for 10 seconds before displaying the room
temperature.
6. Press Warmer button or Cooler button to switch between Emergency Auto
Cooling Allowed (displays as CA) and Emergency Auto Cooling Rejected (displays
as CD).
7. When activating Auto Cooling Operation and room temperature reaches 85°F
while the unit is in the STOP mode, the unit automatically starts in Air
Conditioning Operation and shuts off when the room temperature reaches 80°F.
PTAC-SVX004A-EN
17
Auxillary Controls
Wiring the Wall Thermostat WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury. When it is
necessary to work with live electrical components, have a qualified licensed
electrician or other individual who has been properly trained in handling live
electrical components perform these tasks.
NOTICE
Equipment Damage!
Failure to follow instructions will result in premature failure of the unit.
Improper wiring may damage unit electronics. Common busing is not permitted.
Damage or erratic operation may result. After installing control panel
blockoff PLT05872, the previous control board should be retained to access
event diagnostic codes, if needed in the future.
To wire the to the thermostat: 1. Check to be sure power to unit is
disconnected. 2. Route the wire through the thermostat under the
sleeve and behind the front panel as shown below.
THERMOSTAT WIRE ROUTING (UNDER SLEEVE, BEHIND FRONT PANEL)
3. Remove the terminal connector to simplify wiring.
4. Connect wires from the thermostat to terminals on unit terminal connector.
Note: Thermostat wire is field supplied. Recommended wire gauge is 18 to 20
gauge, solid thermostat wire. Important: Thermostat wire should always be
routed around or under the wall sleeve, NEVER through the wall sleeve.
18
PTAC-SVX004A-EN
Energy Management (24 Vac) Common
R
W Y
O GH
GL
C
· R; 24 Vac · W; Electric Heat · Y; Compressor · O; Reversing Valve (Heat Pump
Unit Connection
Only) · GH; High Fan · GL; Low Fan · C; Common (Typically for Digital
Thermostats) Note: Any incorrect input combinations are
captured as thermostat wiring failures and will light the STATUS LED indicator
on main board. 5. Reinstall terminal connector. 6. Ensure that unit is
configured for wall thermostat enable. See Table 5, p. 16 (DIP switch setting
for wall thermostat). 7. Replace control panel label with control panel guard.
8. Power-up the unit. General Notes: · Anytime there is a second-stage call
for heating from the wall thermostat,, the unit automatically switches over to
electric heating for heat pump models. · For thermostats with two (2) fan
speed output (such
Auxillary Controls
as Low fan or Hi fan), the fan speed is determined by how the terminal
connector is wired. When using Low fan speed, wire the GL output from the
thermostat to GL on the terminal block. When using Hi fan speed, wire the GH
output from the thermostat to GH on the terminal block. .
Energy Management Input (Front Desk Control)
The controller can handle a switch signal from remote energy management input,
called an EM signal or front desk control. The input must be 24 Vac. When the
system receives a 24 Vac signal, it turns OFF the unit; otherwise it is in
normal control. This function is disabled under Freeze Guard protection.
Intelligent Self-Checking Control
The PTAC has an on-board computer continuously checks key components of the
unit to ensure they are operating properly. Under normal operation, the unit
status indicator (STATUS, on main PCB), light is steadily ON. If there is a
major problem, the unit shuts down and displays a diagnostic failure code on
the control. If it is a minor error and the unit can correct it by itself, the
diagnostic code is flashed on the status LED that is easily seen when the
front panel is removed. Refer to the following table of diagnostic codes.
Notes:
· When using a room thermostat, diagnostic codes are not viewable. These codes
are only viewable on the unit control board.
· After the compressor cycles three times the F0 code can appear if the
refrigerant charge is low.
PTAC-SVX004A-EN
19
Operation
The following sections describe the operation of the Trane ProSpace unit.
Control Buttons and Functions
The section describes the buttons and functionality of the Trane ProSpace
unit. · ON/OFF; turns the unit ON or OFF. · Mode; switches between Cool, Fan,
Heat, or Dry
(optional). Pressing this button when in OFF mode and the controller resumes
to the operation status before power-off. · WARMER or COOLER; the dual8 nixie
tube displays the indoor temperature for 15 seconds and then turns OFF. It is
used to increase/decrease the temperature or timer setting. · Fan; sets the
High, Medium, Low or Auto fan speeds. · Timer; sets the timer function by
using either of the buttons on the control panel or by the remote controller.
Timer ON function; the timer can be set to ON
when the unit is OFF. Setting range is between O.5 hours to 24 hours. When
timer ON setting is reached, the system stops and operates according to the
set mode. Timer OFF function; When the unit is off, timer OFF can be set.
Setting range is between O.5 hours, to 24 hours. When timer OFF setting is
reached, the system stops operation. Timer Preview function: use this
function to preview the remaining time of timer. · Sleep function; can only be
set only using the remote controller. · Dry function; This operational mode
will help to manage and reduce the humidity in the room, making it more
comfortable. In Dry mode the unit will operate cooling at low fan speed until
the room temperature is 4 degrees F below the room temperature setting
regardless of fan mode selection. This operation will drive more moisture
20
out by subcooling the space at low speed until 4 degrees below room set point.
The fan will run continuous. No other fan settings will override this
continuous fan operation of the Dry mode. Dry mode is NOT available when a
wall thermostat is installed. This Dry mode is only available via the unit
mounted controls. These unit mounted controls are disabled and may even be
removed when wall thermostats are installed. Dry mode or function should not
be considered a substitute for a stand-alone dehumidifier.
· Buzzer option; when the controller is energized, or when a valid remote
control signal or /button signal is received, the buzzer beeps.
· Auto Fan Speed function; can be automatically selected according to
different modes or indoor temperature to achieve a higher comfort level.
· Emergency Cooling Operation function; When the indoor ambient temperature is
86°F (30°C), the unit starts cooling automatically. When the indoor ambient
reaches 80.6°F (27°C), the unit stops operation.
· F-code Remote Controller function; optional.
LED Display and Digital Display
LEDs
The unit has two (2) 8-segment nixie tubes and eleven (11) LEDs on the main
board. Each LED is lit for the corresponding set mode. Indicators LEDs are:
· High
· Low
· Auto
· Indoor Temperature
· Setpoint Temperature
· Dry
· Cool
· Constant Fan
· Heat
· Timer
· ON/OFF
Digital Display
When in cooling or heating mode, the digital display defaults to the set
temperature. In Fan Mode, it displays indoor ambient temperature. When the
display has three digits, the digital is rolling to display values.
When there is error or protection code displayed, the STATUS LED blinks. In
OFF mode, the digital does not display the error code (except the low
temperature
PTAC-SVX004A-EN
protection). The unit does not display protection status codes 8, 9, or 10.
When multiple protection codes overlap, they cycle through the display without
priority. Refer to Table 8, p. 33 for a list of error codes.
Note: If there is an error with the temperature sensor, only the indoor fan
responds in cooling mode. Other loads do not respond, but the buttons are
still valid.
Mode Functions
Cooling Mode Functions
· When the ambient temperature is 2°F above setpoint, the unit operates under
cooling. Both the outdoor fan and indoor fan operate in the set speed. When
the starting condition of compressor is reached, outdoor fan operates and
compressor begins operation 10 seconds later.
· When the ambient temperature reaches 2°F below setpoint, the unit stops
operation, whereby, the compressor and outdoor fan stop operation. Under
indoor fan cycle mode, the indoor fan stops operation after operating at set
fan speed for 60 seconds (except when it requires the indoor fan to operate in
protection mode). If the fan cycle mode is not selected, the indoor fan
operates at the set fan speed.
· When the indoor fan is set at high speed, the outdoor fan operates at high
speed.
· When the indoor fan is set at low speed, outdoor fan operates at low speed.
· When the unit starts in cooling mode for the first time and the indoor fan
is set to low speed, the outdoor fan starts at high speed. After operating for
3-1/2 minutes and the outdoor tube temperature is below 140°F (60°C), the
outdoor fan switches over to low speed. First time start-up includes, when
switching to low speed cooling from non-cooling mode or when the unit starts
low speed cooling for the first time or enter low speed cooling after a power
failure.
· During cooling mode, and when there is no outdoor condenser high temperature
condition, the unit stops:
When it reaches the setpoint.
When the unit stops for a temperature sensor error.
When the unit stops for freeze protection.
When the start-up condition of outdoor fan is met.
When the indoor fan operates at high fan speed for 3 seconds and then turn
to set fan speed.
If high temperature protection occurs during cooling mode, the outdoor fan is
forced to operate at high speed. When the start-up
PTAC-SVX004A-EN
Operation
condition of outdoor fan in heating mode is met, the outdoor fan operates at
high fan speed for 3 seconds and then turns ON to set the fan speed. When the
indoor fan starts operation, the indoor fan operates at high fan speed for 3
seconds and then turns ON to set fan speed.
· Press the Constant Fan button when in cooling or heating mode to turn ON/OFF
the constant fan function. this function is invalid in wired controller mode.
If constant fan mode is ON, the fan motor constantly operates. If constant fan
mode is OFF, the fan stops as the load stops. The fan speed is controlled by
the Fan Speed button (if a wired controller is connected, the fan speed
follows the command of wired controller). The controller controls whether the
fan is operating or not. The status does not change when:
Switching modes.
When turning the unit ON/OFF.
Switching to wired controller mode.
Switching to panel mode.
Energizing after a power failure.
Heating Mode Functions
When the heating mode LED is lit, and the set fan speed LED is ON. The digital
display shows the set temperature. If select displaying ambient temperature in
additional function setting, the digital display shows as described in this
mode. The set temperature and fan speed will keep the same when switching
modes.
Function
For Heat Pump (General Type)
Note: The electric heater and compressor cannot operate at the same time.
· When ambient temperature of the space is 2°F below setpoint, the compressor
operates in heating mode. The four-way valve and both the indoor/ outdoor fans
start operation at set speed. After 10 seconds, the compressor begins
operation. If the compressor operates and satisfies the setpoint and minimum
operation time of the compressor, then both the compressor and indoor/outdoor
fans deenergize. If the compressor does not meet setpoint and the ambient
temperature drops to 5°F below setpoint, the compressor de-energizes and after
one second, the electric heater starts. The electric heater remains in
operation until the setpoint +2°F is satisfied.
Note: The minimum compressor run time is 6 minutes
· When there is a call for heat and the compressor cannot be energized due to
the protection function, the electric heat energizes after 15 seconds and
remains energized until the setpoint +2°F is satisfied.
21
Operation
Heat/Cool (Pure Electric Heating)
· When the ambient temperature of the space is 2°F below setpoint, the
electric heater starts operating and the indoor fan operates at the set fan
speed. When the setpoint +2°F is satisfied, the electric heater stops
operating. When in fan cycle mode, the indoor fan operates at the condition of
circulating residual heat. If the fan cycle mode is not selected, the indoor
fan operates at the set fan speed.
Auto Fan Speed Mode
· Cooling Mode:
Note: Under Auto Fan Speed control in any mode, there is a 3-1/2 minute delay
when switching the speed of the indoor fan.
High Speed; when the ambient temperature is 4°F higher than setpoint.
Low Speed; when ambient temperature is less than setpoint.
Not Change; when the ambient temperature is 1°F to 4°F higher than setpoint.
· Heating Mode:
High Speed; when the ambient temperature is 4°F lower than setpoint.
Low Speed; when ambient temperature is more than setpoint.
Not Change; when the ambient temperature is 1°F to 4°F lower than setpoint.
Additional Functions
After the unit is turned ON for 30 seconds, press and hold Cooling Button for
5 seconds to start up the configuration mode. After entering this mode, if
adjusting the temperature compensation value by buttons to turn to unit ON/OFF
condition, the load will be activated after 3 seconds. While if entering unit
on or off condition due to the change of the ambient temperature, it can be
activated only after quitting the configuration mode. The following functions
are available when selecting the Low Button:
· Fahrenheit/Celsius Mode: press Warming Button or Cooling Button to switch
between F° or C°.
· Adjusting Cooling or Heating Values: press Warming Button or Cooling Button
to increase/decrease the temperature values in 1° increments. The adjusting
range of the indoor ambient temperature compensation value is between -6°F and
6°F (-3°C and 3°C). The compensation temperature defaults to 0°F in either
cooling or heating mode. The unit can allocate different compensation
temperatures in cooling or heating mode, respectively.
Note: Trane recommends leaving the compensation value set to its default of
0°F.
22
· Display Switchover Between Set Temperature/ Ambient Temperature Mode: press
Warming Button or Cooling Button to set either set temperature or ambient
temperature.
· Set Temperature Display: the digital display shows SP. After quitting
configuration mode, the set temperature displays constantly in either heating
or cooling mode.
· Ambient Temperature Display: The digital display shows AA. After quitting
configuration mode, the ambient temperature displays constantly in either
heating or cooling mode. Under certain circumstances, the unit displays the
set temperature for 10 second and then switches to display ambient temperature
as follows: Press mode button (mode button includes Cool button and Heat
button). Re-energize after power failure. Restart the unit. Turn on the
unit after EM turns off unit. Adjust the set temperature using the Warming
Button or Cooling Button .
· Quitting Configuration Mode: is stopped when pressing the mode button or if
no button is pressed within 30 seconds.
Resetting Timer Press Warming Button or Cooling Button simultaneously for 3
seconds under the protection for compressor and electric heater minimum stop
time or the protection for compressor minimum operation time, reduces the
protection time. Memory The controller runs to the last mode set prior to a
power failure. The following settings are also retained prior to a power
failure: · Operation mode. · Set fan speed. · Set temperature. · value in
minimum stop time of compressor. · Fahrenheit/Celsius display mode. · Cooling
compensation temperature.
The unit operates in default Fan Mode when there is no memory. Fan speed is
set to high with the T-value of 0 and Fahrenheit display mode. Cooling
compensation temperature is 0 and heating compensation temperature is 0. The
default set temperature is 71°F (22°C). The digital display shows the set
temperature under cooling and heating mode.
PTAC-SVX004A-EN
Restore Factory Settings
When pressing the Low button and p for 3 seconds, the digital display shows 00
for 3 seconds in standby and OFF status. This indicates that the factory
settings have been restored. The configuration information defaults to
display:
· Fahrenheit.
· Heating compensation temperature of 0.
· Cooling compensation of 0.
· Set temperature.
The T-value is 0, the Fan Speed is set to High, and the set temperature is
71°F (22°C).
Operating the Remote Control
The optional ProSpace remote control has many of the features that are
accessible through the ProSpace front panel. Ensure that there are no
obstructions between the receiver and the remote controller.
Important: Do not drop or throw the remote control. Do not spill any liquids
in the remote control. Do not put the remote control directly into the
sunlight or near hot surfaces.
ON OFF
AUTO
SWING
COOL DRY FAN HEAT
°F OPER °C AUTO .5H
SLEEP LOCK SPEED
ON / OFF
MODE
FAN SLEEP
SWING TIMER
· ON / OFF; press to turn ON the unit and press again to turn OFF the unit.
When turning ON / OFF the unit, the Timer and Sleep functions are cancelled,
but the pre-setting time is retained.
PTAC-SVX004A-EN
Operation
· MODE; press to cycle through the mode selections in the following order:
Cool to Dry to Fan to Heat. In Heat mode, the initial value is 82°F (28°C) and
in other modes, the initial value is 77°F (25°C).
Note: Heat Mode is only for cooling/heating units. If in Cooling Mode, there
is no action taken when the unit receives a call for heating. Blow-over heat:
when the unit is running in Heat Mode or Auto Heat Mode, the compressor and
indoor fan running, to turn the unit off, the compressor, outdoor fan will
stop running. The upper and lower guide boards rotate to a horizontal
position, the indoor fan run at LOW FAN speed, and the 10 seconds later, the
unit turns OFF.
· FAN; press to cycle through the fan speed selection in the following order:
AUTO to FAN 1 to FAN 2. The speeds are represented on the remote as vertical
bars increasing in size for each speed. When initializing the fan, the AUTO
setting is default.
Note: Only LOW Fan Mode can be selected in DRY mode. Pressing this key can not
adjust the fan speed, but can send message to the unit.
· SLEEP; Press to select SLEEP ON/OFF. When powering the unit, the SLEEP OFF
setting is default. After setup is complete, the signal for SLEEP Mode
displays on the unit. While in SLEEP Mode, the TIMER setting can be adjusted.
SLEEP Mode is not available in FAN and AUTO Modes. Once the unit is turned
OFF, the SLEEP Mode is cancelled.
· SWING; not used.
· TIMER; in SWITCH OFF state, press this key to set the time for AUTO SWITCH
ON state. The range of setting is between O.5 hours to 24 hours. The
characters T-ON and H flash for 5 seconds and within this 5second flash,
press this key once to complete the setting and send the message to the unit.
If this setting is valid, the set time displays for 2 seconds before
displaying the temperature message. During the 5second flash, press + key to
increase the time value and – to decrease the value. The values
increase/decrease in increments of 0.5 hours with each press of the key.
Pressing this key in rapid successions to increase/decrease the values will
advance the increments quickly. The remote controller can increase the set
time by 0.5 hours every 0.25 seconds. After energizing the unit, the default
is NO TIMER setting and the T-ON or H characters do not display. When the
temperature display becomes constant, press this key again to display the
remaining set time. The time values, TON and H, display constantly for 2
seconds. After 2 seconds, the preset temperature displays. Within these 2
seconds, press this key again to CANCEL the AUTO SWITCH ON and send the
message. Pressing this key in SWITCH ON state allows the time to be set to
AUTO SWITCH OFF. Press ON/OFF
23
Operation
key to switch on the unit and CANCEL the AUTO SWITCH ON state.
Note: The +/- buttons are used to increase/decrease value settings for either
time or temperature. Refer to the sub-sections below about how to use the +/-
buttons to set temperature values.
+ Button; press this button to set increased temperature values when unit is
ON. Continuously press and hold this button for more than 2 seconds until °F
(°C) displays. In AUTO Mode, the temperature can not be set up, but this
button can send the signal. Temperature ranges are between 61°F and 86°F (16°C
and 30°C).
Note: To switch between Fahrenheit and Celsius, press and hold the – and MODE
keys simultaneously while in SWITCH OFF state.
– Button; .press this button to set decreased temperature values when unit
is ON. Continuously press and hold this button for two seconds to decrease the
temperature value. The temperature adjustment is unavailable in AUTO Mode, but
this button can send the signal.
· LOCK; to LOCK and UNLOCK (default) the keypad, press and hold the – or + and
MODE keys simultaneously while in either SWITCH ONSWITCH OFF states. The unit
show the LOCK icon when in LOCK Mode, in which case, the lock icon flashes
three (3) times upon operation of any key. The LOCK icon does not display when
the unit is in UNLOCK Mode.
Changing Batteries in the Remote Control
The remote requires two (2) AAA, 1.5V batteries.
1. From the back side of the remote, gently press down on the battery cover
and slide it towards the bottom of the unit.
2. Remove the old batteries from the battery compartment.
3. Insert two (2) new batteries into the battery compartment. Ensure the
batteries poles match the polarity when inserting them into the battery
compartment: + to + and – to -.
Note: Only use the recommended battery type. If the remote has not been used
for an extended period of time, check the expiration date on the batteries or
check for battery leakage.
4. Slide the battery cover back onto the remote until the tab clicks.
BEST PRACTICE: Check your local city/state for proper recycling procedures. A
battery is an electrochemical device with the ability to convert chemical
energy to electrical energy to provide power to electronic devices. Batteries
contain heavy metals such as mercury, lead, cadmium, and nickel, which can
contaminate the environment when batteries are improperly disposed of. When
incinerated, certain metals might be released into the air or can concentrate
in the ash produced by the combustion process. Batteries may produce the
following potential problems or hazards:
· Pollute the lakes and streams as the metals vaporize into the air when
burned
· Contribute to heavy metals that potentially may leach from solid waste
landfills.
· Expose the environment and water to lead and acid.
· Contain strong corrosive acids. May cause burns or danger to eyes and skin.
24
PTAC-SVX004A-EN
Care and Cleaning
Periodic care and cleaning of the ProSpace unit is essential to keep it
running efficiently.
Front Panel and Case
Turn unit off and disconnect power supply. To clean, use a soft brush, water,
and a mild detergent. DO NOT use bleach or abrasives. Some commercial cleaners
may damage the plastic parts.
Outdoor Coil
Important: Product failure due to improper care or lack of maintenance is not
covered under warranty. Airflow restriction may cause damage to the unit.
Coil on outdoor side of unit should be checked regularly. Unit will need to be
removed from its sleeve to inspect dirt build-up that can occur inside of the
coil. If clogged with dirt or soot, the coil should be professionally cleaned.
Clean inside and outside of outdoor coils regularly. Note: Never use a high-
pressure sprayer on the coil.
Coils Grille
Base Pan
In some installations, dirt or other debris may be blown into unit from
outside and settle in the base pan (bottom of the unit). Check the base pan
periodically and clean if required.
Air Filter
Important: Do not the operate unit without filters in place. If a filter
becomes torn or damaged, it should be replaced immediately. Operating without
filters in place or with damaged filters will allow dirt and dust to reach
indoor coil and reduce cooling, heating, airflow, and the efficiency of the
unit. Airflow restriction may cause damage to unit.
This unit contains two (2) air filters. To maintain unit efficiency, clean the
filter at least every 30 days (or sooner depending on application). Keeping
filter clean:
· Decreases the cost of operation.
· Saves energy.
· Prevents a clogged indoor coil.
· Reduces the risk of premature component failure.
To clean the air filter, vacuum off any heavy soil and contaminates. Run water
through the filter and then dry thoroughly before replacing them back into the
unit.
Pull up
2 Air filters
Push down
Removing Air Filter
Replacing Air Filter
Use the following checklist to ensure proper care of the ProSpace unit.
Equipment operation should be checked and verified several times during each
year.
Clean both sides of outdoor coil. (Never use high pressure spray on coils.)
Clean base pan and outdoor vent filter. Clean outdoor orifice and fan. Clean
indoor coil. (Never use high pressure spray
on coils.)
Clean indoor fan, wire screen and front panel. Clean or install new indoor –
air inlet filter(s). Clean wall sleeve and outdoor grille. Inspect cord and
receptacle. Secure electrical connections. Ensure front panel is properly
mounted and not
damaged.
Ensure wall sleeve is installed properly. Ensure heat and cool cycles operate
properly.
PTAC-SVX004A-EN
25
Service Installation
WARNING
Unit Contains R32 Refrigerant!
Failure to follow proper procedures can result in equipment damage or personal
injury.
This unit contains R32 refrigerant which is flammable and odorless.
A2L Read the installation manual
properly before installing or servicing this unit.
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers,
and labels could result in death or serious injury. Technicians, in order to
protect themselves from potential electrical, mechanical, and chemical
hazards, MUST follow precautions in this manual and on the tags, stickers, and
labels, as well as the following instructions: Unless specified otherwise,
disconnect all electrical power including remote disconnect and discharge all
energy storing devices such as capacitors before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently
energized. When necessary to work with live electrical components, have a
qualified licensed electrician or other individual who has been trained in
handling live electrical components perform these tasks.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious
injury. Disconnect all electric power, including remote disconnects before
servicing. Follow proper lockout/tagout procedures to ensure the power can not
be inadvertently energized. Verify that no power is present with a voltmeter.
WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury. When it is
necessary to work with live electrical components, have a qualified licensed
electrician or other individual who has been properly trained in handling live
electrical components perform these tasks.
26
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death
or serious injury. Technicians, in order to protect themselves from potential
electrical, mechanical, and chemical hazards, MUST follow precautions in this
manual and on the tags, stickers, and labels, as well as the instructions
below:
· Before installing/servicing this unit, technicians MUST put on all PPE
required for the work being undertaken (Examples; cut resistant
gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing). ALWAYS refer to
appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
· When working with or around hazardous chemicals, ALWAYS refer to the
appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and
Labelling of Chemicals) guidelines for information on allowable personal
exposure levels, proper respiratory protection and handling instructions.
· If there is a risk of energized electrical contact, arc, or flash,
technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other
country-specific requirements for arc flash protection, PRIOR to servicing the
unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT
PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND
EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
WARNING
Hazardous Voltage and Gas!
Failure to turn off gas or disconnect power before servicing could result in
an explosion or electrocution which could result in death or serious injury.
Turn off the gas supply and disconnect all electric power, including remote
disconnects, before servicing the unit. Follow proper lockout/tagout
procedures to ensure the power can not be inadvertently energized.
PTAC-SVX004A-EN
Disassembling the Unit
1. Grasp filter and pull upwards to remove it from the unit.
5. Remove the screw holding the guard board and pull is upwards to remove it.
2. Remove the front panel from the unit by grasping the bottom corners and gently pushing in to release the cantilever snap joints.
6. Remove the three (3) screws holding the right bracket and then remove the right bracket.
3. Remove the seven (7) screws holding the grille.
7. Remove the four (4) screws holding the middle connection board and then remove the middle connection board.
4. Remove the three (3) screws holding the left bracket and then remove the left bracket.
8. Remove the six (6) screws holding the guard net and then remove the guard net.
PTAC-SVX004A-EN
9. Remove the four (4) screws holding the top panel sub-assembly and then
remove the sub-assembly.
27
Disassembling the Unit
14. Remove four (4) screws holding the right-side baffle plate for the
electric box and then remove the rightside baffle plate.
10. Removed the screw holding the control cover plate and pull out the wiring
terminal connecting the control cover plate and the electric box. Then, remove
the cover plate and electric box.
15. Remove seven (7) screws holding the right-side plate for the electric box
and then remove the rightside plate.
11. Remove four (4) screws holding the display board and then remove the
display board.
12. Remove four (4) screws holding the baffle plate for the electric box and then remove the baffle plate.
16. Remove two (2) screws holding the front cover of the electric box and
then remove the front cover.
17. Remove three (3) screws holding the electric box and then remove the
electric box.
13. Pull out the motor wiring terminal.
28
18. Remove seven (7) screws holding the middle PTAC-SVX004A-EN
connection board and then remove the middle connection board.
Disassembling the Unit
22. Unsolder the spot weld between the capillary subassembly and condenser
Remove the capillary.
23. Remove six (6) screws holding the guide loop subassembly and then pull
upwards to remove the guide loop sub-assembly.
19. Remove the screw holding the cable cross and then remove the cable cross.
WARNING
Recover Refrigerant!
Please be sure to recover refrigerant per standard procedures and guidelines
before proceeding with additional steps below.
20. Unsolder the spot weld between the 4-way valve and the compressor,
condenser, and the evaporator. Remove the 4-way valve.
24. Remove the nuts holding the axial flow blade and the pull outwards to remove the axial flow blade.
21. Remove three (3) nuts holding the compressor and then remove the compressor.
25. Remove four (4) screws holding the motor and then remove the motor.
PTAC-SVX004A-EN
29
Disassembling the Unit
26. Remove four (4) screws holding the middle connection board and then
remove the middle connection board.
30. Remove four (4) screws holding the motor and then remove the motor.
27. Remove four (4) screws holding the propeller housing and then remove the propeller housing.
28. Remove three (3) screws holding the blade end cap sub-assembly and then remove the blade end cap sub-assembly.
31. Remove six (6) screws holding the electric heater and then remove the
electric heater.
32. Pull the evaporator upwards to remove, the remove three (3) screws
holding the condenser. Pull upwards to remove the condenser.
29. Remove screw holding the cross-flow blade and then remove the cross-flow blade.
30
PTAC-SVX004A-EN
Temperature and Resistance Charts
Table 6. Ambient Temperature Sensors for Indoor/Outdoor, 15K
PTAC-SVX004A-EN
31
Temperature and Resistance Charts
Table 7. Tube Temperature Sensors for Indoor/Outdoor, 20K
32
PTAC-SVX004A-EN
Troubleshooting and Resources
Troubleshooting Error Codes and Malfunctions
Table 8. Digital Display Error Codes
Control Board Display
F0
Status LED Number of Flashes Followed by 3 second delay
Green Light On Constant (Normal Operation)
Code Description
Refrigerant loss or sensor issue
F1
1 Flash
Indoor ambient temperature sensor open or short circuited
F2
2 Flashes
Indoor coil tube
temperature sensor
open or short circuited
F4
4 Flashes
Outdoor coil tube
temperature sensor
open or short circuited
FJ(a)
Green Light On Constant (Normal Operation)
Outlet air temperature sensor failure
FP(a)
Green Light On Constant (Normal Operation)
Low temperature prevention protection
Explanation
Troubleshooting
Indoor ambient sensor or indoor tube sensor failure or disconnected.
(yellow/white wire black plug) or (white plug, black wire).
Indoor ambient sensor (RT2) at 77 degrees F = 15K ohms (yellow/white wire
black plug).
Indoor Coil Tube sensor (RT1) at 77 degrees F = 20K ohms (black plug, black
wire).
Outdoor Tube sensor (RT3) at 77 degrees F = 20K ohms (white plug, black wire).
Outlet air temperature sensor (DAHT) at 77 degrees = 20K ohms (red plug, black
wire).
Indoor ambient temperature below 40 degrees F
1. Inspect the unit, specifically the refrigerant system for leaks or visible
damage.
2. Observe the refrigerant circuit temperatures.
3. On the condenser coil there is a “tube temperature sensor”. It is inserted
into a sleeve that is brazed to coil. Verify that the tube temperature sensor
is inserted snuggly into the sleeve. If it is not, insert into the sleeve.
4. Inspect the ambient temperature sensor located in front of the evaporator
coil. Ensure that the sensor is secure in the plastic holders and that it is
not touching the evaporator coil.
5. Inspect the board located inside the compartment that is located below the
on board mounted controls. Verify that the inner tube temp. and the outer tube
temp. Sensors are plugged into the board correctly and not reversed. (If they
are reversed, it can cause the code to appear.)
1. Check the sensor wiring and connections to the main board.
2. Test the resistance of the sensor while disconnected.
3. Replace the main board if needed.
1. Check the sensor wiring and connections to the main board.
2. Test the resistance of the sensor while disconnected.
3. Replace the main board if needed.
1. Check the sensor wiring and connections to the main board.
2. Test the resistance of the sensor while disconnected.
3. Replace the main board if needed.
1. Check the sensor wiring and connections to the main board.
2. Test the resistance of the sensor while disconnected.
3. Replace the main board if needed.
1. Check the sensor wiring and connections to the main board.
2. Test the resistance of the sensor while disconnected.
3. Replace the main board if needed.
PTAC-SVX004A-EN
33
Troubleshooting and Resources
Table 8. Digital Display Error Codes (continued)
Control Board Display
Status LED Number of Flashes Followed by 3 second delay
Code Description
Explanation
Troubleshooting
H3(a)
Green Light On Constant (Normal Operation)
Overload protection detection
Voltage is too low / condenser coil dirty / outdoor fan damaged / compressor failed
1. Power supply voltage is low. 2. Condenser coil is dirty.
3. Outdoor fan is damaged or failed.
4. Compressor failed.
E5(a)
Green Light On Constant (Normal Operation)
Overcurrent protection of compressor
Voltage is too low / condenser coil dirty / outdoor fan damaged / compressor failed
1. Power supply voltage is low. 2. Condenser coil is dirty.
3. Outdoor fan is damaged or failed.
4. Compressor failed.
A2(a)
Green Light On Constant (Normal Operation)
Malfunction protection for electric heat
Unit current is too high / electric heater is damaged / open circuit
1. Power supply voltage is high. 2. Check for any breaks in the wires.
3. Replace the main board number two.
4. The indoor fan is damaged.
5. Replace the electric heater.
U5(a)
Green Light On Constant (Normal Operation)
Unbalanced electric current
All loads are stopped
1. Wires are not connected or inserted correctly.
2. Electric heater is short-circuited or not connected tightly.
3. There is an electric leakage.
A0(a)
Green Light On Constant (Normal Operation)
Electric heater combination wrong
All loads are stopped
1. Wires are not inserted correctly. 2. Electric heater is broken.
A4(a) C7(a)
Green Light On Constant (Normal Operation)
Electric heater current abnormal
All loads are stopped
Green Light On Constant (Normal Operation)
Temperature protection All loads are stopped time too long
5 flashes (unit remains operational)
Freeze prevention protection for evaporator
Indoor tube temperature is too low in cooling mode
1. Part of electric heater is broken or short-circuited.
2. Electric Heater is abnormal.
1. Temperature limiter is broken.
2. Connection wire of loads of electric heater is broken.
6 flashes 7 flashes
High temperature protection for outdoor condenser
Frost prevention (heat pump)
Outdoor tube temperature is low in heat pump mode. This is normal operation in cold outdoor ambient temperatures. Electric heat will cycle as needed.
8 flashes
High temperature protection for evaporator
Indoor tube temperature is high in heat pump mode.
9 flashes
Wrong wire connection indicated for wired controller
(a) These codes will only be shown on the unit display board. When a unit is being operated from a wireless or wired thermostat, the codes won’t be visble. Change Dip Switch 2 (down – disabling thermostat) to diagnose with controller. Remove power and power back up.
34
PTAC-SVX004A-EN
Troubleshooting and Resources
Table 9. Malfunction Causes and Solutions
Status
After energizing, operation indicator is not bright and the buzzer does not
sound. Under normal power supply situations, the operation indicator is not
bright after energizing.
After energizing, the room circuit breakers immediately trips OFF. After
energizing, the air switch trips OFF. After energizing, the operation
indicator is bright while there is no display on the remote controller or the
buttons have no action.
Fan motor not operating. Filter blockage. Unit is not heating or cooling
properly in heat pump mode or cool pump mode. Unit is not heating or cooling
properly in heat pump mode or cool pump mode.
Compressor is not operating.
Electric heat elements not energizing.
Electric heat element not energizing.
Protection of temperature limiter.
When turning ON the unit, the heating effect is poor.
Unit is not heating.
Wrong wire connection or a poor connection. Wire harness connected to main
board has a poor connection. Using a universal multi-meter measure the
capacitance of the capacitor in micro farads. If the measured capacitance is
not the same as rated capacitance the capacitor is damaged.
Wrong wire connection or a poor connection. Compressor relay on main board is
damaged or the wire harness of the compressor is loose.
Compressor capacitor is damaged.
Cause
Solution
Air Conditioner Cannot Be Started No power supply or poor connection for power
plug.
Poor connection for wiring terminals.
Electric short.
Check for power failure. If so, wait for power recovery. If not, check power
supply circuit and ensure the power plug is complete inserted into wall
outlet.
Check the circuit according to the circuit diagram and properly connect the
wires. Ensure all wiring terminals are tightly connected.
Ensure the unit is properly grounded. Ensure the wires inside unit are
properly connected. Check the wiring inside the unit and whether the
insulation layer of the power cord is not damaged. If so, replace the power
cord.
Improper model selection for the air switch.
Select the proper air switch.
Malfunction of remote controller. Air Conditioner Is Cooling Poorly
Fan motor malfunction. Filter is blocked.
Replace the remote controller batteries. Repair or replace the remote
controller.
Refer to the table section below, “Fan Motor Does Not Operate” . Clean the
filter.
Capillary malfunction.
Refrigerant is leaking.
Compressor malfunction.
Electric Heater Provides Poor Heating
Heating relay on main board is damaged. Wiring harness between the main board
and display board is loose.
Air inlet blocked by objects. Malfunction of temperature limiter. Use a
universal meter to measure the two contact points of the temperature limiter.
If the resistance value is too large, the temperature limiter is damaged.
Fuse is burned out. Fan Motor Does Not Operate
Check the wiring status according to the circuit diagram.
Replace the capillary. Investigate the cause of the leaks and repair. Add any
necessary refrigerant. Refer to the table section below, “Compressor Does Not
Operate” .
Replace main board.
Check wiring harness connection. Clean the filter and remove any objects
obstructing the inlet.
Replace the temperature limiter. Measure resistance across fuse, If fuse is
bad, replace.
Connect the wires according to the wiring diagram to ensure all wiring
terminals are connected securely.
Check wire harness connection.
Ensure wire harness is connected securely.
Fan capacitor is damaged. Compressor Does Not Operate
Check the wiring status according to the wiring diagram.
Replace the fan capacitor.
Connect the wires according to the wiring diagram to ensure all wiring
terminals are connected securely.
Ensure the relay is functioning correctly in cooling/heat pump mode.
Using a universal meter measure the microfarad rating of the capacitor if it
is not the same as the rating listed on the capacitor it is damaged.
Replace the main board. Replace the compressor capacitor.
PTAC-SVX004A-EN
35
Troubleshooting and Resources
Table 9. Malfunction Causes and Solutions (continued)
Status Compressor coil burnt out. Compressor cannot operate.
There is water leakage indoors. There is water leakage indoors.
Cause Measured resistance between compressor terminals is 0 or open.
Compressor cylinder may be blocked. Air Conditioning Leaking
Drainage duct blocked.
Unit has incorrect pitch.
Solution
Replace the compressor. Open compressor to investigate. Replace the
compressor.
Eliminate any debris inside drainage duct. Ensure unit is pitched a 1/4″
downward from inside to outside the wall.
Technicians Guidelines
Aptitude requirement for maintenance man (repairs should be done only be
specialists).
1. Any person who is involved with working on or breaking into a refrigerant
circuit should hold a current valid certificate from an industry-accredited
assessment authority, which authorises their competence to handle refrigerants
safely in accordance with an industry recognised assessment specification
2. Servicing shall only be performed as recommended by the equipment
manufacturer. Maintenance and repair requiring the assistance of other skilled
personnel shall be carried out under the supervision of the person competent
in the use of flammable refrigerants.
Safety preparation work
The maximum refrigerant charge amount is shown on the table below:
Note: Please refer to the nameplate for the charging quantity of R32.
Prior to beginning work on systems containing flammable refrigerants, safety
checks are necessary to ensure that the risk of ignition is minimised. For
repair to the refrigerating system, the following precautions shall be
complied with prior to conducting work on the system.
· Work procedure
Work shall be undertaken under a controlled procedure so as to minimise the
risk of a flammable gas or vapour being present while the work is being
performed.
· General work area
All maintenance staff and others working in the local area shall be instructed
on the nature of work being carried out. Work in confined spaces shall be
avoided. The area around the workspace shall be sectioned off. Ensure that the
conditions within the area have been made safe by control of flammable
material.
· Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to
and during work, to
ensure the technician is aware of potentially toxic or flammable atmospheres.
Ensure that the leak detection equipment being used is suitable for use with
all applicable refrigerants, i.e. non-sparking, adequately sealed or
intrinsically safe.
· Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any
associated parts, appropriate fire extinguishing equipment shall be available
to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging
area.
· No ignition sources
No person carrying out work in relation to a refrigeration system which
involves exposing any pipe work shall use any sources of ignition in such a
manner that it may lead to the risk of fire or explosion. All possible
ignition sources, including cigarette smoking, should be kept sufficiently far
away from the site of installation, repairing, removing and disposal, during
which refrigerant can possibly be released to the surrounding space. Prior to
work taking place, the area around the equipment is to be surveyed to make
sure that there are no flammable hazards or ignition risks. “No Smoking” signs
shall be displayed.
· Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before
breaking into the system or conducting any hot work. A degree of ventilation
shall continue during the period that the work is carried out. The ventilation
should safely disperse any released refrigerant and preferably expel it
externally into the atmosphere.
· Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the
purpose and to the correct specification. At all times the manufacturer’s
maintenance and service guidelines shall be followed. If in doubt, consult the
manufacturer s ‘ technical department for assistance.
36
PTAC-SVX004A-EN
The following checks shall be applied to installations using flammable
refrigerants:
The actual refrigerant charge is in accordance with the room size within
which the refrigerant containing parts are installed;
The ventilation machinery and outlets are operating adequately and are not
obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit
shall be checked for the presence of refrigerant;
Marking to the equipment continues to be visible and legible. Markings and
signs that are illegible shall be corrected;
Refrigeration pipe or components are installed in a position where they are
unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components perare constructed of materials
which are inherently resistant to being corroded or are suitably protected
against being so corroded.
· Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety
checks and component inspection procedures. If a fault exists that could
compromise safety, then no electrical supply shall be connected to the circuit
until it is satisfactorily dealt with. If the fault cannot be corrected
immediately but it is necessary to continue operation, an adequate temporary
solution shall be used. This shall be reported to the owner of the equipment
so all parties are advised.
Initial safety checks shall include:
That capacitors are discharged: this shall be done in a safe manner to avoid
possibility of sparking;
That no live electrical components and wiring are exposed while charging,
recovering or purging the system;
That there is continuity of earth bonding.
Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be
disconnected from the equipment being worked upon prior to any removal of
sealed covers, etc. If it is absolutely necessary to have an electrical supply
to equipment during servicing, then a permanently operating form of leak
detection shall be located at the most critical point to warn of a potentially
hazardous situation.
Particular attention shall be paid to the following to ensure that by working
on electrical components, the casing is not altered in such a way that the
level of
PTAC-SVX004A-EN
Troubleshooting and Resources
protection is affected. This shall include damage to cables, excessive number
of connections, terminals not made to original specification, damage to seals,
incorrect fitting of glands, etc.
· Ensure that the apparatus is mounted securely.
· Ensure that seals or sealing materials have not degraded to the point that
they no longer serve the purpose of preventing the ingress of flammable
atmospheres. Replacement parts shall be in accordance with the manufacturer’s
specifications
Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit
without ensuring that this will not exceed the permissible voltage and current
permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while
live in the presence of a flammable atmosphere. The test apparatus shall be at
the correct rating.
Replace components only with parts specified by the manufacturer. Other parts
may result in the ignition of refrigerant in the atmosphere from a leak.
Note: The use of silicon sealant can inhibit the effectiveness of some types
of leak detection equipment. Intrinsically safe components do not have to be
isolated prior to working on them.
Cabling:
Check that cabling will not be subject to wear, corrosion, excessive pressure,
vibration, sharp edges or any other adverse environmental effects. The check
shall also take into account the effects of aging or continual vibration from
sources such as compressors or fans.
Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the
searching for or detection of refrigerant leaks. A halide torch (or any other
detector using a naked flame) shall not be used.
The following leak detection methods are deemed acceptable for all refrigerant
systems.
Electronic leak detectors may be used to detect refrigerant leaks but, in the
case of FLAMMABLE REFRIGERANTS, the sensitivity may not be adequate, or may
need re-calibration. (Detection equipment shall be calibrated in a
refrigerant-free area.) Ensure that the detector is not a potential source of
ignition and is suitable for the refrigerant used. Leak detection equipment
shall be set at a percentage of the LFL of the refrigerant and shall be
calibrated to the refrigerant employed, and the appropriate percentage of gas
(25 % maximum) is confirmed.
Leak detection fluids are also suitable for use with most refrigerants but the
use of detergents containing chlorine shall be avoided as the chlorine may
react with the refrigerant and corrode the copper pipe-work.
37
Troubleshooting and Resources
Notes: Examples of leak detection fluids are:
· bubble method,
· fluorescent method agents.
If a leak is suspected, all naked flames shall be removed/extinguished.
If a leakage of refrigerant is found which requires brazing, all of the
refrigerant shall be recovered from the system, or isolated (by means of shut
off valves) in a part of the system remote from the leak. Removal of
refrigerant shall be according to Clause Removal and evacuation.
Removal and evacuation
When breaking into the refrigerant circuit to make repairs or for any other
purpose conventional procedures shall be used. However, for flammable
refrigerants it is important that best practice be followed, since
flammability is a consideration. The following procedure shall be adhered to:
1. safely remove refrigerant following local and national regulations;
2. purge the circuit with inert gas;
3. evacuate (optional for A2L);
4. purge with inert gas (optional for A2L);
5. open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders
if venting is not allowed by local and national codes. For appliances
containing flammable refrigerants, the system shall be purged with oxygen-free
nitrogen to render the appliance safe for flammable refrigerants. This process
might need to be repeated several times. Compressed air or oxygen shall not be
used for purging refrigerant systems.
For appliances containing flammable refrigerants, refrigerants purging shall
be achieved by breaking the vacuum in the system with oxygen-free nitrogen and
continuing to fill until the working pressure is achieved, then venting to
atmosphere, and finally pulling down to a vacuum (optional for A2L). This
process shall be repeated until no refrigerant is within the system (optional
for A2L). When the final oxygen-free nitrogen charge is used, the system shall
be vented down to atmospheric pressure to enable work to take place.
Ensure that the outlet for the vacuum pump is not close to any potential
ignition sources and that ventilation is available.
Charging procedures
In addition to conventional charging procedures, the following requirements
shall be followed.
· Ensure that contamination of different refrigerants does not occur when
using charging equipment. Hoses or lines shall be as short as possible to
minimise the amount of refrigerant contained in them.
38
· Cylinders shall be kept in an appropriate position according to the
instructions.
· Ensure that the refrigeration system is earthed prior to charging the system
with refrigerant.
· Label the system when charging is complete (if not already).
· Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system, it shall be pressure tested with the
appropriate purging gas.
The system shall be leak-tested on completion of charging but prior to
commissioning. A follow up leak test shall be carried out prior to leaving the
site.
Decommissioning
Before carrying out this procedure, it is essential that the technician is
completely familiar with the equipment and all its detail. It is recommended
good practice that all refrigerants are recovered safely. Prior to the task
being carried out, an oil and refrigerant sample shall be taken in case
analysis is required prior to reuse of reclaimed refrigerant. It is essential
that electrical power is available before the task is commenced.
1. Become familiar with the equipment and its operation.
2. Isolate system electrically.
3. Before attempting the procedure, ensure that:
· mechanical handling equipment is available, if required, for handling
refrigerant cylinders;
· all personal protective equipment is available and being used correctly;
· the recovery process is supervised at all times by a competent person;
· recovery equipment and cylinders conform to the appropriate standards.
4. Pump down refrigerant system, if possible.
5. If a vacuum is not possible, make a manifold so that refrigerant can be
removed from various parts of the system.
6. Make sure that cylinder is situated on the scales before recovery takes
place.
7. Start the recovery machine and operate in accordance with manufacturer’s
instructions.
8. Do not overfill cylinders. (No more than 80 % volume liquid charge).
9. Do not exceed the maximum working pressure of the cylinder, even
temporarily.
10. When the cylinders have been filled correctly and the process completed,
make sure that the cylinders and the equipment are removed from site promptly
and all isolation valves on the equipment are closed off.
PTAC-SVX004A-EN
11. Recovered refrigerant shall not be charged into another refrigeration
system unless it has been cleaned and checked.
Labelling
Equipment shall be labelled stating that it has been decommissioned and
emptied of refrigerant. The label shall be dated and signed. For appliances
containing flammable refrigerants, ensure that there are labels on the
equipment stating the equipment contains flammable refrigerant.
Recovery
When removing refrigerant from a system, either for servicing or
decommissioning, it is recommended good practice that all refrigerants are
removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate
refrigerant recovery cylinders are employed. Ensure that the correct number of
cylinders for holding the total system charge are available. All cylinders to
be used are designated for the recovered refrigerant and labelled for that
refrigerant (i.e. special cylinders for the recovery of refrigerant).
Cylinders shall be complete with pressure-relief valve and associated shut-off
valves in good working order. Empty recovery cylinders are evacuated and, if
possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of
instructions concerning the equipment that is at hand and shall be suitable
for the recovery of all appropriate refrigerants including, when applicable,
flammable refrigerants. In addition, a set of calibrated weighing scales shall
be available and in good working order. Hoses shall be complete with leakfree
disconnect couplings and in good condition. Before using the recovery machine,
check that it is in satisfactory working order, has been properly maintained
and that any associated electrical components are sealed to prevent ignition
in the event of a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the
correct recovery cylinder, and the relevant waste transfer note arranged. Do
not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have
been evacuated to an acceptable level to make certain that flammable
refrigerant does
Troubleshooting and Resources
not remain within the lubricant. The evacuation process shall be carried out
prior to returning the compressor to the suppliers. Only electric heating to
the compressor body shall be employed to accelerate this process. When oil is
drained from a system, it shall be carried out safely.
Resources
Refer to the latest revision of literature numbers below:
· Packaged Terminal Air Conditioner Mechanical Specification (PTAC-PRD001)
· Packaged Terminal Air Conditioner Product Data Sheet (PTAC-PRD002)
· Control Block-off Plate Installation Instructions (PTAC-SVN024)
· Power Cord Assembly Installation Instructions (PTAC-SVN025)
· Drain Kit Installation Instructions (PTAC-SVN026) · Grille Installation
Instructions (PTAC-SVN027) · Wall Sleeve Installation Instructions (PTAC-
SVN028) · Knock-Down Wall Sleeve Installation Instructions
(PTAC-SVN029) · Wired Controller Installation Instructions (PTAC-
SVN030) · 265 Volt Hardwire Kit Installation Instructions
(PTAC-SVN031) · Subbase Installation Instructions (PTAC-SVN032) · Disconnect
Switch Installation Instructions (PTAC-
SVN033) · Leveling Legs Installation Instructions (PTAC-
SVN034)
· Wireless Remote Control with Receiver Installation and Operation (PTAC-
SVU003)
· Packaged Terminal Air Conditioner Warranty (PTAC-SVW003)
· Packaged Terminal Air Conditioner Installation, Operation, and Maintenance
(PTAC-SVX002)
· Wireless Thermostat Installation, Operation, and Maintenance (PTAC-SVX003)
PTAC-SVX004A-EN
39
Trane – by Trane Technologies (NYSE: TT), a global innovator – creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane. com or tranetechnologies.com.
Trane has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
PTAC-SVX004A-EN 14 Jul 2023 Supersedes (New)
©2023 Trane
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>