TRANE EXVG Water Source Heat Pump User Guide
- October 30, 2023
- Trane
Table of Contents
TRANE EXVG Water Source Heat Pump
Product Information: Water Source Heat Pump AxiomTM
The Water Source Heat Pump AxiomTM is a heating and cooling system that uses water as its heat source. It comes in various models, including EXVG009-030, EXVG036-070, DXHG024-070, EXHG009-024, and EXHG030-070. Each model has a different size, compressor type, net weight, ship weight, filter size nominal, water in/out size (FPT), condensate size (NPTI), and blower wheel size (inches). The system comes with various factory-installed and field-installed options such as ducted filter rack, deluxe controls, hot gas reheat, pump module, insulation, MERV filters, thermostats, drain pan, waterside economizer, and sound package.
Product Usage Instructions:
Before using the Water Source Heat Pump AxiomTM, ensure that it is installed correctly as per the installation manual. Ensure that the water source is connected to the system and that the system is powered on.
To control the system, use the provided thermostat or zone sensors. Set the desired temperature and mode (heating or cooling) using the controls. The system will automatically adjust its operation to maintain the set temperature.
Regular maintenance is necessary to ensure optimal performance of the system. Replace the air filters as per the manufacturer’s recommendations. Check the drain pan and clean it if necessary Inspect the blower wheel and clean it if necessary. Check the water source and ensure that it is clean and free of debris.
If you encounter any issues with the system, refer to the troubleshooting section of the user manual or contact a qualified technician for assistance.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Added Symbio™ 400-B to the table 1 List of option.
Table 1.List of options
Factory Installed Options | Field Installed Options |
---|---|
1-inch or 2-inch Ducted Filter Rack | 2-inch or 4-inch Ducted Filter Rack |
Air-Fi® Wireless Communications | Ducted Panel |
Deluxe 24V, Symbio™ 400-B/UC400-B Controls | Hose Kits (or ship separate hoses |
and valves)
Factory-mounted Isolation Valve| Low, Medium and High Electric Heat
Hot Gas Reheat| Pump Module
Matte or Foil Face Insulation| Pump Module Hose Kit
MERV 8 or 13 Filters| Thermostats or Zone Sensors
Polymer or Stainless Steel IAQ Drain Pan| Waterside Economizer
Recessed Unit Mounted Disconnect Switch|
Standard or Deluxe Sound Package
Table 2.General data – models EXHG009-024
Model EXHG | 009 | 012 | 015 | 018 | 024 |
---|---|---|---|---|---|
Unit size width x depth x height (in.) | 25.5 x 46 x 17.75 | 25.5 x 46 x 17.75 | |||
25.5 x 49 x 18.75 | 25.5 x 55 x 19.75 | 25.5 x 55 x 19.75 | |||
Compressor type | Rotary | Rotary | Rotary | Rotary | Scroll |
Net weight (lbs.) | 173 | 173 | 173 | 269 | 269 |
Ship weight (lbs.) | 297 | 297 | 297 | 393 | 393 |
Filter size nominal (in.) | 16 x 19 | 17 x 19 | 17 x 20 | 18 x 23 | 19 x 23 |
Water in/out size (FPT) | 1/2 | 1/2 | 1/2 | 3/4 | 3/4 |
Condensate size (NPTI) | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 |
Blower wheel Size (in.) | 9 x 8 | 9 x 8 | 10 x 8 | 10 x 9 | 10 x 9 |
Table 3.General data – models EXHG030-070
Model EXHG | 030 | 036 | 042 | 048 | 060 | 070 |
---|---|---|---|---|---|---|
Unit size width x depth x height (in.) | 28 x 68 x 21.75 | 28 x 68 x 21.75 | ||||
29.38 x 77.75 x 22.13 | 29.38 x 77.75 x 22.13 | 29.38 x 86.75 x 22.13 | 29.38 x |
86.75 x 22.13
Compressor type| Scroll| Scroll| Scroll| Scroll| Scroll| Scroll
Net weight (lbs.)| 313| 313| 381| 381| 434| 434
Ship weight (lbs.)| 458| 458| 560| 560| 613| 613
Filter size nominal (in.)| 20 x 30| 20 x 30| 20 x 20 (qty-2)| 20 x 20 (qty-2)|
30 x 20
20 x 20
| 30 x 20
20 x 20
Water in/out size (FPT)| 3/4| 3/4| 1.00| 1.00| 1.00| 1.00
Condensate size (NPTI)| 3/4| 3/4| 3/4| 3/4| 3/4| 3/4
Blower wheel Size (in.)| 11 x 11| 11 x 11| 11 x 11| 11 x 11| 11 x 11| 11 x 11
Table 4.General data – models EXVG009-03
Model EXVG | 009 | 012 | 015 | 018 | 024 | 030 |
---|---|---|---|---|---|---|
Unit size width x depth x height (in.) | 21.5 x 21.5 x 34 | 21.5 x 21.5 x 34 | ||||
21.5 x 23 x 36 | 21.5 x 26 x 38 | 21.5 x 26 x 38 | 24 x 32.5 x 42 | |||
Compressor type | Rotary | Rotary | Rotary | Rotary | Scroll | Scroll |
Net weight (lbs.) | 152 | 152 | 188 | 222 | 236 | 280 |
Ship weight (lbs.) | 207 | 207 | 246 | 282 | 296 | 343 |
Filter size nominal (in.) | 16 X 19 | 16 X 19 | 17 X 20 | 18 X 23 | 18 X 23 | 20 X |
30
Water in/out size (FPT)| 0.50| 0.50| 0.75| 0.75| 0.75| 1.00
Model EXVG| 009| 012| 015| 018| 024| 030
---|---|---|---|---|---|---
Condensate size (NPTI)| 0.75| 0.75| 0.75| 0.75| 0.75| 0.75
Blower wheel Size (in.)| 9 x 8| 9 x 8| 10 x 8| 10 x 9| 10 x 9| 11 x 11
Table 5.General data – models EXVG036-070
Model EXVG | 036 | 042 | 048 | 060 | 070 |
---|---|---|---|---|---|
Unit size width x depth x height (in.) | 24 x 32.5 x 42 | 25.4 x 32.5 x 49 | 25.4 | ||
x 32.5 x 49 | 25.4 x 32.5 x 55 | 25.4 x 32.5 x 55 | |||
Compressor type | Scroll | Scroll | Scroll | Scroll | Scroll |
Net weight (lbs.) | 281 | 329 | 345 | 367 | 432 |
Ship weight (lbs.) | 344 | 394 | 410 | 436 | 501 |
Filter size nominal (in.) | 20 X 30 | 27 X 30 | 27 X 30 | 30 X 33 | 30 X 33 |
Water in/out size (FPT) | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Condensate size (NPTI) | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 |
Blower wheel Size (in.) | 11 x 11 | 11 x 11 | 11 x 11 | 11 x 11 | 11 x 11 |
Table 6.General data – models DXHG024-070
Model DXHG | 024 | 036 | 048 | 060 | 070 |
---|---|---|---|---|---|
Unit size width x depth x height (in.) | 25.5 x 55 x 19.75 | 28 x 68 x 21.75 | |||
29.38 x 77.75 x 22.13 | 29.38 x 86.75 x 22.13 | 29.38 x 86.75 x 22.13 | |||
Compressor type | Two-Stage Scroll | Two-Stage Scroll | Two-Stage Scroll | Two- | |
Stage Scroll | Two-Stage Scroll | ||||
Net weight (lbs.) | 269 | 313 | 381 | 434 | 434 |
Ship weight (lbs.) | 393 | 458 | 560 | 613 | 613 |
Filter size nominal (in.) | 18 x 23 | 20 x 30 | 20 x 20 (qty-2) | 30 x 20 |
20 x 20
| 30 x 20
20 x 20
Water in/out size (FPT)| 3/4| 3/4| 1.00| 1.00| 1.00
Condensate size (NPTI)| 3/4| 3/4| 3/4| 3/4| 3/4
Blower wheel Size (in.)| 10 x 9| 11 x 11| 11 x 11| 11 x 11| 11 x 11
Table 7.General data – models DXVG024-070
Model DXVG | 024 | 036 | 048 | 060 | 070 |
---|---|---|---|---|---|
Unit size width x depth x height (in.) | 21.5 x 26 x 38 | 24 x 32.5 x 42 | 25.4 x | ||
32.5 x 49 | 25.4 x 32.5 x 55 | 25.4 x 32.5 x 55 | |||
Compressor type | Two-Stage Scroll | Two-Stage Scroll | Two-Stage Scroll | Two- | |
Stage Scroll | Two-Stage Scroll | ||||
Net weight (lbs.) | 236 | 279 | 354 | 371 | 437 |
Ship weight (lbs.) | 296 | 342 | 419 | 440 | 506 |
Filter size nominal (in.) | 18 x 23 | 23 x 30 | 27 x 30 | 30 x 33 | 30 x 33 |
Water in/out size (FPT) | 0.75 | 1.00 | 1.00 | 1.00 | 1.00 |
Condensate size (NPTI) | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 |
Blower wheel Size (in.) | 10 x 9 | 11 x 11 | 11 x 11 | 11 x 11 | 11 x 11 |
Table 8.ANSI/AHRI/ASHRAE/ISO13256-1 WLHP, GWHP and GLHP performance – 0.75 to 6 tons
Model
|
Rated GPM
|
Rated CFM
| Water Loop Heat Pump| Ground Water Heat Pump| Ground Loop
Heat Pump
---|---|---|---|---|---
Cooling 86°F| Heating 68°F| Cooling 59°F| Heating
50°F| Full Cool 77°F| Full Heat 32°F
Capacity Btuh|
EER
| Capacity Btuh|
COP
| Capacity Btuh|
EER
| Capacity Btuh|
COP
| Capacity Btuh|
EER
| Capacity Btuh|
COP
EXV/H009| 2.25| 285| 7900| 16.10| 9900| 5.6| 8800| 25.0| 8200| 4.8| 8300|
18.8| 6100| 3.7
EXV/H012| 3.00| 380| 11600| 16.40| 15200| 5.8| 13700| 27.9| 12300| 5.0| 12300|
19.5| 9300| 4.0
EXV/H015| 3.75| 475| 15100| 16.10| 18700| 5.3| 17000| 25.8| 15300| 4.6| 15800|
19.0| 12100| 3.8
EXV/H018| 4.50| 570| 18800| 17.60| 23600| 5.7| 21100| 28.7| 18800| 4.9| 19600|
20.6| 14600| 4.1
EXV/H024| 6.00| 760| 24600| 17.40| 32100| 5.7| 27400| 27.2| 25900| 5.0| 25600|
20.3| 19500| 3.9
EXV/H030| 7.50| 950| 31400| 17.80| 38400| 5.8| 35000| 27.2| 31000| 5.0| 32800|
20.7| 23600| 4.1
EXV/H036| 9.00| 1140| 35500| 17.60| 43100| 5.8| 39400| 26.5| 35000| 5.0|
37100| 20.4| 27200| 4.1
EXV/H042| 10.50| 1330| 38400| 18.00| 48000| 6.4| 43300| 27.5| 38500| 5.5|
40500| 21.1| 29400| 4.3
EXV/H048| 12.00| 1520| 45400| 17.70| 55600| 6.1| 50400| 26.4| 44800| 5.3|
47100| 20.3| 34600| 4.3
EXV/H060| 15.00| 1900| 55700| 17.50| 69000| 5.9| 60800| 25.7| 55900| 5.1|
57700| 20.1| 42900| 4.1
EXV/H070| 17.50| 2215| 63800| 17.30| 82100| 5.40| 68900| 24.9| 66900| 4.8|
66100| 19.80| 52000| 4.1
Note: Rated in accordance ANSI/AHRI/ASHRAE/ISO13256-1. Certified conditions are 80.6°F DB/66.2°F WB EAT in cooling and 68°F DB/59°F WB EAT in heating. Entering liquid temperature in cooling is 86°F for Water Loop, 77°F for Ground Loop (full load), 68°F for Ground Loop (part load), and 59°F for Ground Water. Entering liquid temperature in heating is 68°F for Water Loop, 32°F for Ground Loop (full load), 41°F for Ground Loop (part load), and 50°F for Ground Water
Table 9.ANSI/AHRI/ASHRAE/ISO13256-1 WLHP, GWHP and GLHP performance – 2 to 6 tons
Model
|
Load
|
Rated GPM
|
Rated CFM
| Water Loop Heat Pump| Ground Water Heat Pump| Ground Loop Heat
Pump
---|---|---|---|---|---|---
Cooling 86°F| Heating 68°F| Cooling 59°F|
Heating 50°F| Full Cool 77°F| Full Heat 32°F
Capacity Btuh|
EER
| Capacity Btuh|
COP
| Capacity Btuh|
EER
| Capacity Btuh|
COP
| Capacity Btuh|
EER
| Capacity Btuh|
COP
DXV/H024| Full| 6.0| 760| 24700| 16.8| 32100| 5.5| 27500| 24.4| 25700| 4.9|
25900| 19.2| 19400| 3.9
DXV/H024| Part| 6.0| 608| 18500| 17.7| 24100| 5.9| 20500| 28.3| 18900| 4.9|
20000| 24.5| 16300| 4.3
DXV/H036| Full| 9.0| 1140| 33000| 17.3| 40900| 5.9| 37100| 25.1| 32900| 5.1|
34500| 19.7| 25500| 4.1
DXV/H036| Part| 9.0| 912| 24500| 18.3| 30500| 6.3| 27600| 29.3| 24300| 5.2|
26600| 25.2| 21100| 4.5
DXV/H048| Full| 12.0| 1520| 45200| 17.9| 55200| 6.1| 50400| 26.4| 44400| 5.3|
46600| 20.6| 34500| 4.3
DXV/H048| Part| 12.0| 1216| 32800| 18.7| 40000| 6.6| 36900| 31.2| 31900| 5.3|
35700| 26.7| 28000| 4.7
DXV/H060| Full| 15.0| 1900| 52100| 17.6| 63900| 6.0| 56600| 24.8| 51700| 5.2|
53900| 19.9| 39800| 4.2
DXV/H060| Part| 15.0| 1520| 38300| 18.7| 47300| 6.6| 42000| 29.9| 37800| 5.4|
41000| 25.8| 32400| 4.6
DXV/H070| Full| 17.5| 2215| 64400| 17.3| 82700| 5.4| 69100| 23.8| 67400| 4.8|
66800| 19.6| 52900| 4.0
DXV/H070| Part| 17.5| 1772| 47100| 18.9| 59700| 6.0| 51100| 29.7| 48000| 5.0|
50000| 25.6| 42000| 4.4
Note:Performance data EXVG 0.5 Ton or 0.75 Ton Rated in accordance with ANSI/AHRI/ASHRAE/ISO13256-1. Certified conditions are 80.6°F DB/66.2°F WB EAT in cooling and 68°F DB/59°F WB EAT in heating. Entering liquid temperature in cooling is 86°F for Water Loop, 77°F for Ground Loop (full load), 68°F for Ground Loop (part load), and 59°F for Ground Water. Entering liquid temperature in heating is 68°F for Water Loop, 32°F for Ground Loop (full load), 41°F for Ground Loop (part load), and 50°F for Ground Water.
*Table 10.Electrical data – 0.75 to 6 tons, EX009-070**
Model No.| Unit Volts| Blower Motor HP| Minimum
Circuit Ampacity| Maximum Overcurrent Protective Device
---|---|---|---|---
EXH/EXV009| 208-230/60/1| 1/3| 6/6| 15/15
EXH/EXV009| 265/60/1| 1/3| 5| 15
EXH/EXV012| 208-230/60/1| 1/3| 8/8| 15/15
EXH/EXV012| 265/60/1| 1/3| 7| 15
EXH/EXV015| 208-230/60/1| 1/3| 10/10| 15/15
EXH/EXV015| 265/60/1| 1/3| 7| 15
Model No.| Unit Volts| Blower Motor HP| Minimum
Circuit Ampacity| Maximum Overcurrent Protective Device
---|---|---|---|---
EXH/EXV070| 460/60/3| 1| 13| 20
Model No.| Unit Volts| Blower Motor HP| Minimum
Circuit Ampacity| Maximum Overcurrent Protective Device
---|---|---|---|---
EXH/EXV018| 208-230/60/1| 1/2| 12/12| 20/20
EXH/EXV018| 265/60/1| 1/2| 10| 15
EXH/EXV024| 208-230/60/1| 1/2| 19/19| 30/30
EXH/EXV024| 265/60/1| 1/2| 13| 20
EXH/EXV024| 208-230/60/3| 1/2| 11/11| 15/15
EXH/EXV024| 460/60/3| 1/2| 6| 15
EXH/EXV030| 208-230/60/1| 3/4| 20/20| 30/30
EXH/EXV030| 265/60/1| 3/4| 16| 25
EXH/EXV030| 208-230/60/3| 3/4| 13/13| 20/20
EXH/EXV030| 460/60/3| 3/4| 7| 15
EXH/EXV036| 208-230/60/1| 3/4| 23/23| 35/35
EXH/EXV036| 265/60/1| 3/4| 17| 25
EXH/EXV036| 208-230/60/3| 3/4| 15/15| 20/20
EXH/EXV036| 460/60/3| 1| 7| 15
EXH/EXV042| 208-230/60/1| 3/4| 25/25| 40/40
EXH/EXV042| 208-230/60/3| 3/4| 17/17| 25/25
EXH/EXV042| 460/60/3| 1| 9| 15
EXH/EXV048| 208-230/60/1| 1| 25/25| 40/40
EXH/EXV048| 208-230/60/3| 1| 20/20| 30/30
EXH/EXV048| 460/60/3| 1| 9| 15
EXH/EXV060| 208-230/60/1| 1| 31/31| 50/50
EXH/EXV060| 208-230/60/3| 1| 22/22| 35/35
EXH/EXV060| 460/60/3| 1| 10| 15
EXH/EXV070| 208-230/60/1| 1| 39/39| 60/60
EXH/EXV070| 208-230/60/3| 1| 26/26| 40/40
*Table 11.Electrical data – 2 to 6 tons, DX024-070**
Model No.| Unit Volts| Blower Motor HP| Minimum
Circuit Ampacity| Maximum Overcurrent Protective
Device
---|---|---|---|---
DXH/DXV024| 208-230/60/1| 1/2| 17/17| 25/25
DXH/DXV024| 265/60/1| 1/2| 13| 20
DXH/DXV024| 208-230/60/3| 1/2| 10/10| 15/15
DXH/DXV024| 460/60/3| 1/2| 6| 15
DXH/DXV036| 208-230/60/1| 3/4| 19/19| 30/30
DXH/DXV036| 265/60/1| 3/4| 15| 20
DXH/DXV036| 208-230/60/3| 3/4| 13/13| 20/20
DXH/DXV036| 460/60/3| 1| 7| 15
DXH/DXV048| 208-230/60/1| 1| 25/25| 40/40
DXH/DXV048| 208-230/60/3| 1| 21/21| 30/30
DXH/DXV048| 460/60/3| 1| 10| 15
DXH/DXV060| 208-230/60/1| 1| 31/31| 50/50
DXH/DXV060| 208-230/60/3| 1| 22/22| 35/35
DXH/DXV060| 460/60/3| 1| 10| 15
DXH/DXV070| 208-230/60/1| 1| 39/39| 60/60
DXH/DXV070| 208-230/60/3| 1| 26/26| 40/40
DXH/DXV070| 460/60/3| 1| 12| 15
Figure 1.Clearances – EXHG/DXHG 0.75 to 6 tons
A minimum 14-inch clearance for servicing the unit is required for all EXH 0.75 to 6 tons configurations from other mechanical and electrical equipment (where shown) to enable panel removal from the unit for service/maintenance ability. The optimum clearance required is 20 inches.
Figure 2.Clearances – EXVG/DXVG 0.75 to 6 tons
A 24-inch clearance from other mechanical and electrical equipment (where
shown) is recommended for most unit configurations. This will enable panel
removal from the unit for service/maintenance. The 24-inch side clearance on
EXVG/DXVG 0.75-6T models is for optimal access only. Side clearance is not a
requirement as most components can be accessed from the front of the unit.
A 1-inch minimum clearance between the filter rack and any obstacle is
required for units in a free return application to provide proper airflow to
the air-to-refrigerant coil. A 12-inch minimum clearance between the filter
rack and any obstacle should be provided to properly attached ductwork.The
1-inch dimension shown in the back of the unit represents the supply duct
collar for the back supply option. This clearance is needed to clear these
flanges.
Trane – by Trane Technologies (NYSE: TT), a global climate innovator – creates comfortable, energy-efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
WSHP-PRC030D-EN 21 Jun 2023
Supersedes WSHP-PRC030C-EN (Mar 2023)