Commissioning and Settings Adjustment:

To commission or adjust settings for individual requirements or applications, you need to order the LEV71808 Hand Held Remote. This remote can be used for multiple sensors.

Installation Recommendations:

  • Ensure a minimum distance of 3m between each luminaire with sensors installed to avoid interference.
  • Avoid placing MW sensors near metal reflective surfaces or in narrow enclosed environments to prevent false triggering.
  • Keep the MW sensor away from electromagnetic wave products such as WIFI routers or cameras, maintaining a distance of more than 2 meters to prevent interference.

Microwave dimming Sensor: LEV71951

To fit sensor to the Toughbay™ Pro – remove the blank cap from the centre of the lens, then fit the sensor making sure not to cross thread by rotating clockwise until hand tight- do not over tighten. On/off function – When the sensor is powered on for the first time, the light will be turned on at 100% brightness, and it will be turned off after 10±5s. For Dim function- When the sensor is powered on for the first time, the light will be turned on at 100% brightness, and it will be turned off after 10±5s, it will then dim the light to a low level(set by standby dim level)During the initialization, the external movement induction signal will not be detected.NOTE: AFTER A POWER FAILURE THE SENSOR WILL MAINTAIN ITS SETTINGS.
For use with Toughbay™ Pro. The default settings below cannot be changed on the sensor manually.

Default settings are: Detection area 100%, Hold time 5 secs, Stand-by Period: 0 secs, Stand-by dim level: 10%, Daylight sensor: Disable.

To commission or adjust settings for individual requirements or individual applications;

Please order LEV71808 Hand Held Remote(one remote can be used for multiple sensors)
To avoid interference between luminaires with sensors installed, we recommend the minimum distance between each luminaire is 3m. MW sensors should be kept away from metal reflective surfaces, or a narrow enclosed environment, the microwave will be reflected repeatedly and cause false triggering. Ensure the MW sensor is kept away from electromagnetic wave products, such as WIFI router /WIFI camera, away from more than 2 meters to prevent electromagnetic wave interference.

SPECIFICATION

Input Voltage 12 + 2 VDC
Working current 25 + 5mA
Detection area 25%/50%/75%/100%
Hold Time 5s/30s/1 min/3min/5min/10min/20min/30min
Daylight Priority settings – on 51ux/15Lux/30Lux/50Lux
Daylight Priority settings – off 150lux

Standby Period

| 0s/10s/1 min/3min/5min/1 0min/30min/+ ¥(for on/off function set to 0s)(for 2 step dimming set to + ¥) (For 3 step dimming set to 10s/1 min/3min/5min/1 0min/30min + DH)
Stand-by dimming level| 10% / 20% / 30% / 50%
Sensor principle| Microwave motion detector(5.8GHz + 75MHz)
Mounting height(sensor)| 10m (12m) Max.(when mounted at 12m, do not set detection area 25% or 50%, it will not detect correctly)
Motion detection| (0.3-1 m/s) @10m
Operating temperature| 0°C TO 40°c
IP rating| IP65
Factory Setting| Detection area:100%,Hold time:3 min, Stand-by Period: 5 min, Stand-by dim level:50%, Daylight Sensor: Disable

FAQs

FAQ’S – QUESTION CAUSE REMEDY



THE LUMINAIRE WILL NOT COME ON

| INCORRECT DAYLIGHT SENSOR SETTING SELECTED| ADJUST SETTING
LOAD HAS FAILED| REPLACE LOAD
POWER IS SWITCHED OFF| SWITCH ON POWER





THE LOAD IS PERMINANTLY ON

| CONTINUOUS MOVEMENT IN DETECTION AREA| CHECK DETECTION AREA SETTING
TOO CLOSE TO WIFI HUB/ROUTER| MOVE WIFI HUB/ROUTER RO REPOSITION FITTING
THE LUMINAIRE IS INSTALLED IN AN AREA TO CLOSE TO REFLECTIVE SURFACES i.e. GLASS, METAL OR CONCRETE WALLS| 1.   ENSURE THAT LUMINAIRE IS INSTALLED WITH A MINIMUM 100CM SPACE BETWEEN ANY REFLECTIVE SURFACES

2. REDUCE SENSITIVITY(DETECTION AREA)

WILL NOT ILLUMINATE EVEN THOUGH THERE IS MOVEMENT| SPEED OF MOVING OBJECT IS NOT IN THE RANGE OF 0.5-1M/S OR THE DETECTION RADIUS IS TOO SMALL| ****

CHECK DETECTION SETTINGS


THE REMOTE CONTROL IS NOT WORKING

| BATTERY IS DEAD| REPLACE BATTERY
THE REMOTE CONTROL IS NOT ALIGNED WITH THE SENSOR| CHANGE THE POSITION/ANGLE OF THE REMOTE/CHECK TOGGLE BUTTON SETTING FOR CORRECT HEIGHT

Remote Control Setting

Transmitting angle of remote control against different setting, please choose right button based on mounting height of sensor.

Note: False triggering can occur when a fi tting/sensor is installed too close to a large solid object i.e. wall. If this happens reduce the detection area sensitivity/percentage to resolve this. It is recommended by the manufacturer that this product is installed a minimum of 2 Metre away from any solid object i.e. wall/steel work or glass.

Detection area diagrams

ISO9001 – 2015 – Registered Firm Certificate No. GB 1552
JCC Lighting Products Ltd. Lux Park, Chichester Business Park, City Fields Way, Tangmere, Chichester, West Sussex, PO20 2FT

Technical Support: +44(0)1243 838986
Customer Services: +44(0)1243 838999

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals