MITSUBISHI ELECTRIC TRANE HVAC US TPKA0A.1KA Series Split System Heat Pump Instruction Manual

May 15, 2024
MITSUBISHI ELECTRIC TRANE HVAC US

MITSUBISHI-ELECTRIC-logo

MITSUBISHI ELECTRIC TRANE HVAC US TPKA0A.1KA Series Split System Heat

Pump

MITSUBISHI-ELECTRIC-TRANE-Split-System-Heat-Pump-image

Product Information

Specifications

  • Brand: MITSUBISHI ELECTRIC TRANE HVAC US
  • Product Type: Split-System Heat Pump
  • Model: TPKA0A.1KA Series

Product Usage Instructions

1. Safety Precautions

Before installing the unit, ensure you read and understand all safety precautions outlined in the manual. Safety precautions are crucial for preventing injury or damage. Obtain consent from the supply authority before connecting the equipment to the power supply system.

2. Installation Location

Choose a suitable location for installation as per the guidelines provided in the manual. Ensure proper ventilation and clearance around the unit for efficient operation.

3. Installing the Indoor Unit

Follow the step-by-step instructions in the manual to correctly install the indoor unit. Proper installation is essential for optimal performance.

4. Installing the Refrigerant Piping

Refer to the manual for detailed instructions on installing the refrigerant piping system. Use only the specified refrigerant as mentioned in the outdoor unit installation manual.

5. Drainage Piping Work

Ensure proper drainage piping work to avoid any water leakage issues. Follow the instructions carefully to set up the drainage system correctly.

6. Electrical Work

For electrical connections, follow the provided guidelines to connect the unit safely to the power supply. If unsure, consult a qualified electrician.

7. Test Run

After installation, perform a test run to ensure the unit operates normally. Refer to the operation manual for detailed instructions on conducting a test run.

8. Easy Maintenance Function

Learn about the easy maintenance functions of the unit as described in the manual. Regular maintenance is key to prolonging the lifespan of the product.

FAQs

  • Q: What refrigerant should be used with this unit?
    • A: Use only the refrigerant specified in the outdoor unit installation manual to prevent any issues with the product.
  • Q: Can I mix different refrigerants?
    • A: Do not mix the specified refrigerant with any other type, as this can lead to malfunctions and may release poisonous gases.
  • Q: Why is it important to follow safety precautions?
    • A: Safety precautions are crucial to prevent injury, damage, and ensure proper functioning of the unit. Always adhere to the safety guidelines provided.

MITSUBISHI ELECTRIC TRANE HVAC US
SPLIT-SYSTEM HEAT PUMP
TPKA0A.1KA Series

INSTALLATION MANUAL

FOR INSTALLER

For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing

the air-conditioner unit.

MANUEL D’INSTALLATION

POUR L’INSTALLATEUR

Avant d’installer le climatiseur, lire attentivement ce manuel, ainsi que le manuel d’installation de l’appareil

extérieur pour une utilisation sûre et correct.

MANUAL DE INSTALACIÓN

PARA EL INSTALADOR

Para un uso correcto y seguro, lea detalladamente este manual y el manual de instalación de la unidad exterior

antes de instalar la unidad de aire acondicionado.

English Français Español

Note: In this installation manual, the term “Wired remote controller” refers only to the TAR-41MAA and the term “Wireless remote controller” refers only to the PAR-SL101A-E. If you need any information for other remote controllers, refer to the installation manual that is included with the grille, which includes a remote controller, or the initial setting manual that is included with the optional remote controller.

Safety precautions

Before installing the unit, make sure you read all the “Safety Precautions”. The “Safety Precautions” provide very important points regarding safety. Make sure you follow them. Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system.

Symbols used in the text Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the unit.

Symbols used in the illustrations
: Indicates a part which must be grounded. : Be sure not to do.
After installation work has been completed, explain the “Safety Precautions,” use, and maintenance of the unit to the customer according to the information in the Operation Manual and perform the test run to ensure normal operation. Both the Installation Manual and Operation Manual must be given to the user for keeping. These manuals must be passed on to subsequent users.

Warning:
· Carefully read the labels affixed to the main unit. · Ask a dealer or an authorized technician to install, relocate and repair the
unit.
· The user should never attempt to repair the unit or transfer it to another location.
· For installation and relocation work, follow the instructions in the Installation Manual and use tools and pipe components specifically made
for use with refrigerant specified in the outdoor unit installation manual.
· The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons, or strong winds. An incorrectly installed unit may fall down and cause damage or injuries.
· Do not alter the unit. It may cause fire, electric shock, injury or water leakage.
· The unit must be securely installed on a structure that can sustain its weight.
· The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
· If the air conditioner is installed in a small room or closed room, measures
must be taken to prevent the refrigerant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. Should the refrigerant leak and cause the concentration limit to be exceeded, hazards due to lack of oxygen in the room may result. · Keep gas-burning appliances, electric heaters, and other fire sources (ignition sources) away from the location where installation, repair, and
other air conditioner work will be performed. If refrigerant comes into contact with a flame, poisonous gases will be released.
· Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
· All electric work must be performed by a qualified technician according to local regulations and the instructions given in this manual.
· Do not use intermediate connection of the electric wires.
· Use only specified cables for wiring. The wiring connections must be made securely with no tension applied on the terminal connections. Also, never splice the cables for wiring (unless otherwise indicated in this document). Failure to observe these instructions may result in overheating or a fire.
· When installing or relocating, or servicing the air conditioner, use only the specified refrigerant written on outdoor unit to charge the refrigerant lines.
Do not mix it with any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high pressure in the refrigerant line, and may result in an explosion and other hazards. The use of any refrigerant other than that specified for the system will
cause mechanical failure or system malfunction or unit breakdown. In the worst case, this could lead to a serious impediment to securing product
safety.

· The appliance shall be installed in accordance with national wiring regulations.
· This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
· Children should be supervised to ensure that they do not play with the appliance.
· The terminal block cover panel of the unit must be firmly attached. · If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard. · Use only authorized accessories by Mitsubishi Electric and ask a dealer or
an authorized technician to install them. If accessories are incorrectly installed, water leakage, electric shock, or fire may result.
· After installation has been completed, check for refrigerant leaks. If refrigerant leaks into the room and comes into contact with the flame of a heater or portable cooking range, poisonous gases will be released.
· Do not use means to accelerate the defrosting process or to clean, other
than those recommended by the manufacturer. · The appliance shall be stored in a room without continuously operating
ignition sources (for example: open flames, an operating gas appliance or an operating electric heater).
· Do not pierce or burn. · Be aware that refrigerants may not contain an odour. · Pipe-work shall be protected from physical damage. · The installation of pipe-work shall be kept to a minimum. · Compliance with national gas regulations shall be observed. · Keep any required ventilation openings clear of obstruction. · Do not use low temperature solder alloy in case of brazing the refrigerant
pipes.
· When performing brazing work, be sure to ventilate the room sufficiently. Make sure that there are no hazardous or flammable materials nearby. When performing the work in a closed room, small room, or similar location, make sure that there are no refrigerant leaks before performing the work. If refrigerant leaks and accumulates, it may ignite or poisonous gases may be released.
· Exercise caution when using any auxiliary heat source and follow all third party manufacturer instructions and safety guidelines for installation and
usage.
Any auxiliary heat source connected to this unit via the CN24 connection must have an independent temperature control mechanism. Failure to install and maintain such temperature control mechanism may void the warranty for this unit.
Mitsubishi Electric shall not bear any warranty obligation or other liability any damage or loss in connection with such third party auxiliary heaters.

1

1. Safety precautions

1.1. Before installation (Environment) Caution:
· Do not use the unit in an unusual environment. If the air conditioner is installed in areas exposed to steam, volatile oil (including machine oil), or sulfuric gas, areas exposed to high salt content such as the seaside, the performance can be significantly reduced and the internal parts can be damaged.
· Do not install the unit where combustible gases may leak, be produced, flow, or accumulate. If combustible gas accumulates around the unit, fire or explosion may result.
· Do not keep food, plants, caged pets, artwork, or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items
can be damaged by temperature changes or dripping water.

· When the room humidity exceeds 80% or when the drainpipe is clogged, water may drip from the indoor unit. Do not install the indoor unit where
such dripping can cause damage.
· When installing the unit in a hospital or communications office, be prepared for noise and electronic interference. Inverters, home appliances, high- frequency medical equipment, and radio communications equipment can cause the air conditioner to malfunction or breakdown. The air conditioner may also affect medical equipment, disturbing medical care, and communications equipment, harming the screen display quality.

1.2. Before installation or relocation Caution:
· Be extremely careful when transporting the units. Two or more persons are needed to handle the unit as it weighs 20 kg, 44lbs or more. Do not grasp the packaging bands. Wear protective gloves as you can injure your hands on the fins or other parts.
· Be sure to safely dispose of the packaging materials. Packaging materials, such as nails and other metal or wooden parts may cause stabs or other injuries.
· Thermal insulation of the refrigerant pipe is necessary to prevent condensation. If the refrigerant pipe is not properly insulated, condensation
will be formed. · Place thermal insulation on the pipes to prevent condensation. If the drainpipe
is installed incorrectly, water leakage and damage to the ceiling, floor, furniture, or other possessions may result.

· Do not clean the air conditioner unit with water. Electric shock may result. · Tighten all flare nuts to specification using a torque wrench. If tightened too
much, the flare nut can break after an extended period. · If the unit is run for long hours when the air above the ceiling is at high
temperature/high humidity (dew point above 26 ºC, 79 ºF), dew condensation may be produced in the indoor unit or the ceiling materials. When operating the units in this condition, add insulation material (10-20 mm, 25/64-25/32 inch) to the entire surface of the unit and ceiling materials to avoid dew condensation.

1.3. Before electric work Caution:
· Be sure to install molded case circuit breakers. If not installed, electric shock may result.
· For the power lines, use standard cables of sufficient capacity. Otherwise, a short circuit, overheating, or fire may result.
· When installing the power lines, do not apply tension to the cables.

· Be sure to ground the unit. If the unit is not properly grounded, electric shock may result.
· Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and molded case circuit breaker) with the specified capacity. If the circuit breaker capacity is larger than the specified capacity, breakdown or fire may result.

1.4. Before starting the test run Caution:
· Turn on the main power switch more than 12 hours before starting operation. Starting operation just after turning on the power switch can severely damage the internal parts.
· Before starting operation, check that all panels, guards and other protective parts are correctly installed. Rotating, hot, or high voltage parts can cause injuries.

· Do not operate the air conditioner without the air filter set in place. If the air
filter is not installed, dust may accumulate and breakdown may result. · Do not touch any switch with wet hands. Electric shock may result. · Do not touch the refrigerant pipes with bare hands during operation. · After stopping operation, be sure to wait at least five minutes before turning off
the main power switch. Otherwise, water leakage or breakdown may result.

2

Installation location

1170

B

46-1/16

A
11-3299/654

CK

(mm) (inch)

365 14-3/8

L F
G

D E

  • H

J I

Fig. 2-1

2.1. Outline dimensions (Indoor unit) (Fig. 2-1)
Select a proper position allowing the following clearances for installation and
maintenance.
(mm, inch)

A

B

C

D

E

Min. 100.5 Min. 3-31/32

Min. 52.3 Min. 2-1/16

Min. 48 Min. 1-7/8

Min. 250

Min. 220

Min. 9-27/32 Min. 8-21/32

F Air outlet: Do not place an obstacle within 1500 mm, 59-1/16 inch of the air outlet. G Floor surface H Furnishing I When the projection dimension of a curtain rail or the like from the wall exceeds 60 mm,
2/23/64 inch extra distance should be taken because the fan air current may create a short cycle. J 1800 mm, 70-7/8 inch or greater from the floor surface (for high location mounting) K 108 mm, 4-1/4 inch or greater with left or rear left piping. L Minimum 7 mm, 9/32 inch.

Note: (For radio frequency interface) Connect a cord of the radio frequency interface to indoor controller
board before mounting the indoor unit on the wall. Refer to P.10 for details on how to installation the radio frequency
interface.

20-7/8 17-9/32 16-15/16
15-1/8 13-11/32
7-7/16 0
8-17/32 13-11/32
13-3/4 15-1/8 17-9/32 17-11/16

Installing the indoor unit

1

2

3

4

5

6

23-1/32 20-3/8 17-7/8 17-9/32 16-3/32 15-1/8 14-11/32 12-3/8

F
D
5/8 0
31/32 1-31/32 2-15/16 3-15/16 4-19/32 4-29/32 5-19/32
7-9/16 9-17/32
11 11-1/2
C

Fig. 3-1
G A

0 2-1/8

4-11/32 2-3/8 13/32 13/32 2-3/8 4-11/32
1/8

E

A

3-15/16

K

I J
Fig. 3-2

R1-15/32

A C
3

B E D

A Sleeve B Hole C (Indoors) D Wall E (Outdoors)

Fig. 3-3

12-3/8 14-11/32 15-1/8 16-3/32 17-9/32 17-7/8 18-5/16 23-1/32

3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories.

PART NUMBER

ACCESSORY

QUANTITY

LOCATION OF SETTING

1

Mount board

1

2

Tapping screw 4 × 25

7

3

Felt tape

2

Fix at the back of the unit

4

L-shaped connection pipe

1

5

Charge nut

1

6

Spacer

1

Make use of packaging material

(inch)

B

2-1/8

31/32 0

1-1/4 1/2

1/2

1-15/32

2-15/32

3-7/16

4-1/8

5-3/32

6-9/16

8-17/32 9-1/32 10-13/32 11-1/2 12-5/32 12-1/4
D

3.2. Installing the wall mounting fixture
3.2.1. Setting the wall mounting fixture and piping positions (Fig. 3-2)
Using the wall mounting fixture, determine the unit’s installation position and the locations of the piping holes to be drilled.
Warning:
Before drilling a hole in the wall, you must consult the building contractor.
A Mount board 1 B Indoor unit C Bottom left rear pipe hole (ø75-ø80 mm, 2-61/64~3-35/64 inch) D Bottom right rear pipe hole (ø75-ø80 mm, 2-61/64~3-35/64 inch) E Knockout hole for left rear hole (75 × 480) F Bolt hole (4-ø9 mm, 23/64 inch hole) G Center measurement hole (ø2.5 mm, 3/32 inch hole) H Tapping hole (75-ø5.1 mm, 13/64 inch hole) I Hole centre J Align the scale with the line. K Insert scale.

3.2.2. Drilling the piping hole (Fig. 3-3) Use a core drill to make a hole of 75-80 mm, 2-61/64~3-5/32 inch diameter
in the wall in the piping direction, at the position shown in the diagram to
the left.
The hole should incline so that the outside opening is lower than the inside opening.
Insert a sleeve (with a 75 mm, 2-61/64 inch diameter and purchased locally) through the hole.

Note: The purpose of the hole’s inclination is to promote drain flow.

3. Installing the indoor unit

F C

A D

E
G I
H Fig. 3-4
B

B A

C

D
Fig. 3-5

A
Fig. 3-6
B

A
Fig. 3-7
A

Fig. 3-8
E

C
Fig. 3-9

D
Fig. 3-10

3.2.3. Installing the wall mounting fixture (Fig. 3-4) Since the indoor unit weighs near 21 kg, 46.3lbs, selection of the mounting
location requires thorough consideration. If the wall does not seem to be strong enough, reinforce it with boards or beams before installation. The mounting fixture must be secured at both ends and at the centre, if possible. Never fix it at a single spot or in any nonsymetrical way. (If possible, secure the fixture at all the positions marked with a bold arrow.)
Warning:
If possible, secure the fixture at all positions indicated with a bold arrow.
Caution:
· The unit body must be mounted horizontally. · Fasten at the holes marked with as shown by the arrows.
A Min. 120 mm, 4-11/16 inch B Min. 220 mm, 8-11/16 inch C Min. 70 mm, 2-3/4 inch D Fixing screws (4 × 25) 2 E Level F Fasten a thread to the hole. G Place the level against the horizontal reference line of the mount board and mount so that it is
level. Hang a weight from the thread and align with EPK of the mount board to permit leveling. H Weight I Mount board 1
3.3. When embedding pipes into the wall (Fig. 3-5)
· The pipes are on the bottom left. · When the cooling pipe, drain pipes internal/external connection lines etc are to
be embedded into the wall in advance, the extruding pipes etc, may have to be bent and have their length modified to suit the unit. · Use marking on the mount board as a reference when adjusting the length of the embedded cooling pipe. · During construction, give the length of the extruding pipes etc some leeway. A Mount board 1 B Reference marking for flare connection C Through hole D On-site piping
3.4. Preparing the indoor unit

  • Check beforehand because the preparatory work will differ depending on the exiting direction of the piping.
  • When bending the piping, bend gradually while maintaining the base of the piping exiting portion. (Abrupt bending will cause misshaping of the piping.)
  • Do not perform piping on the right side.
    Attachment of L-shaped connection pipe 4 Right, left and rear piping (Fig. 3-6) 1. Remove the flare nut and cap of the indoor unit. (Gas pipe only) 2. Apply refrigerating machine oil to the flare sheet surface. (Preparation on
    location) 3. Facing the direction in which the L-shaped connection pipe 4 will be removed,
    make a quick connection to the indoor unit flare connection opening. 4. Tighten the flare nut using a double open-end wrench. (Fig. 3-9)
    Tightening force: 68~82 N·m, 49~59ft lbs 5. Attach the charge nut 5 to the liquid pipe side joint portion, and check for
    leakage of the L-shaped connection pipe 4 connection portion. Remove the charge nut 5 after completion of the work. Tightening force: 34~42 N·m, 25~30ft lbs 6. Cover the flare connection portion with the pipe cover of the L-shaped connection pipe 4 so that it is not exposed. (Fig. 3-10) A L-shaped connection pipe 4 B Cut-off position (Straight pipe portion) C Tightening direction D Cover with pipe cover E Cover the flare nut connection portion with the pipe cover.
    Lower piping (Fig. 3-7) 1. Cut L-shaped connection pipe 4 at the position indicated in (Fig. 3-8). 2. Insert the flare nut that was removed earlier onto the straight pipe side of the cut
    L-shaped connection pipe 4 and then flare the end of the pipe. 3. Remove the flare nut and cap of the indoor unit. (Gas pipe only) 4. Apply refrigerating machine oil to the flare sheet surface. (Preparation on
    location) 5. Quickly connect the L-shaped connection pipe 4 that has been processed as
    described in part 2) to the indoor unit flare connection opening. 6. Tighten the flare nut using a double open-end wrench. (Fig. 3-9)
    Tightening force: 68~82 N·m, 49~59ft lbs 7. Attach the charge nut 5 to the liquid pipe side joint portion, and check for
    leakage of the L-shaped connection pipe 4 connection portion. Remove the charge nut 5 after completion of the work. Tightening force: 34~42 N·m, 25~30ft lbs 8. Cover the flare connection portion with the pipe cover of the L-shaped connection pipe 4 so that it is not exposed. (Fig. 3-10)
    4

3. Installing the indoor unit

C

D

A

B

E
Fig. 3-11

A Fig. 3-12

B

C

    1. Fig. 3-13

Leakage check of the L-shaped connection pipe connection portion 1. Attach the charge nut 5 to the liquid pipe side joint portion.
Tightening force: 34~42 N·m, 25~30ft lbs 2. Pressurize by filling with nitrogen gas from the charge nut.
Do not pressurize to the current constant pressure all at once. Pressurize gradually. 1) Pressurize to 0.5 MPa, 73PSIG wait five minutes, and make sure the
pressure does not decrease. 2) Pressurize to 1.5 MPa, 218PSIG wait five minutes, and make sure the
pressure does not decrease. 3) Pressurize to 4.15 MPa, 601PSIG and measure the surrounding temperature
and refrigerant pressure. 3. If the specified pressure holds for about one day and does not decrease, the
pipes have passed the test and there are no leaks. · If the surrounding temperature changes by 33.8°F, the pressure will change by
about 0.01 MPa, 1.5PSIG. Make the necessary corrections. 4. If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the
source of the gas leak.
Extraction and processing of the piping and wiring (Fig. 3-11) 1. Connection of indoor/outdoor wiring See page 10. 2. Wrap the felt tape 3 in the range of the refrigerant piping and drain hose which
will be housed within the piping space of the indoor unit. · Wrap the felt tape 3 securely from the base for each of the refrigerant piping
and the drain hose. · Overlap the felt tape 3 at one-half of the tape width. · Fasten the end portion of the wrapping with vinyl tape. A Liquid pipe B Gas pipe C Indoor/outdoor connection cable D Drain hose E Felt tape 3 3. Be careful that the drain hose is not raised, and that contact is not made with the indoor unit box body. Do not pull the drain hose forcefully because it might come out.
Rear and lower piping (Fig. 3-12) 1) Be careful that the drain hose is not raised, and that contact is not made with the indoor unit box body. Arrange the drain hose at the underside of the piping and wrap it with felt tape 3. 2) Securely wrap the felt tape 3 starting from the base. (Overlap the felt tape at one-half of the tape width.) A Cut off for right piping.
Left and left rear piping (Fig. 3-13) 4. Drain hose replacement See 5. Drainage piping work
Be sure to replace the drain hose and the drain cap for the left and rear left piping. Dripping may occur if you forget to install or fail to replace these parts. B Drain cap 1) Be careful that the drain hose is not raised, and that contact is not made with
the indoor unit box body. 2) Securely wrap the felt tape 3 starting from the base. (Overlap the felt tape at
one-half of the tape width.) 3) Fasten the end portion of the felt tape 3 with vinyl tape.
C Cut off for left piping.

5

3. Installing the indoor unit
C

B

A

Fig. 3-14

C D

B

A

Fig. 3-15

B A
C

E D
Fig. 3-16

3.5. Mounting the indoor unit
1. Affix the mount board 1 to the wall. 2. Hang the indoor unit on the hook positioned on the upper part of the mount
board.
Rear and lower piping (Fig. 3-14) 3. While inserting the refrigerant piping and drain hose into the wall penetration
hole (penetration sleeve), hang the top of the indoor unit to the mount board

    1. Move the indoor unit to the left and right, and verify that the indoor unit is hung
      securely. 5. Fasten by pushing the bottom part of the indoor unit onto the mount board 1.
      (Fig. 3-15) Check that the knobs on the bottom of the indoor unit are securely hooked into
      the mount board 1. 6. After installation, be sure to check that the indoor unit is installed level.
      A Mount board 1 B Indoor unit C Hook D Square hole
      Left and left rear piping (Fig. 3-16) 3. While inserting the drain hose into the wall penetration hole (penetration
      sleeve), hang the top of the indoor unit to the mount board 1. Giving consideration to the piping storage, move the unit all the way to the left side, then cut part of the packaging carton and wrap into a cylindrical form as illustrated in the diagram. Hook this to the rear surface rib as a spacer, and raise the indoor unit. 4. Connect the refrigerant piping with the site- side refrigerant piping. 5. Fasten by pushing the bottom part of the indoor unit onto the mount board 1.
      Check that the knobs on the bottom of the indoor unit are securely hooked into the mount board 1. 6. After installation, be sure to check that the indoor unit is installed level. A Indoor unit B Packaging carton C Cut off D Wrap into a cylindrical form E Fasten with tape

6

Installing the refrigerant piping

45°± 2°

90°± 0.5°
øA

R(R01.4/6t4o tRo0R.81/32)

Union joint

Flare nut

Male side
Lock the union joint with a wrench.

Female side
Tighten the flare nut with a torque wrench.
Fig. 4-1

4.1. Precautions
4.1.1. For devices that use R410A refrigerant · Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration
oil applied to the flared sections.
· Use C1220 copper phosphorus for copper and copper alloy seamless pipes, to connect the refrigerant pipes. Use refrigerant pipes with the
thicknesses specified in the table below. Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric
compounds, oxidants, debris, or dust.

Warning:
When installing or relocating, or servicing the air conditioner, use only the specified refrigerant written on outdoor unit to charge the refrigerant lines.
Do not mix it with any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high pressure in the refrigerant line, and may result in an explosion and other hazards. The use of any refrigerant other than that specified for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst case, this could lead to a serious impediment to securing product safety.

Liquid pipe Gas pipe

A024, 030, 036 ø9.52 mm, 3/8 inch thickness 0.8 mm, 1/32 inch ø15.88 mm, 5/8 inch thickness 1.0 mm, 3/64 inch

· Do not use pipes thinner than those specified above.

4.2. Connecting pipes (Fig. 4-1)
· When commercially available copper pipes are used, wrap liquid and gas pipes

with commercially available insulation materials (heat-resistant to 100 °C, 212°F

or more, thickness of 12 mm, 1/2 inch or more).

· The indoor parts of the drain pipe should be wrapped with polyethylene foam

insulation materials (specific gravity of 0.03, thickness of 9 mm, 23/64 inch or

more).

· Flare the ends of the refrigerant pipes. A · Apply refrigerating machine oil over the entire flare sea surface. B · Use the flare nuts as follows. C

· For connection, first align the center, then tighten the first 3 to 4 turns of flare nut

by hand. · Use 2 wrenches to tighten piping connections. D

· Use refrigerant piping insulation provided to insulate indoor unit connections.

Insulate carefully. A Flare cutting dimensions

Copper pipe O.D.

Flare dimensions

(mm, inch)

øA dimensions (mm, inch)

ø9.52, 3/8″

12.8 – 13.2, 1/2-33/64

ø15.88, 5/8″

19.3 – 19.7, 49/64-25/32

D Flare nut tightening torque Copper pipe O.D. (mm, inch) ø9.52, 3/8″ ø15.88, 5/8″

Flare nut O.D. (mm, inch) 22, 7/8 29, 1-9/64

Tightening torque (N·m, ft·lbs)
34 – 42, 25-30 68 – 82, 49-59

Warning:
· Be careful of flying flare nut! (Internally pressurized) Remove the flare nut as follows: 1. Loosen the nut until you hear a hissing noise. 2. Do not remove the nut until the gas has been completely released (i.e., hissing noise stops). 3. Check that the gas has been completely released, and then remove the nut.
· When installing the unit, securely connect the refrigerant pipes before starting the compressor.

7

4. Installing the refrigerant piping

4.3. Positioning refrigerant and drain piping (Fig. 4-2)

A Gas pipe

  • Indicates the condition with accessories mounted.

B Liquid pipe

C Drain hose

D Left-side piping knockout hole

E Right-side piping knockout hole

F Lower piping knockout hole

G Mount board 1

(inch)

46-1/16

11-5/8

3/16 G

2-9/16 2-5/8
5/16 3-1/32

14-3/8

5/16 3-1/32 2-5/8

2-9/16

D

17-15/32 (A)* 18-31/32 (B) 23-1/32 (C)

4-27/32 6-1/16 5-9/32

2-9/16 E

2-9/16

3-1/32 13/32 3-7/16

45-15/32

F

F

Fig. 4-2

3-1/32 3-7/16

2-51/64

A
B
Fig. 4-3
B C
A D
Fig. 4-4

4.4. Refrigerant piping (Fig. 4-3)
Indoor unit 1. Remove the flare nut and cap of the indoor unit. 2. Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil
(available from your local supplier) to the flare sheet surface. 3. Quickly connect the on site cooling pipes to the unit. 4. Wrap the pipe cover that is attached to the gas pipe and make sure that the
connection join is not visible. 5. Wrap the pipe cover of the unit’s liquid pipe and make sure that it covers the
insulation material of the on site liquid pipe. 6. The portion where the insulation material is joined is sealed by taping.
A Site-side refrigerant piping B Unit side refrigerant piping
4.4.1. Storing in the piping space of the unit (Fig. 4-4) 1. Wrap the supplied felt tape in the range of the refrigerant piping which will be
housed within the piping space of the unit to prevent dripping. 2. Overlap the felt tape at one-half of the tape width. 3. Fasten the end portion of the wrapping with vinyl tape, etc.
A Gas pipe B Liquid pipe C Indoor/outdoor connection cable D Felt tape 3

8

Drainage piping work

A

D

B

E

C

C

F

J

G

I

K

C

H

Fig. 5-1

1

A

2

a

b

3

4B

A

A
Fig. 5-2

D

C

B

A

E
Fig. 5-3

5.1. Drainage piping work (Fig. 5-1)
· Drain pipes should have an inclination of 1/100 or more. · For extension of the drain pipe, use a soft hose (inner dia. 15 mm, 19/32 inch)
available on the market or hard vinyl chloride pipe (VP-16 mm, 5/8 inch/O.D. ø22 mm, ø55/64 inch PVC TUBE). Make sure that there is no water leakage from the connections. · Do not put the drain piping directly in a drainage ditch where sulphuric gas may be generated. · When piping has been completed, check that water flows from the end of the drain pipe.
Caution:
The drain pipe should be installed according to this Installation Manual to ensure correct drainage. Thermal insulation of the drain pipes is necessary to prevent condensation. If the drain pipes are not properly installed and insulated, condensation may drip on the ceiling, floor or other possessions.
A Inclined downwards B Must be lower than outlet point C Water leakage D Trapped drainage E Air F Wavy G The end of drain pipe is under water. H Drainage ditch I 5 cm or less between the end of drain pipe and the ground. J Drain hose K Soft PVC hose (Inside diameter 15 mm, 19/32 inch)
or Hard PVC pipe (VP-16 mm, 5/8 inch) Bond with PVC type adhesive
Preparing left and left rear piping (Fig. 5-2) 1 Remove the drain cap. · Remove the drain cap by holding the bit that sticks out at the end of the pipe and
pulling. A Drain cap 2 Remove the drain hose. · Remove the drain hose by holding on to the base of the hose a (shown by arrow) and pulling towards yourself b. 3 Insert the drain cap. · Insert a screwdriver etc into the hole at the end of the pipe and be sure to push to the base of the drain cap. 4 Insert the drain hose. · Push the drain hose until it is at the base of the drain box connection outlet. · Please make sure the drain hose hook is fastened properly over the extruding drain box connection outlet. B Hooks
Storing in the piping space of the indoor unit (Fig. 5-3)
When the drain hose will be routed indoors, be sure to wrap it with commercially
available insulation. Gather the drain hose and the refrigerant piping together and wrap them with the
supplied felt tape 3.
Overlap the felt tape 3 at one-half of the tape width.

  • Fasten the end portion of the wrapping with vinyl tape, etc.
    A Gas pipe B Liquid pipe C Drain hose D Indoor/outdoor connection wiring E Felt tape 3
    Check of drainage (Fig. 5-4) 1. Open the front grille and remove the filter.
  1. Facing the fins of the heat exchanger, slowly fill with water. 3. After the drainage check, attach the filter and close the grille.

Fig. 5-4

9

Electrical work

F E

D A
B

J
2-11/64 inch 15/32 inch

J

K G H

H

F

E D

15/32 inch 2-11/64 inch
K

I MN L OP

R

S

Fig. 6-1
V

T
Fig. 6-2
Y

U W

Fig. 6-3
Z f

X
Fig. 6-4
Z

CN105 (RED)

a d

b
Fig. 6-5

c
Fig. 6-6

6.1. Indoor unit (Fig. 6-1)
Connection can be made without removing the front panel. 1. Open the front grille, remove the screw (1 piece), and remove the electrical
parts cover. 2. Securely connect each wire to the terminal board. In consideration of servicing, provide extra length for each of the wires. Take care when using strand wires, because beards may cause the wiring to
short out. 3. Install the parts that were removed back to their original condition.
A Electrical box cover B Fixing screw D Ground wire connection portion F Indoor/outdoor connection terminal board: S1, S2, and S3, have polarity G Lead H Terminal screw I Ground wire: Connect the ground wire in the direction illustrated in the diagram. K Indoor/outdoor connection cord L Conduit plate M Bush (purchased locally) N Lock nut (purchased locally) O Connector (purchased locally) P Conduit (purchased locally)
Only for wired remote controller E Wired remote control terminal board: 1 and 2, do not have polarity. H Terminal screw J Wired remote control cord
For CN105 connecting procedures 1 Press and unlock the knobs on both sides of the front grille and lift the front grille until it is
level. Pull the hinges forward to remove the front grille. (Fig. 6-2) 2 Remove 3 screw caps of the panel. Remove 5 screws. (Fig. 6-2) 3 Unfix 3 hooks. (Fig. 6-3) 4 Hold the lower part of both ends of the panel and pull it slightly toward you, and then
remove the panel by pushing it upward. 5 Remove the front and side electrical box covers (each 1 screws). (Fig. 6-4) 6 Remove the water cut. (Fig. 6-4) 7 Remove the screw of the corner box. (Fig. 6-2)
Remove the corner box. 8 Remove the cable guide. (Fig. 6-5) 9 Remove the screw of the electrical box. (Fig. 6-7) 0 Remove the liquid pipe thermistor (TH2). (Fig. 6-5) 1 Tear off the tape partly of vane motor and loosen the cord. (Fig. 6-5) 2 Loosen the cord of the fan motor. (Fig. 6-5) 3 Pull out the electrical box toward you. 4 CN105 (RED) on indoor controller board. (Fig. 6-6) 5 Replace the removed parts.
R Front grille S Screws T Screws and screw caps U Screw of the corner box V Hooks W Screw of electrical box cover (side) X Screw of electrical box cover (Front) Y Water cut Z Indoor controller board (I.B) a Electrical box b Lead wire of vane motor c Cable guide d Lead wire of fan motor e Screw of the electrical box f Liquid pipe thermistor (TH2)
Warning: Be extremely careful not to cut your hands by Sharp-edged parts or end faces of the box. There are some Sharp-edged parts on the indoor controller board.

e
Fig. 6-7
(see the bottom)
10

6. Electrical work
6.1.1. Indoor unit power supplied from outdoor unit The following connection patterns are available. The outdoor unit power supply patterns vary on models.

1:1 System

C

A

B

L1

L2

GR

S1 S2 S3

F

CN105

D

(RED)

S1

S2
S3 H

GE

1 2

  • Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.

D

G

A

BC

L1

L2

GR

S1

S1

S2

S2

S3

S3

E

F

1

2

A Outdoor unit power supply B Wiring circuit breaker or isolating switch C Outdoor unit D Indoor unit/outdoor unit connecting cords E Wired remote controller F Indoor unit G Indoor unit earth H Indoor controller board
A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor/outdoor unit connecting cords F Remote controller G Indoor unit

  • Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units. Applied earth type depends on outdoor unit. Please refer to connected outdoor unit Installation Manual.
    Simultaneous twin/triple/four system

C

FF

A

B

L1

L2

GR

D

S1

S1

S1

S2

S2

S2

S3

S3

S3

GE

1 2

1
2G

  • Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.

A Outdoor unit power supply B Wiring circuit breaker or isolating switch C Outdoor unit D Indoor unit/outdoor unit connecting cords E Wired remote controller F Indoor unit G Indoor unit earth
Only for wired remote controller.

Circuit rating

Wiring Wire No.
× size

Indoor unit model Minimum circuit ampacity Maximum rating of overcurrent protective device
Indoor unit-Outdoor unit Indoor unit earth Wired remote controller-Indoor unit Indoor unit-Outdoor unit S1-S2 Indoor unit-Outdoor unit S2-S3 Wired remote controller-Indoor unit

TPKA0A.1KA80A Series

1 A

15 A

*1

3 × AWG14 (Polar)

1 × Min. AWG14

*2

2 × Min. AWG22 (unshielded)

*3

208/230 V AC

*3

24 V DC / 28 V DC

*3

12 V DC

1. Max. 50 m, 165 ft 2. Max. 500 m, 1640 ft (For two wired remote controllers: Max. 200 m, 656 ft) *3. The figures are NOT always against the ground.
S3 terminal has 24 V DC / 28 V DC against S2 terminal. However, between S3 and S1, these terminals are not electrically insulated by the transformer or other device.

Notes: 1. Wiring size must comply with the applicable local and national code. 2. Power supply cords and indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57) 3. Use copper supply wires.
4. Use UL wires rated 300V or more for the power supply cords and the indoor unit/outdoor unit connecting cords.
5. Install an earth longer than other cords. 6. Indoor and outdoor connecting wires have polarities. Make sure to match the terminal number (S1, S2, S3) for correct wirings. 7. Wiring for remote controller cable shall be apart (5 cm, 2 inch or more) from power source wiring so that it is not influenced by electric noise from
power source wiring.
8. This appliance incorporates an earth connection for functional purpose only.

Warning: Never splice the power cable or the indoor-outdoor connection cable, otherwise it may result in a smoke, a fire or communication failure.

11

6. Electrical work

1

B

C

A 2
D

A
Fig. 6-8

7 A

Fig. 6-9
1 4 2 3 6 5 8

6.2. Remote controller
6.2.1. For wired remote controller 1) Two remote controllers setting
If two remote controllers are connected, set one to “Main” and the other to
“Sub”.
For setting procedures, refer to “Function selection of remote controller” in the
operation manual for the indoor unit.

6.2.2. For wireless remote controller 1) Installation area
· Area in which the remote controller is not exposed to direct sunshine.

· Area in which there is no nearby heating source.

· Area in which the remote controller is not exposed to cold (or hot) winds.

B

· Area in which the remote controller can be operated easily.

· Area in which the remote controller is beyond the reach of children.

  1. Installation method (Fig. 6-8)

1 Attach the remote controller holder to the desired location using 2 tapping

screws.

2 Place the lower end of the controller into the holder.

A Remote controller B Wall C Display panel D Receiver

· The signal can travel up to approximately 7 meters (in a straight line) within

45 degrees to both right and left of the center line of the receiver.

  1. Setting (Clock setting) (Fig. 6-9)

1 Insert batteries or press the

button with something sharp.

[CLOCK] A and [:] B blinks.

2 Press the

button with something sharp.

3 Press the button to set the time.

Press the 4 Press the

button to set the Day. button with something sharp at the end.

[CLOCK] and [:] lighted.

  1. Mode display setting (to cooling only setting)

(The factory setting is “COOL/DRYING/AUTO/FAN/HEAT”)

1. Press the

button 1 to stop the air conditioner.

2. Press the

button 3 in 5 seconds. Model setting screen will be

displayed.

3. Press the

button 7. Operation mode A blinks. (Fig. 6-10)

4. Press the button 4 to change setting No.

5. Check that setting No. “6” is displayed and only

blink at operation

mode A, then press the

button 3 in 5 seconds.

  1. Initial setting

The following settings can be made in the initial setting mode.

Item

Setting

Fig. 6-12

Temperature unit

ºC/ºF

A

Time display

12-hour format/24-hour format

B

Pair No.

0­3

C

Backlight

On/Off

D

5-1. Switching to the initial setting mode

1. Press the

button 1 to stop the air conditioner.

2. Press the

button 2.

The Function setting screen will be displayed and the function No. A will

blink. (Fig. 6-11)

Press the button 4 to change the function No.

3. Check that function No. “1” is displayed, and the

press the button

The display setting screen will be displayed. (Fig. 6-12)

Fig. 6-10

A

A

C

B

D

Fig. 6-11

Fig. 6-12

12

6. Electrical work

Service menu
Test run Input maintenance info. Settings Check Others
Main menu: RETURN Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-13

Function setting

Ref. address

Unit No.

Grp./1/2/3/4/All

Monitor: SELECT

Cursor

Address

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-15

Function setting

Ref. address Grp.

Mode 1

Mode 2

Mode 3

Mode 4

Request: SELECT

Cursor

Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-17

5-2. Changing the temperature unit A

Press the

button 5.

Each time the

button 5 is pressed, the setting switches between

and .

: The temperature is displayed in degrees Celsius.

: The temperature is displayed in degrees Fahrenheit.

5-3. Changing the time display B

Press the

button 6.

Each time the

button 6 is pressed, the setting switches between

and

: The time is displayed in the 12-hour format.

: The time is displayed in the 24-hour format. 5-4. Changing the pair No. C

Press the button 4.

Each time the button 4 is pressed, the pair No. 0­3 changes.

Pair No. of wireless remote controller 0 1 2 3

Indoor PC board Initial setting Cut J41 Cut J42 Cut J41, J42

5-5. Changing the backlight setting D

Press the

button 8.

Each time the

button 8 is pressed, the setting switches between

and .

: The backlight comes on when a button is pressed.

: The backlight does not come on when a button is pressed.

Settings menu Function setting

Service menu: MENU

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-14

Function setting
Ref. address Grp. Mode 1 Mode 2 Mode 3 Mode 4

Cursor

Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-16

Function setting Ref. address Grp.

Sending data

6.3. Function settings
6.3.1. By wired remote controller 1 (Fig.6-13)
· Select “Service” from the Main menu, and press the [SELECT/HOLD] button. · Select “Settings” from the Service menu, and press the [SELECT/HOLD] button.
2 (Fig.6-14) · Select “Function settings” with the [SELECT/HOLD] button.
3 (Fig. 6-15) · Set the indoor unit refrigerant addresses and unit numbers with the [F1] through [F4] buttons, and then press the [SELECT/HOLD] button to confirm the current setting.

When the [SELECT/HOLD] button is pressed, the target indoor unit will start fan operation. If the unit is common or when running all units, all indoor units for the selected refrigerant address will start fan operation. 4 (Fig. 6-16) · When data collection from the indoor units is completed, the current settings appears highlighted. Non-highlighted items indicate that no function settings are made. Screen appearance varies depending on the “Unit No.” setting. 5 (Fig. 6-17) · Use the [F1] or [F2] button to move the cursor to select the mode number, and change the setting number with the [F3] or [F4] button. 6 (Fig. 6-18) · When the settings are completed, press the [SELECT/HOLD] button to send the setting data from the remote controller to the indoor units. · When the transmission is successfully completed, the screen will return to the Function setting screen.

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-18

13

6. Electrical work

Fig. 6-19 Fig. 6-21

6.3.2. By wireless remote controller

1 Going to the function select mode

Press the

button between of 5 seconds.

(Start this operation from the status of remote controller display turned off.)

[CHECK] is lighted and “00” blinks. (Fig. 6-19)

Press the button to set the “50”.

Direct the wireless remote controller toward the receiver of the indoor unit and

A

press the

button.

2 Setting the unit number

Press the button to set unit number A. (Fig. 6-20)

Direct the wireless remote controller toward the receiver of the indoor unit and

Fig. 6-20

press the

button.

3 Select a mode

Press the button to set Mode number B. (Fig. 6-21)

Direct the wireless remote controller toward the receiver of the indoor unit and

press the

button.

Current setting number:

1=1 beep (1 second)

2=2 beep (1 second each)

3=3 beep (1 second each)

4 Selecting the setting number

Use the button to change the Setting number C. (Fig. 6-22)

Direct the wireless remote controller toward the receiver of the indoor unit and

B

press the

button.

5 To select multiple functions continuously

C

Repeat select 3 and 4 to change multiple function settings continuously.

6 Complete function selection

Fig. 6-22

Direct the wireless remote controller toward the sensor of the indoor unit and

press the

button.

Note:
Make the above settings on units as necessary. · Table 1 summarizes the setting options for each mode number. · Be sure to write down the settings for all functions if any of the initial set-
tings has been changed after the completion of installation work.

Function table (Table 1) Select unit number “Grp.”
Mode Power failure automatic recovery Indoor temperature detecting
LOSSNAY connectivity
Power voltage

Settings

Not available

Available

*1

Indoor unit operating average

Set by indoor unit’s remote controller

Remote controller’s internal sensor

Not Supported

Supported (indoor unit is not equipped with outdoor-air intake)

Supported (indoor unit is equipped with outdoor-air intake)

230 V

208 V

Select unit numbers 1 to 4 or “All” Mode Filter sign
Fan speed
Fan speed during the cooling thermostat is OFF

Settings 100 Hr 2500 Hr No filter sign indicator Silent (low ceiling) Standard High ceiling Setting fan speed Stop Extra low

1 When the power supply returns, the air conditioner will start 3 minutes later. 2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.

Mode no. 01 02
03 04

Setting no. Initial setting

1

2

*2

1

2

3

1

2

3

1

2

setting

Mode no. 07 08 27

Setting no. Initial setting

1

2

3

1

2

3

1

2

3

setting

14

6. Electrical work

Service menu
Test run Input maintenance info. Settings Check Others
Service menu: RETURN Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-23

CN24 settings Address

Mointor: SELECT Address

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-25

CN24 settings

CN24 enabled condition

T

5 ºF

Setting display: SELECT Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-27

CN24 enabled condition

T

5 ºF

Select: SELECT

Temp.

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-29

CN24 enabled condition

T

4 ºF

Changes saved Service menu: MENU

Settings Function setting Rotation settings CN24 settings
Service menu: MENU Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-24

CN24 settings

Limit settings CN24 disabled (UB) CN24 enabled (UA) H/P enabled (LB) H/P disabled (LA)

50 ºF 47 ºF 15 ºF
5 ºF

Setting display: SELECT

Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-26

Limit settings
CN24 disabled (UB) CN24 enabled (UA) H/P enabled (LB) H/P disabled (LA)

50 ºF 47 ºF
15 ºF
5 ºF

Select: SELECT Cursor

Temp.

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-28

Limit settings
CN24 disabled (UB) CN24 enabled (UA) H/P enabled (LB) H/P disabled (LA)
Changes saved
Service menu: MENU

50 ºF 48 ºF
15 ºF
5 ºF

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-30

6.4 CN24 settings (Mass save settings)
· Heat Pump auto ON/OFF setting depend on Outdoor temperature · Heater via CN24 auto ON/OFF setting depend on Outdoor temperature or
difference between setting temp. and indoor ambient temperature.
1 (Fig.6-23) · Select “Service” from the Main menu, and press the [SELECT/HOLD] button. · Select “Settings” with the [F1] or [F2] button, and press the [SELECT/HOLD] button.
2 (Fig.6-24) · Select “CN24 settings” with the [F1] or [F2] button, and press the [SELECT/ HOLD] button.
3 (Fig.6-25) · Set the indoor unit refrigerant address with the [F1] or [F2] button, then press the [SELECT/HOLD] button.
4 (Fig.6-26, 6-27) · Select “Limit settings” or “CN24 ON condition” with the [F1] or [F2] button and press the [SELECT/HOLD] button.
5 (Fig.6-29, 6-31) · Set T(difference between ambient temp. and setting temp.) with [F3] or [F4] button and press the [SELECT/HOLD] button.
6 (Fig.6-28, 6-30) · Set UB, UA, LB, LA with [F3] or [F4] button and press the [SELECT/HOLD] button.

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 6-31

Connected outdoor unit
TRUZA TRUZH NTXSKS09/12/15/18/24/30/36A112BA NTXSKH09/12/15/18/24/30/36A112AA NTXMMX/NTXMPH

UB Setting range Default 32°F ~ 70°F 47°F 32°F ~ 70°F 47°F 32°F ~ 70°F 47°F 32°F ~ 70°F 47°F 32°F ~ 70°F 47°F

UA Setting range Default 23°F ~ 61°F 38°F 23°F ~ 61°F 38°F 23°F ~ 61°F 38°F 23°F ~ 61°F 38°F 23°F ~ 61°F 38°F

*If outdoor unit not listed above table, please refer to outdoor IM for details.

15

LB Setting range Default -27°F ~ 52°F -27°F ~ 52°F 14°F ~ 52°F 14°F ~ 52°F 14°F ~ 52°F –

LA Setting range Default -36°F ~ 43°F -36°F ~ 43°F 5°F ~ 43°F 5°F ~ 43°F 5°F ~ 43°F –

6. Electrical work
6.5. Rotation setting
You can set these functions by wired remote controller. (Maintenance monitor) 1 Select “Service” from the Main menu, and press the [SELECT/HOLD] button. 2 Select “Settings” with the [F1] or [F2] button, and press the [SELECT/HOLD] button. 3 Select “Rotation setting” with the [F1] or [F2] button, and press the [SELECT/HOLD] button.

Settings menu
Function setting Rotation setting

Service menu: MENU Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

4 Set the rotation function. · Select “Rotation” with the [F1] button. · Select the switching period or “Backup only” with the [F2] or [F3] button.
“Rotation” setup options None, 1 day, 3 days, 5 days, 7 days, 14 days, 28 days, Backup only
Notes: · When 1 to 28 days are selected from the setup options, the backup function is also enabled. · When “Backup only” is selected, the rotation function will be disabled. The systems with refrigerant
addresses of 00 or 01 (00 system/ 01 system) will be operated as a main system while the 02 system is the standby mode as backup.

Rotation setting

Rotation

Backup only

TempDifTrigger +4°C

Select : SELECT Cur. – Content +

Reset

F1 F2 F3 F4

5 Set the support function. · Select “TempDifTrigger” with the [F1] button. · Select the difference between the suction temperature and the set temperature with the [F2] or [F3] button.
“TempDifTrigger” setup options
None, +4ºC, +6ºC, +8ºC
Notes: · The support function is available only in the COOL mode. (Not available in the HEAT, DRY and AUTO
mode.) · The support function is enabled when any option other than “None” is selected from the “Rotation”
setup options.

Rotation setting

Rotation

Backup only

TempDifTrigger +4°C

Select : SELECT Cur. – Content +

Reset

F1 F2 F3 F4

6 Press the [SELECT/HOLD] button to update the setting.
Reset method · Press the [F4] button in step 4 or 5 to reset the operation time of the rotation function. Once it is reset, operation will start from the systems with
refrigerant addresses of 00 or 01. Note: When the system with refrigerant address of 02 is in the backup operation, the 00 or 01 systems will be operated again.

16

Test run

7.1. Before test run
After completing installation and the wiring and piping of the indoor and outdoor units, check for refrigerant leakage, looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply.
Use a 500-volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1.0 M.

Do not carry out this test on the control wiring (low voltage circuit) terminals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0 M. Insulation resistance.

7.2. Test run
7.2.1. Using wired remote controller Make sure to read operation manual before test run. (Especially items to secure safety)
Step 1 Turn on the power.
Remote controller: The system will go into startup mode, and the remote controller power lamp (green) and “Please Wait” will blink. While the lamp and message are blinking, the remote controller cannot be operated. Wait until “Please Wait” is not displayed before operating the remote controller. After the power is turned on, “Please Wait” will be displayed for approximately 3 minutes.
Indoor controller board: LED 1 will be lit up, LED 2 will be lit up (if the address is 0) or off (if the address is not 0), and LED 3 will blink. Outdoor controller board: LED 1 (green) and LED 2 (red) will be lit up. (After the startup mode of the system finishes, LED 2 will be turned off.) If the outdoor controller
board uses a digital display, [- ] and [ -] will be displayed alternately every second. If the operations do not function correctly after the procedures in step 2 and thereafter are performed, the following causes should be considered and eliminated if they are found.
(The symptoms below occur during the test run mode. “Startup” in the table means the LED display written above.)

Symptoms in test run mode

Remote Controller Display

OUTDOOR BOARD LED Display < > indicates digital display.

Remote controller displays “Please Wait”, and After “startup” is displayed, only green lights

cannot be operated.

up. <00>

After power is turned on, “Please Wait” is displayed for 3 minutes, then error code is displayed.

After “startup” is displayed, green (once) and red (once) blink alternately.

After “startup” is displayed, green (once) and red (twice) blink alternately.

No display appears even when remote controller operation switch is turned on. (Operation lamp does not light up.)

After “startup” is displayed, green (twice) and red (once) blink alternately.

After “startup” is displayed, only green lights up. <00>

Display appears but soon disappears even when After “startup” is displayed, only green lights

remote controller is operated.

up. <00>

Cause
· After power is turned on, “Please Wait” is displayed for 3 minutes during system startup. (Normal)
· Incorrect connection of outdoor terminal block (L1, L2, GR and S1, S2, S3.)
· Outdoor unit’s protection devise connector is open.
· Incorrect wiring between the indoor and outdoor unit (Polarity is wrong for S1, S2, S3.)
· Remote controller transmission wire short. · There is no outdoor unit of address 0. (Address is other than
0.) · Remote controller transmission wire open. · After canceling function selection, operation is not possible for
about 30 seconds. (Normal)

Step 2 Switch the remote controller to “Test run”.
1 Select “Test run” from the Service menu, and press the [SELECT/HOLD] button. (Fig. 7-1)
2 Select “Test run” from the Test run menu, and press the [SELECT/HOLD] button. (Fig. 7-2)
3 The test run operation starts, and the Test run operation screen is displayed.

Service menu
Test run Input maintenance info. Settings Check Others
Main menu: RETURN Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 7-1

Test run menu
Test run Drain pump test run

Service menu: MENU Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 7-2

Step 3 Perform the test run and check the airflow temperature and auto vane.
1 Press the [F1] button to change the operation mode. (Fig. 7-3) Cooling mode: Check that cool air blows from the unit. Heating mode: Check that warm air blows from the unit.
2 Press the [SELECT/HOLD] button to display the Vane operation screen, and then press the [F1] and [F2] buttons to check the auto vane. (Fig. 7-4) Press the [RETURN] button to return to the Test run operation screen.

Test run Cool Mode

Remain

Pipe F
Switch disp. SELECT

Auto Fan

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 7-3

Remain

Vane

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Fig. 7-4

17

7. Test run

Step 4 Confirm the operation of the outdoor unit fan.
The speed of the outdoor unit fan is controlled in order to control the performance of the unit. Depending on the ambient air, the fan will rotate at a slow speed and will keep rotating at that speed unless the performance is insufficient. Therefore, the outdoor wind may cause the fan to stop rotating or to rotate in the opposite direction, but this is not a problem.

Step 5 Stop the test run.

1 Press the [ON/OFF] button to stop the test run. (The Test run menu will appear.) Note: If an error is displayed on the remote controller, see the table below.

LCD

Description of malfunction

U, F (* indicates an alphanumeric
character excluding FB.)

Outdoor unit malfunction Refer to the wiring diagram for the outdoor unit.

LCD

Description of malfunction

E0 ­ E5

Communication error between the remote controller and the indoor unit

E6 ­ EF

Communication error between the indoor unit and the outdoor unit

See the table below for the details of the LED display (LED 1, 2, and 3) on the indoor controller board.

LED 1 (microcomputer power supply)

Indicates whether control power is supplied. Make sure that this LED is always lit.

LED 2 (remote controller power supply)

Indicates whether power is supplied to the wired remote controller. The LED is lit only for the indoor unit that is connected to the outdoor unit that has an address of 0.

LED 3 (indoor/outdoor unit communication)

Indicates whether the indoor and outdoor units are communicating. Make sure that this LED is always blinking.

7.2.2. Using wireless remote controller
B
A 1
2 3
Fig. 7-5
A B
1
2 3
4 5
Fig. 7-6

Test run (Fig. 7-5)

1. Press the

button 1 to stop the air conditioner.

· If the weekly timer is enabled ( is on), press the

button 3 to

disable it ( is off).

2. Press the

button 2 for 5 seconds.

·

comes on and the unit enters the service mode.

3. Press the

button 2.

·

B comes on and the unit enters the test run mode.

4. Press the following buttons to start the test run.

: Switch the operation mode between cooling and heating and start the

test run.

: Switch the fan speed and start the test run.

: Switch the airflow direction and start the test run.

: Switch the louver and start the test run.

: Start the test run. 5. Stop the test run.

· Press the

button 1 to stop the test run.

· After 2 hours, the stop signal is transmitted.

Self-check (Fig. 7-6)

1. Press the

button 1 to stop the air conditioner.

· If the weekly timer is enabled ( is on), press the

button 3 to

disable it ( is off).

2. Press the

button 2 for 5 seconds.

·

A comes on and the unit enters the self-check mode.

3. Press the button 5 to select the refrigerant address (M-NET address) B of the

indoor unit for which you want to perform the self-check.

4. Press the

button 4.

· If an error is detected, the check code is indicated by the number of beeps

from the indoor unit and the number of blinks of the OPERATION INDICA-

TOR lamp. 5. Press the

button 1.

·

A and the refrigerant address (M-NET address) B go off and the self-

check is completed.

18

7. Test run

7.3. Self-check
Refer to the installation manual that comes with each remote controller for details.

· Refer to the following tables for details on the check codes. (Wireless remote controller) [Output pattern A]

Beeper sounds

Beep

Beep Beep Beep

Beep

Beep Beep

OPERATION INDICATOR lamp flash pattern

1st

2nd

3rd

nth

1st

2nd · · · Repeated

Off

On

On

On

On

Off

On

On

Self-check Approx. 2.5 sec. 0.5 sec. 0.5 sec. 0.5 sec.

0.5 sec. Approx. 2.5 sec. 0.5 sec. 0.5 sec.

starts

(Start signal received)

Number of flashes/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)

Number of flashes/beeps in pattern indicates the check code in the following table

[Output pattern B]

Beeper sounds

Beep

OPERATION INDICATOR lamp flash pattern

Off Self-check Approx. 2.5 sec. starts (Start signal received)

On Approx. 3 sec.

Beep 1st

Beep 2nd

Beep 3rd

On

On On

0.5 sec. 0.5 sec. 0.5 sec.

Beep nth

On

Off

0.5 sec. Approx. 2.5 sec.

Number of flashes/beeps in pattern indicates the check code in the following table (i.e., n=5 for “U2”)

On Approx. 3 sec.

Beep 1st

Beep 2nd · · · Repeated

On

On

0.5 sec. 0.5 sec.

Number of flashes/beeps in pattern indicates the check code in the following table

[Output pattern A] Errors detected by indoor unit

Wireless remote controller
Beeper sounds/OPERATION INDICATOR lamp flashes
Check code (Number of times) 1 2 3 4
5
6 7 8 9 10 11 12 14 No sound No sound No sound

Wired remote controller
RF thermostat
Check code
P1 P2, P9 E6, E7 P4 P5 PA P6 EE P8 E4 ­ PB (Pb) PB (Pb) PL E0, E3 E1, E2 ­ ­ ­ ­

Symptom
Inlet sensor error Pipe (Liquid or 2-phase pipe) sensor error Indoor/outdoor unit communication error Float switch connector CN4F open. Drain pump error Forced compressor error Freezing/Overheating safeguard operation Communication error between indoor and outdoor units Pipe temperature error Remote controller signal receiving error ­ Indoor unit fan motor error Indoor unit control system error (memory error, etc.) Refrigerant circuit abnormal Remote controller transmission error Remote controller control board error No corresponding

Remark

1 If the beeper does not sound again after the initial 2 beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come on, there are no error records.
2 If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm the self-check start signal was received, the specified refrigerant address is incorrect.
· On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit. Blink of operation lamp
· On wired remote controller Check code displayed in the LCD.

19

7. Test run

[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)

Wireless remote controller
Beeper sounds/OPERATION INDICATOR lamp flashes (Number of times) 1 2 3 4 5 6 7 8 9 10
11
12 13 14

Wired remote controller
RF thermostat
Check code
E9 UP U3, U4 UF U2 U1, Ud U5 U8 U6 U7
U9, UH
­ ­ Others

Symptom
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit) Compressor overcurrent interruption Open/short of outdoor unit thermistors Compressor overcurrent interruption (When compressor locked) Abnormal high discharging temperature/49C worked/insufficient refrigerant Abnormal high pressure (63H worked)/Overheating safeguard operation Abnormal temperature of heat sink Outdoor unit fan safeguard stop Compressor overcurrent interruption/Abnormal of power module Abnormality of super heat due to low discharge temperature Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/Current sensor error ­ ­ Other errors (Refer to the technical manual for the outdoor unit.)

Remark
For details, check the LED display of the outdoor controller board.

1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come on, there are no error records.
2 If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm the self-check start signal was received, the specified refrigerant address is incorrect.

· On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit. Blink of operation lamp
· On wired remote controller Check code displayed in the LCD.
· If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.

PLEASE WAIT

Symptom
Wired remote controller
For about 3 minutes following power-on

LED 1, 2 (PCB in outdoor unit)
After LED 1, 2 are lighted, LED 2 is turned off, then only LED 1 is lighted. (Correct operation)

PLEASE WAIT Error code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).

After about 3 minutes has expired following power-on

Only LED 1 is lighted. LED 1, 2 blink.
Only LED 1 is lighted. LED 1 blinks twice, LED 2 blinks once.

On the wireless remote controller with condition above, following phenomena takes place. · No signals from the remote controller are accepted. · OPE lamp is blinking. · The buzzer makes a short piping sound.

Cause
· For about 3 minutes following power-on, operation of the remote controller is not possible due to system start-up. (Correct operation)
· Connector for the outdoor unit’s protection device is not connected.
· Reverse or open phase wiring for the outdoor unit’s power terminal block (L1, L2, GR)
· Incorrect wiring between indoor and outdoor units (incorrect polarity of S1, S2, S3)
· Remote controller wire short

Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED 1, 2, 3) provided on the indoor controller, refer to page 18.

20

8. Easy maintenance function
Maintenance data, such as the indoor/outdoor unit’s heat exchanger temperature and compressor operation current can be displayed with “Smooth maintenance”. This cannot be executed during test operation. Depending on the combination with the outdoor unit, this may not be supported by some models.

1

Check menu

Error history Diagnosis Smooth maintenance Request code

Service menu: MENU Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

2

Smooth maintenance

Ref.address Stable mode
Cool / Heat/ Normal

Begin: SELECT

Cursor

Address

Smooth maintenance Ref.address Stable mode
Cool / Heat/ Normal StabilizationCollecting
Exit: ON/OFF

· Select “Service” from the Main menu, and press the [SELECT/HOLD] button. · Select “Check” with the [F1] or [F2] button, and press the [SELECT/HOLD] button. · Select “Smooth maintenance” with the [F1] or [F2] button, and press the
[SELECT/HOLD] button.
Select each item. · Select the item to be changed with the [F1] or [F2] button. · Select the required setting with the [F3] or [F4] button.
“Ref. address” setting ………. “0” – “15” “Stable mode” setting……….. “Cool” / “Heat” / “Normal” · Press the [SELECT/HOLD] button, fixed operation will start. * Stable mode will take approx. 20 minutes.

3

Smooth maintenance

Ref. address Cool COMP. current COMP. run time COMP. On / Off COMP. frequency Return: RETURN
Page

A
Hr times Hz

Smooth maintenance

Ref.address

Cool

Sub cool

OU TH4 temp.

OU TH6 temp.

OU TH7 temp.

Return: RETURN

Page

377 F 455 F
F 86 F

Smooth maintenance

Ref.address
IU air temp. IU HEX temp. IU filter time

Cool
83F F 5 5FF
HrHr

Return: RETURN Page

The operation data will appear. The Compressor-Accumulated operating (COMP. run) time is 10-hour unit, and the Compressor-Number of operation times (COMP. On/Off) is a 100-time unit (fractions discarded)
Navigating through the screens · To go back to the Service menu…………….[MENU] button · To return to the previous screen ………. [RETURN] button

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals