CyberPower PR2200RT2UCN Smart App Sinewave Ups User Manual

September 8, 2024
CyberPower

PR2200RT2UCN Smart App Sinewave Ups

“`html

Specifications:

  • Model: PR2200RT2UCN/PR2200RTXL2UCN

  • Manufacturer: Cyber Power Systems (USA), Inc.

  • Input: AC Inlet

  • Output: Battery Backed and Surge Protected Outlets

  • Network Connectivity: SNMP/HTTP Network Slot, Cloud Monitoring
    (Ethernet Port)

  • Ports: BM Port (PR2200RTXL2UCN), Dry Contact, Serial Port, USB
    Port, EPO/ROO Port

  • Additional Features: LCD Module, Output Circuit Breaker, TVSS
    Screw, Extended Battery Module Connector Socket

Product Usage Instructions:

1. Installation and Setup:

Follow the provided user manual for installation instructions.
Ensure the UPS is connected to a grounded AC power outlet with fuse
or circuit breaker protection.

2. Maintenance Guidelines:

Regularly check and maintain the UPS and batteries as per the
manual. Do not remove the cover except for battery servicing.

3. Safety Precautions:

  • Do not use the UPS for medical or life support equipment.

  • Avoid direct sunlight exposure and keep away from strong heat
    sources.

  • Do not block ventilation openings around the housing.

FAQ:

Q: How do I register my product?

A: Visit www.cyberpowersystems.com/registration to register your
product for warranty and support benefits.

Q: What should I do in case of a power outage?

A: The UPS will provide backup power during outages. Ensure it
is properly connected and charged for uninterrupted operation.

Q: Can I connect sensitive equipment to the UPS?

A: Yes, connect sensitive electronics to the battery-backed
outlets for surge protection.

“`

YOUR ULTIMATE ALLY IN POWER

SMART APP SINEWAVE UPS SERIES
PR2200RT2UCN/PR2200RTXL2UCN
USER MANUAL

1

2

6 7

5

4

3

8 9 10 11

FEATURES
1. PowerSwitch 2. ToollessBatteryAccessDoor
(behindfaceplate) 3. FrontPanelAccessTabs
(behindfaceplate) 4. LCDModule 5. Faceplate

18

17 16 15 14 13 12

6. BatteryBackedandSurge ProtectedOutlets
7. OutputCircuitBreaker 8. SNMP/HTTPNetworkSlot 9. CloudMonitoring(EthernetPort) 10. InputCircuitBreaker 11. ACInlet 12. BMPort(PR2200RTXL2UCN) 13. DryContact 14. SerialPort 15. USBPort 16. EPO/ROOPort 17. TVSSScrew 18. ExtendedBatteryModule
ConnectorSocket(PR2200RTXL2UCN)

Cyber Power Systems (USA), Inc. 424112thAvenueEast,Suite400|Shakopee,MN55379|CyberPowerSystems.com

PRODUCT REGISTRATION
ThankyouforpurchasingaCyberPowerproduct.Pleasetakeafewminutestoregisteryour productatwww.cyberpowersystems.com/registration.Registrationcertifiesyourproduct’s warranty,confirmsyourownershipintheeventofaproductlossortheftandentitlesyoutofree technicalsupport.RegisteryourproductnowtoreceivethebenefitsofCyberPowerownership.

IMPORTANT SAFETY WARNINGS (SAVETHESEINSTRUCTIONS)
Thismanualcontainsimportantinstructionsthatshouldbefollowedduringinstallationand maintenanceoftheUPSandbatteries.Pleasereadandfollowallinstructionsthoroughlybefore andduringtheinstallationandoperationoftheproduct.

CAUTION! TheUPSmustbeconnectedtoa groundedACpoweroutletwithfuseorcircuit breakerprotection.DONOTplugtheUPSinto anoutletthatisnotgrounded.Ifyouneed todeenergizethisequipment,turnoffand unplugtheUPS.
CAUTION! Thebatterycanenergize hazardouslivepartsinsideevenwhenthe ACinputpowerisdisconnected.
CAUTION! Topreventtheriskoffireor electricshock,installinatemperature andhumiditycontrolledindoorarea,free ofconductivecontaminants.Pleasesee specificationsforacceptabletemperature andhumidityrange.
CAUTION! Forpluggableequipment,the socketoutletshallbeinstallednearthe equipmentandshallbeeasilyaccessible.
CAUTION! Toreducetheriskofelectricshock, donotremovethecover,excepttoservicethe battery.Therearenoserviceablepartsinside, exceptforthebattery.
CAUTION! Toavoidelectricalshock,turnoff theunitandunplugitfromtheACpower sourcebeforeservicingthebatteryor installingacomputercomponent.
CAUTION! Wheninstallingtheequipment, ensurethatthesumoftheleakagecurrentof theUPSandtheconnectedequipmentdoes notexceed3.5mA.
CAUTION! DonotunplugtheunitfromAC Powerduringoperation,asthiswillinvalidate theprotectivegroundinsulation.
CAUTION! Toreducetheriskoffire,connect onlytoacircuitprovidedwith30amperes maximumbranchcircuitovercurrent protectioninaccordancewiththeNational ElectricCode,ANSI/NFPA70.

CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! DONOTusein anycircumstancethatwouldaffectoperation orsafetyofanylifesupportequipment,with anymedicalapplications,orpatientcare.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! Toreducetheriskoffire,do notusewithornearaquariums.Condensation fromtheaquariumcancomeincontact withmetalelectricalcontactsandcausethe machinetoshortout.
CAUTION! DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE!
CAUTION! DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE HOUSING!
CAUTION! DO NOT USE THE UPS ON ANY TRANSPORTATION! Toreducetheriskoffire orelectricshock,donotusetheunitonany transportationsuchasairplanesorships.The effectofshockorvibrationcausedduring transitandthedampenvironmentcancause theunittoshortout.
CAUTION! DisposeoforrecycletheUPS aftertheendofitslifeinaccordancewith localregulations.

INSTALLING YOUR UPS SYSTEM
UNPACKING
InspecttheUPSuponreceipt. Theboxshouldcontainthefollowing:
(a)UPSunit
(b)Faceplate
(c)RailKitCP2RAIL02,includes: 14xM5PanHeadScrews 8xPlasticWashers
(d)Managementcables 1xUSBCable 1xEPOCable
(e)User’sManual
(f)MechanicalAccessory,includes: 2xRackMountBracketsCPEAR04 2xRackMountHandles 1xTowerBaseplate 12xDustCovers 4xM5TrussHeadScrews 8xM5FlatHeadScrews 4xM4FlatHeadScrews 4xRubberFeet 4xM4RoundHeadScrews
OVERVIEW
TheCyberPowerSmartAppSinewave UninterruptiblePowerSupply PR2200RT2UCN/PR2200RTXL2UCNfeatures 2430Joulesofsurgeprotection,provides batterybackupduringpoweroutagesand isActivePFCcompatibleforsafeguarding missioncriticalservers,telecomequipment, VoIPandinternetworkinghardwarethat requireseamlesssinewavepower.Itsfull AutomaticVoltageRegulation(AVR)boost/ bucktechnologydeliversaconsistentand cleanACpower,protectingconnected equipmentandpreventingcostlybusiness interruptions.ThisUPSisGreenPowerUPSTM Bypasscircuitrypatentedtosaveonenergy costsbyreducingenergyconsumptionand heatbuildup.
TheUPSunitincorporatesmicroprocessor basedfulldigitalcontrolandincludes PowerPanel®Businesssoftwareprovidingthe userunsurpassedflexibilityandcontrol.An optionalSNMP/HTTPRemoteManagement adapter(RMCARD)supportsremote managementandcontrolofthemachine throughastandardwebbrowser.

AUTOMATIC VOLTAGE REGULATOR
Theincomingutility powermaybedamaging toimportantdataand hardware,butwith AutomaticVoltage Regulation,thecomputer willnotexperience damagingvoltagelevels. TheAVRautomatically increaseslowordecreaseshighvoltagetoa safeandconsistentoutputvoltage.
DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
1. Ensurethattheequipmentpluggedintothe UPSdoesnotexceedtheUPSunit’srated capacity.Iftheratedcapacitiesoftheunit areexceeded,anoverloadconditionmay occurandcausetheUPSunittoshutdown orthecircuitbreakertotrip.
2. Therearemanyfactorsthatcanaffect theamountofpowerthatyourelectronic equipmentwillrequire.Foroptimalsystem performancekeeptheloadbelow80%of theunit’sratedcapacity.
INSTALLATION
Theproductisdesignedfortowerinstallation andrackinstallationfor2postrackand 4postrack.Readandfollowtheprocedures thoroughlybeforeandduringyourinstallation oftheproduct.Theinstallationvideosare availableonline.ScantheQRcodebelowfor detailedinformation.
Preparation
CAUTION! Itisstronglyrecommendedtohave anadditionalpersonassistthisinstallation processiftheproductisheavy.
CAUTION!Itisstronglyrecommendedthat the2postrackbeboltedtothefloorpriorto theinstallationoftheproduct.
1. Removeallequipmentconnectedto theproduct.
2. Makesuretheproductisdisconnected fromACpowersource.
3. Removeinternalbatteriestoreduce weightoftheunitbeforetheinstallation. RefertoBATTERYREPLACEMENTsection forinstructions.

INSTALLING YOUR UPS SYSTEM – CONTINUED
Rack Installation for 2-Post Rack

1 x8

2 x4,

x4

1. AttachthebracketswithprovidedM5flatheadscrews.
2. AffixtheproducttotherackwithsuitableM5/M6screwsandcagenuts. (M5trussheadscrewsareprovidedwiththeproductinthemechanicalaccessorybox.)

Rack Installation for 4-Post Rack

1 x8, x6

2 x8,

x8

3 x4

x4

1. UsetheprovidedM5flatheadscrewstoattachthebracketsandprovidedM5panhead screwsforhangingbrackets.
2. ScrewthehangingrailstotherackwithprovidedM5panheadscrewsandplasticwashers.
3. Lifttheproductuponthehangingrailsandslidetheunitintotherack.Affixtheproduct totherackwithprovidedM5trussheadscrews.Ifhandlesareneeded,affixthemtothe bracketswithM4flatheadscrews.
Note:TheRailKitisincludedforselectedmodels.SeeUNPACKINGsection.Forothermodels, itisalsoavailableforpurchase.PartnumberCP2RAIL02.

Tower Installation

1 x4

2

x4, 3 x4

1. AttachthebracketstothebaseplatewiththeprovidedM4flatheadscrews.
2. RemovethefaceplateandrotatetheLCDmodule,thenreinstallthefaceplate.
3. ScrewtherubberfeetwithprovidedM4roundheadscrewsandthenputtheUPSonto theassembledtowerstand.Youcanalsoputthedustcoversinthescrewholesonthe topsideoftheUPStopreventdustfromfallingintotheunit.

BASIC OPERATION

Normal Use
1. ProperlyinstalltheUPS.
2. Connectequipmenttotheoutletsonthe rearpanelofUPS.
3. PlugtheUPSintoa2pole,3wire groundedreceptacle/walloutlet.
4. PressthepowerswitchonLCDmodule once.Thedisplayscreenwilllightup andshow”UPSOn/Off”onthefirstline. UsetheUp/Downbuttontoselect”On” or”DelayOn”andthenpresstheEnter buttontoturnontheUPS. ThedisplayscreenwillshowCyberPower inthefirstlineandtheUPSmodelinthe secondline.ThentheOnlineorOnBattery IndicatorontheLCDmodulelightsup, indicatingtheUPSisoperatingfromutility orbattery.
5. ToturnofftheUPS,pressthepowerswitch onLCDmoduleonce.Thedisplayscreen willlightupandshow”UPSOn/Off”on thefirstline.UsetheUp/Downbuttonto select”Off”or”DelayOff”andthenpress theEnterbuttontoturnofftheUPS.The displayscreenwillshow”Goodbye”andall theindicatorswillbeoff.
IMPORTANT! For first time usage, plug your UPS into an AC outlet to disable cold start protection. Otherwise, your UPS will not turn on.
IMPORTANT! Do not use an adapter, line conditioner, or other surge protection devices between the wall outlet and the UPS. Use of such a device may impede proper operation of the UPS.
Beawareofthefollowingstatements:
A. YourUPSmaybeusedimmediatelyupon receipt.However,chargingthebatteryfor atleast12hoursisrecommendedtoensure thebatteryreachesitsmaximumcharge. Chargelossmayoccurduringshipping andstorage.Torechargethebattery, simplyleavetheunitpluggedintoanAC outlet.Theunitwillchargeineithertheon oroffstate.
B. Tomaintainoptimalbatterycharge, leavetheUPSpluggedintoanACoutlet atalltimes.

C. DONOTplugalaserprinter,copier,space heater,vacuum,papershredder,pumpsor otherlargeelectricaldevicetotheUPS. Thepowerdemandsofthesedeviceswill possiblyoverloadanddamageyourUPS.
D. AlwaysplugtheUPSintoa2pole,3wire groundedreceptacle/walloutlet.Make surethewallbranchoutletisprotected byafuseorcircuitbreakeranddoesnot serviceequipmentwithlargeelectrical demands,e.g.airconditioner,refrigerator, copier,etc.Avoidusingextensioncords.
E. Topreventtheriskofelectricshock,follow thestepstogroundtheUPS:
(a)ConnectagroundwiretotheTVSS screwontherearpanelofUPS.
(b)Connectanothersideoftheground wiretotheground.
F. IfyourUPSfreezes,youcandoahard rebootasbelowsteps.
(a)Pressandholdthepowerswitchon theLCDmoduleforaround1520seconds; theUPSwillbeforciblyshutdown.All indicators,displayscreen,andoutputwill beoffimmediately.
(b)Afteranabnormalshutdown,theUPS restartsitselfwhenitispoweredbyutility. IftheUPSdoesnotrestartautomatically, slightlypressthepowerswitchonLCD moduleoncetowakeuptheUPSto performtheautorestartfunction.
Whenthereisnoutility,youneedto followbelowprocedurestoturnonthe UPS.Slightlypressthepowerswitchon LCDmoduleonce.Thedisplayscreen willlightupandshow”UPSOn/Off”on thefirstline.UsetheUp/Downbuttonto select”On”or”DelayOn”andthenpress theEnterbuttontoturnontheUPS.The displayscreenwillshowCyberPowerinthe firstlineandtheUPSmodelinthesecond line.ThentheOnBatteryIndicatoronthe LCDmodulelightsup,indicatingtheUPS isoperatingfrombattery.
Note:WhentheUPSisoff,pressingand holdingthepowerswitchforaround15 20secondscannotturnontheUPSeven thoughthedisplayscreenwilllightup forafewseconds.Followabovestepsto correctlyturnontheproduct.

CLEANING AND MAINTENANCE
CAUTION!Toreducetheriskofelectricshock,donotremovethecoverexcepttoservice thebattery.Therearenouserserviceablepartsinsideexceptforthebattery.Forbattery replacement,pleaserefertoBATTERYREPLACEMENTsection.
CAUTION!TurnofftheunitandunplugitfromtheACpowersourcebeforecleaning.
CAUTION!Neverimmersetheunitinwaterorotherliquids.Onlyuseasoft,slightly dampclothtowipethesurfaceoftheunit.Donotuseaspraydirectlytocleanordisinfect theunit.Tostoretheproductforanextendedperiod,coveritandstorewiththebatteryfully charged.Whileinstorage,rechargethebatteryeverythreemonthstoensurebatterylife.

OPERATION AND STORAGE ENVIRONMENT
Topreventriskoffireorelectricshock,installorplacetheunitinatemperatureandhumidity controlledindoorarea,freeofconductivecontaminants.

Operation Storage

Temperature RelativeHumidity
Elevation Temperature RelativeHumidity
Elevation

32°F­104°F/0°C­40°C 0%­95%Noncondensing 0­9,843ft./0­3,000m 5°F­113°F/15°C­45°C 0%­95%Noncondensing 0­49,213ft./0­15,000m

NETWORK OPERATION
Local Monitoring ConnecteithertheUSBcableorSerialcabletothecorrespondingportontheUPSandon thecomputerwithPowerPanelBusinesssoftwareinstalled.PowerPanelBusinesssoftwareis availableonourwebsite.Pleasegotowww.cyberpowersystems.com/products/software/power panelbusinessforthefreedownload.Note:USBandSerialportcannotbeusedsimultaneously. SerialportwillbedisablediftheUSBportisused.
Remote Monitoring ThisproductisequippedwithaSNMP/HTTPnetworkslot.IfyouwouldliketocontroltheUPS fromaremotelocation,especiallyunderaprivatenetwork,aCyberPowerRemoteManagement Card(RMCARD)isrequired.Formoreinformation,visitwww.cyberpowersystems.com.

Cloud Monitoring
ThisproductfeaturesanEthernetportforCloudConnection,whichmakesiteasytomonitor CyberPowerUPSsystemsfromanywhere.FollowbelowstepstogetyourUPSonCloud.
1. Hardwareinstallation:ConnecttheCloudMonitoring(EthernetPort)ontheUPSrearpanel toawalljackornetworkswitchusingasuitableEthernetcable.

LED Indicators

Conditions

Link

Off

TheUPSisnotconntectedtothenetwork

On(Yellow) TheUPSisconnectedtothenetwork.

Off

TheCloudMonitoring(EthernetPort)isnotpowered.

Tx/Rx On(Green) TheCloudMonitoring(EthernetPort)ispowered.

Flashing

Receivingortransmittingdatapacket.

2. Applicationinstallation:InstallPowerPanelCloudApponyoursmartphoneandthen launchtheapplication.PowerPanelCloudAppisavailablefordownloadontheAppleApp StoreorGooglePlay.

iOS

Android

3. Signupandlogin.

NETWORK OPERATION – CONTINUED
4. AddadeviceinthePowerPanelCloudApp. (a) Click”+”intheupperrightcornerofthehomepage.
(b) Locatethe”AddDevicebyQRCode”toaddyourCloudUPS. (c) ScantheQRCodeonthetopsideoftheUPS.IftheQRCodescanwassuccessful,
click”Add”andnamethedeviceyouaremonitoring. (d) Afterthesetupiscompleted,youwillseeyourdeviceonthehomepage.
(e) WaittilltheUPSissuccessfullyconfigured.
5. StartmonitoringyourUPS! InadditiontotheMobileApp,youcanaccessthePowerPanelCloudaccountviaaweb browser:https://powerpanel.cyberpower.com.Formoreinformation,pleaserefertothe PowerPanelCloudUser’sManual.

LCD OPERATION GUIDE

Display Interface

1

1. PowerSwitch/PowerOnIndicator

2. OnlineIndicator

3. Fault/WarningIndicator

2

4

4. OnBatteryIndicator

3

5

5. BatteryFaultIndicator

6. DisplayScreen

7. MenuButton

6

8. EscButton

9. UpButton

10. DownButton

11. EnterButton

Menu

Esc

Enter

7 8 9 10 11

Basic Operation PressUp/DownButtontoscrollthroughtheUPSstatus.PressEscbuttontogobacktotop.

Menu Status

Item

OperationMode

EstimatedRuntime

InputVoltageInformation BatteryInformation

OutputVoltageInformation LoadInformation

NCLStatus UPSTemperature DateandTime

LCD Setting Guide
PressMenuButtontoenterSetupMenuanduseUp/DownButtontoscrollthroughmenus. PressEnterButtontogointotheselectedmenuandusetheUp/DownButtonandEnterButton toselectthesettingitemandtocompletethesetting.EscButtonispressedtoexitthesubmenu andgobacktopreviouspage.

Menu BasicSetup

UtilityQuality

AmbientSetup

ECOMode LEDBrightness

OutletControl Test Logs

UPSConfiguration SelfTest Event110

Item
Sensitivity
LCDHibernation CyclingDisplay NCLConfiguration AlarmTest

ExtendedBatteryModule Quantity(Selectmodels) AudibleAlarm
tablecontinued

LCD OPERATION GUIDE – CONTINUED

Menu About

UPSModelName UPSSerialNumber LastBatteryChangeDate NextBatteryChangeDate

Item UPSFirmwareVersion IPAddress MACID ServicePortnumber

AdvancedSetup

OutputVoltage MinimumOutputVoltage MaximumOutputVoltage LowBatteryThreshold BatteryChangeDate

ScheduleTest DateandTime PowerMeterRest IPAccess IPAddress

tablecontinued
BMStatus UPSBatteryInformation
SubnetMask Gateway FirmwareUpdate BacktoDefault
Onlydisplayedinstandbymode

Menu / Basic Setup

Item

Default

Option

Description

UtilityQuality

Normal

Good Normal Poor

Selectthevoltagequalityoftheinpututilitypower.
IfGoodisselected,theUPSwillbemoresensitiveto powerqualityandgotobatterymodemoreoftento supplythecleanestpowertoconnecteddevices.
IfPoorisselected,theUPSwilltoleratemorepower fluctuationsandgotobatterymodelessoften.

Sensitivity

Medium

ExtendedBattery
ModuleQuantity 0 (Selectmodels)

Customized
High Medium Low
010 Autosensing

“Customized”showsupwhenMaximum/Minimum OutputVoltagehasbeenadjustedinAdvancedSetup Menuorthroughsoftware.
Selectthesensitivityleveltopowereventsfor connectedequipment. Iftheconnectedequipmentishighlysensitiveto powerevents,selectHigh;theUPSwillgotobattery modemoreoftentoprovidethecleanestpower. Iftheconnectedequipmentcantoleratemorepower events,selectLow;theUPSwillgotobatterymode lessoften.
IfAutosensingisselected,theUPSwillchangethe numbersautomatically.

LCD OPERATION GUIDE – CONTINUED

Menu / Ambient Setup

Item

Default

Option

Description

ECOMode

Active

LEDBrightness Dim

Active Inactive

WhenActiveisselected,theUPSwillchange relatedsetupfunctionsinthismenuautomatically toworkunderlowenergyconsumption.

Youcanalsosetthefunctionsinthismenu ActiveCustomized independentlyandthengobacktoEcoMode InactiveCustomized tohaveacheck.IfActiveisdisplayed,theUPS
worksunderlowenergyconsumption.

Bright Normal Dim OnlyPowerOn

TheLEDbrightnesscanbesetinaccordancewith theambientlightsordifferentusagescenario.
IfOnlyPowerOnisselected,allLEDindicators willbeoffexceptPowerOnIndicator.

LCDHibernation

Afterone minute

Never After1minute After5minutes After10minutes

Afterthisamountoftimewithnoactivity,the displayscreenwillshutofftosaveenergy.

CyclingDisplay Never

Never After10seconds After20seconds After30seconds

Afterthisamountoftimewithnoactivity, UPSwillstartcyclingthestatusinformationon displayscreen.

AudibleAlarm

Quiet

Normal Quiet MuteonBattery Off

Normalcontainsfaultandwarningalarmsand allremindingalarmsofbatteryoperation includingswitchingtobatterypower,working underbatterymode,reachingLowBattery Threshold,soonrunningoutofbattery,and LowBatteryShutdown.
IfQuietisselected,theUPSwillemitfaultand warningalarmsandremindingalarmindicating theUPSreachesLowBatteryThreshold.
IfMuteOnBatteryisselected,onlyfaultand warningalarmwillsound.
AllalarmsaredisabledifOffisselected.

LCD OPERATION GUIDE – CONTINUED

Menu / Outlet Control

Item DelayTurnOn

Default

Option

4seconds 0600seconds

DelayTurnOff

4seconds 0600seconds

RebootDuration 12seconds 4300seconds

Minimum Restored Capacity

0%

0100%

Uptimeon Battery

Disable

Enable:51800 seconds
Disable

Reserved Runtime

Disable

NCLSwitch
Canonlybeconfigured intheSubmenu,NCL Configuration.

On

OffonOverload
Canonlybeconfigured intheSubmenu,NCL Configuration.

Disable

Enable:01800 seconds Disable On DelayOn Off DelayOff Reboot DelayReboot
Enable Disable

Description
Theamountoftimethattheoutletswillwaitbefore actualstartup.
Theamountoftimethattheoutletswillwaitbefore actualshutdown.
Theamountoftimethattheoutletswillremainoff beforetheUPSrestartsitself.
ItisthecriteriaforUPStoperformautorestartas utilityisrestored.Ifbatterycapacityishigherthan thissetting,theautorestartwillbeperformed; otherwise,theUPSwillkeepchargingthebattery untilbatterycapacityreachesthatlevel.
Setthemaximumruntimeonbatterymode.The UPSwillshutdownaftertheamountoftimespent inbatterymodehasreachedthissetting.Makesure theestimatedruntimeislargerthanthissetting; otherwise,theUPSwillstillstopsupplyingpower whenitisrunningoutofbattery.
WhentheUPSisinbatterymode,itwillcut offoutputpowerwhentheremainingruntime reachesthelevel.
ThisisthemainswitchforNCLoutletgroups.
NCLoutletswillbeturnedoffwhentheUPSis overloadedinbatterymodeiftheitemisenabled. NCLoutletswillturnonautomaticallyasutility isrestored.

Menu / Test Item
SelfTest
AlarmTest

Default

Option

Yes No
No

ShortTest ShortTest
ContinuousTest

Description
SelectYestoordertheUPStoquicklytestthe backupfunctionbyenteringtobatterymode, checkingifitworks.Thetesttakesaround10 seconds.
Thisitemteststhealarm’saudiblewarningand LEDindicators’functionalities.Shorttestlasts5 seconds.Incontinuoustesting,pressanybuttonto stopthetest.

LCD OPERATION GUIDE – CONTINUED
Menu / Logs AllkindsofeventsarerecordedandtheUPSwillshowthelast10eventsinthismenu.Events arecategorizedintofoursortsandshowninacapitalletterinasingleeventlogonthedisplay screen:(F)Fault,(W)Warning,(S)Shutdown,andnoletterforanormaltransferevent.

Menu / Advanced Setup
ThismenucontainsmoreadjustableanddetaileditemsforUPSadvancedusage.Readtheitem descriptionsbelowthoroughlybeforeyouchangethesettings.

Item

Default

Option

OutputVoltage

120V
Selectmodels andregions

100V 110V 120V 127V

100V:89V 100V:8692V

MinimumOutput 110V:97V 110V:97106V

Voltage

120V:102V 120V:97106V

127V:111V 127V:108114V

100V:111V 100V:108114V

MaximumOutput 110V:128V 110V:127136V

Voltage

120V:131V 120V:127136V

127V:143V 127V:140146V

LowBattery Threshold

300 seconds

01800seconds

35%

2065%

BatteryChange Date

/

ScheduleTest­ OnStartup

No

ScheduleTest­ Frequency

Never

DateandTime
PowerMeter Reset

// :
No

Month/Year
Yes No Never Every1week Every2weeks Every3weeks Every4weeks Year/Month/Day Hour:Minute
Yes No

Description
SelecttheACoutputvoltageonbatterymode.
Setthevalueloweriftheutilityvoltageisusually lowtoavoidunnecessarybatteryusage. Makesuretheconnectedequipmentcanwork underthevoltagecondition.
Setthevaluehigheriftheutilityvoltageisusually hightoavoidunnecessarybatteryusage. Makesuretheconnectedequipmentcanwork underthevoltagecondition.
TheUPSwillemitanaudiblealarmindicatingthat theremainingruntimeisreachingitsthreshold. TheUPSwillemitanaudiblealarmindicatingthat theremainingbatterycapacityisreachingits threshold. Optionalsetupinformationforuserstorecordthe installationdateofbatterypack.Resetthedata whenreplacingnewbatterypack. IfYesisselected,theUPSwillperformaSelfTest everytimeonstartup.
SelecttheamountoftimethattheUPSwillperform SelfTestperiodicallyafterstartup.
SettheDateandTimeforuseindata/eventlogs.
SelectYestoresetthevalueofLoadEnergyin StatusMenu.
tablecontinued

LCD OPERATION GUIDE – CONTINUED

tablecontinued

Item IPAccess IPAddress

Default DHCP

Option
DHCP ManualIPSetup

Auto sensing

Autosensing ManualKeyin

SubnetMask

Auto sensing

Autosensing ManualKeyin

Gateway

Auto sensing

FirmwareUpdate
Onlydisplayedin StandbyMode

No

BacktoDefault No

Autosensing ManualKeyin
Yes No Yes No

Description
SelectthewaytoaccesstheIP/SubnetMask/ Gateway.Thisshows”NoWebDevice”whenno RMCARDisinstalled.
ChangetheIPAccesssettingtomanualIPSetup andthenthisitemcanbeadjustedmanually. Thisshows”NoWebDevice”whennoRMCARD isinstalled.
ChangetheIPAccesssettingtomanualIPSetup andthenthisitemcanbeadjustedmanually. Thisshows”NoWebDevice”whennoRMCARD isinstalled.
ChangetheIPAccesssettingtomanualIPSetup andthenthisitemcanbeadjustedmanually. Thisshows”NoWebDevice”whennoRMCARD isinstalled.
SelectYestoupdatethefirmwareofUPSin StandbyMode.
SelectYestorestoretheUPSfactory defaultsettings.

Fault Warning Display and Alarm
ThefollowingtableshowsthefaultandwarningindicationsoftheUPS.Thewarning messagecycleswhentheUPSisstillturnedon.Refertotheerrorcodebelowandtake necessarymeasures.
AftertheUPSshutsdownoristurnedoffmanually,theerrormessagecoulddisappearbutthe eventrecordscanbefoundintheLogMenu.Tosafelycheckthelogs,pressthepowerswitch onceandthenpresstheEscbuttontoenteranotheroperationmode­StandbyMode.Press MenubuttonandgotoLogMenutodoacheck.
Note:WhentheUPSisinStandbyMode,itdoesnothaveoutput.Allindicatorswillnot illuminateandonlythedisplayscreenlightsupwhentheUPSisoperated.ToleavetheStandby Mode,refertoBASICOPERATIONsectiontoturnontheUPS.OryoucandisconnecttheUPS fromtheACpowersource,waitforaminute,andthenUPSwillcompletelybecomeoff.

LCD OPERATION GUIDE – CONTINUED

Display Screen Line 1
UPSFault!

Display Screen Line 2
E01Overcharge:Contact CyberPowerforrepair.

LED Indicator

Alarm

i

Beepsonceevery2seconds*

UPSFault!

E03NoCharge:Contact CyberPowerforrepair.

UPSOff! UPSOff!

E20OutputShort:Connected equipmentmayhaveproblems, removethemandcheck.
E21OutputShort:Connected equipmentmayhaveproblems, removethemandcheck.

Warning!UPSOff!

E22Overload:Unplugatleastone connecteddevice.

i

i

Beepsfor3seconds

i

Beepsfor3seconds

i

Constantalarm*

Warning!

E23OverTemp:Turnofftheunit andcheckventilation.

i

Beepsonceevery2seconds*

Warning!

E24OverTemp:Turnofftheunit andcheckventilation.

i

Beepsonceevery2seconds*

UPSOff!

E25EPO:ChecktheEPO connectorstatus.

Warning!

E27FanFail(FR):Contact CyberPowerforrepair.

i

Warning!

E27FanFail(FL):Contact CyberPowerforrepair.

i

Warning!

E29FanFail(B):Contact CyberPowerforrepair.

i

Warning! Warning! Warning! Warning!

BatteryDisconnected:Check batterywiringandcondition.
BatteryDefect:Checkbattery wiringandcondition.
ServiceBattery:Batteries havereachedrecommended maintenanceperiod.
WiringFault:Checkutilitywiring andground.

(Flashes) (Flashes)

Beepsonceevery2seconds foraperiodof30seconds
Beepsonceevery2seconds foraperiodof30seconds

*Pressanybuttontocancelthealarm.

EPO AND ROO CONFIGURATION
TheEmergencyPowerOff(EPO)portisasafetyfeaturethatcanbeusedtoimmediately shutdowntheUPSandcutoffitspowersupplytoconnectedequipment.Itisnecessaryto manuallypressthepowerswitchontheLCDmoduletorestarttheUPSandreapplypowerto connectedequipment.
TheRemoteOn/Off(ROO)sharesthesameportwithEPOandthosetwofunctionscanbeused atthesametime.ROOisaremotepowercontrolfunctionwhichallowsusersnotonlytopower onbutalsopowerofftheUPSfromaremotelocation.

Installation
1. VerifytheUPSisoffandunplugged.
2. TheEPO/ROOinterfaceisanIEC60950safetyextralowvoltage(SELV)circuit.Follow theappropriatecircuitdiagrambelowtowiretheprovidedEPOcabletoyourEPO/ROO configuration.ConnectisolateddrycontactsanduseONLYlatchingswitch.

EPO
4 1

OPTION 1: USER SUPPLIED NORMALLY OPEN SWITCH (RECOMMENDED)

1

ROO SWITCH

2

3

4

N.O. EPO SWITCH

OPTION 2: USER SUPPLIED NORMALLY CLOSED SWITCH

1

ROO SWITCH

2

N.C. EPO SWITCH

3

4

3-4 JUMPER

3. Afterwiring,makesuretheexternalEPO/ROOswitchisnotactivatedtoenableUPSoutput.
4. PlugtheUPSintoanACoutletandturntheUPSonviapowerswitchontheLCDmodule.
5. ActivatetheexternalEPO/ROOswitchtotestthefunction.CheckthestatuschangeofUPS fromitsLCDmodule.
6. ForEPOuser:DeactivatetheexternalEPOswitchandrestarttheUPSviapowerswitchon theLCDmodel. ForROOuser:PresstheexternalROOswitchagaintorestarttheUPS.

Restriction on ROO
A. ROOcanonlyturnontheUPSwhenutilityisavailable.
B. ROObecomesinactiveiftheUPSisshutdownduetoFault,LowBattery,orEPO;itis necessarytomanuallypressthepowerswitchontheLCDmoduletorestarttheUPSand reapplypowertoconnectedequipment.
C. ROOisactiveonlywhenUPSpowerstatusisthesameasROOcircuit.Iftheyaredifferent, manuallyadjusttheexternalROOswitchtosynchronizecurrentUPSstatus.
Forinstance,theUPSisturnedoffviapowerswitchontheLCDmodule;however,theROO switchstaysin”on”position,whichmeansthecontactisclosed.Usershavetomanually presstheexternalROOswitchto”off”position,makingcontactopen,toreactivatetheROO, verifyingthepowerstatusshownonLCDmoduleandROOswitchisonthesamepage.And thenuserscanpresstheexternalROOswitchagaintoturnontheUPS.
PowerswitchontheLCDmodule,softwareandexternalROOswitchcanallturnon/offtheUPS.

DRY CONTACT
ThisUPSoffersusersthesolutionforUPSstatusmonitoringviatwooutputrelays.Refer toNetworkOperationinthismanual,verifyingtheUPSisconnectedtoacomputerwith PowerPanelBusinesssoftwareinstalledorisequippedwithRMCARD.Followbelowcircuitto wireyourdrycontactportandchooseyourpreferredmonitoringstatusviathoseinterfaces. UPSstatuswhichcanbemonitoredbydrycontactislistedbelow:

UPS Status PowerFailure BatteryLow SummaryAlarm
UPSFail

UPS Conditions
UPSdetectsutilityfailure
Batterycapacityislowerthanthreshold.
UPSexitsalarmsduetoInverterFault,OutputShort,OverTemperature,Overload, BatteryOvercharge,LowBattery,BatteryDisconnected,andBatteryDefect.
UPShasmalfunctionedduetoInverterFault,DCPowerFault,and OverTemperature.

*DefaultsettingsofrelaycontactsarePowerFailureandBatteryLow(NormallyOpen).

Internal Circuit

Relay 1

Battery Low

Common (for relays)

Output Relay Rating

Voltage:30VDCMax

1

Current:3AMax(perrelay)

6

2

7

Relay 2

3

8

Power Failure

Relay Status

UPS Status

4

Pin1shorttoPin5 BatteryLow

9

5

Pin8shorttoPin5 PowerFailure

Example Application
Supply12VDCtotheCommoncontactandconnectLEDstotheDB9portPin1andPin8. WhenUPSdetectsutilityfailureorwhenUPSbatterycapacityislowerthanthreshold,the connectedLEDswillilluminate.

Battery Low 1 6 2

7

12V

3

Power Failure 8

4

Common (for relays)

9 5

BATTERY REPLACEMENT
Readandfollowtheimportantsafetyinstructionsbeforeservicingthebatteries.Visitthe CyberPowerofficialwebsiteatwww.cyberpowersystems.comorcontactyourdealerformore informationonreplacementbatteries.Thebatteryreplacementvideoisavailableonline.Scan theQRcodebelowfordetailedinformation.
CAUTION! RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. Whenreplacingbatteries,replacewiththesamenumberofthefollowingbattery: CyberPowerRB1290X4JforPR2200RT2UCN/PR2200RTXL2UCN.
CAUTION!RiskofEnergyHazard,12V,maximum9Amperehourbattery.(PR2200RT2UCN/ PR2200RTXL2UCN)
CAUTION!Theusedbatteriesareconsideredhazardouswasteandmustbedisposedthrough recycling.Mostretailersthatsellleadacidbatteriescollectusedbatteriesforrecycling,as requiredbylocalregulations.Donotdisposeofbatteriesinafire.Thebatteriesmayexplode.
CAUTION!Donotopenormutilatebatteries.Releasedmaterialisharmfultotheskinandeyes. Itmaybetoxic.
CAUTION!DonotreplacebatterieswhiletheUPSisinbatterymode.
CAUTION!Whenthebatterypackisdisconnected,theloadsconnectedtotheUPSarenot protectedfrompowerfailure.
CAUTION!Donotuseadamagedordeformedbatterypack.
Take the following precautions before replacing the battery: 1. Removewatches,rings,orothermetalobjects. 2. Usetoolswithinsulatedhandles. 3. Wearrubberglovesandboots. 4. Donotlaytoolsormetalpartsontopofbatteries. 5. Determineifbatteryisinadvertentlygrounded.Ifinadvertentlygrounded,removesource
fromground.CONTACTWITHANYPARTOFAGROUNDEDBATTERYCANRESULTIN ELECTRICALSHOCK.Thelikelihoodofsuchshockcanbereducedifsuchgroundsare removedduringinstallationandmaintenance(applicabletoequipmentandremotebattery suppliesnothavingagroundedsupplycircuit).
Battery Replacement Procedure

1

2

3

1. Removefaceplateandunscrewthethumbscrewsonbatterycoverandthenopenthebattery cover.Note:Thumbscrewsaredesignedfixedonthebatterycover,donotremovethemfrom themetalcover.
2. Disconnectthebatteryandbatterymanagementmoduleconnector.
3. Insertthenewbatterypack.Assembletheconnectors,thumbscrewsandfaceplate. Rechargetheunitforatleast12hourstoensuretheUPSperformsexpectedruntime.
Reminder:BatteryChangeDateisoptionalsetupinformationforuserstorecordtheinstallation dateofbatterypack.ItcanbeadjustedthroughLCDmoduleinAdvancedSetupMenuor throughsoftware.

TECHNICAL SPECIFICATIONS

GENERAL

MODEL

UPSTopology

EnergySaving

INPUT

NominalInputVoltage

InputFrequency

PlugType

PowerCordLength

OUTPUT

PowerCapacity

OnBatteryOutputVoltage

OnBatteryOutputFrequency

OnBatteryOutputWaveform

BATTERY

BatteryType

ReplaceableBatteryPack

TypicalRechargeTime

PHYSICAL
Dimensions (Width/Height/Depth)
Weight(lb/kg)

SAFETY

ConformanceApprovals

Environmental

PR2200RT2UCN

PR2200RTXL2UCN

LineInteractive GreenPowerUPSBypassTechnology

100/110/120V 5060Hz+/3Hz(Autosensing)
NEMAL530P 10ft.(3.0m)

2200VA/2200W 100/110/120VAC+/5%
50Hz60Hz+/1% SineWave

SealedMaintenanceFreeLeadAcidBattery 1xRB1290X4J
3hoursto90%fromtotaldischargeunder100%load

2Urack/17.1×3.4×16.2in 434×86.5x411mm
59.8lbs/27.12kg

2Urack/17.1×3.4×19.7in 434x86x500mm
79.6lbs/36.11kg

UL1778/CSAC22.2No107.3/FCCClassA/VCCIClassA/ENERGYSTAR RoHSCompliant

TROUBLESHOOTING

Problem
UPSdoesnotprovide powertoequipment.
UPSdoesnotperform expectedruntime.

Possible Cause

Solution

Circuitbreakerhastrippeddueto anoverload.

TurntheUPSoffandunplugatleastone pieceofequipment.Wait10seconds, resetthecircuitbreaker,andthenturn theUPSon.

Batteriesaredischarged.

RechargetheUPSforatleast3hours.

UPShasbeendamagedbyasurge ContactCyberPowerSystemsat:

orspike.

cyberpowersystems.comforrepair.

Noncriticaloutletshaveturnedoff automaticallyduetoanoverloadin batterymode.

NCLoutletswillbeturnedon automaticallyasutilityisrestored.To avoidrecurring,check”OffonOverload” settinginOutletControlMenuand disablethefunction.

Batteriesarenotfullycharged. Batteriesaredegraded.

Rechargethebatteriesbyleavingthe UPSpluggedin.
ContactCyberPowerSystemsat: cyberpowersystems.comforreplacement batteries.

UPSdoesnotrecognizethe correctquantityofExtended BatteryModules.

AdjustthesettingofExtendedBattery ModuleQuantityonyourUPStocorrect numbersviaLCDmodule,PowerPanel BusinesssoftwareorRMCARDinterface (ifinstalled).

UPSisnotconnectedtoan ACoutlet.

Theunitmustbeconnectedtoa 100­120Vor100­125Voutlet.(See TECHNICALSPECIFICATIONSsection)

Batteriesarewornout.

ContactCyberPowerSystemsat: cyberpowersystems.comfor replacementbatteries.

UPScannotbeturnedon. Mechanicalproblem

ContactCyberPowerSystemsat: cyberpowersystems.comforrepair.

Partofhardrebootprocesshas beenperformed.

Longpressofthepowerswitchto forciblyshutdowntheUPSwhenit freezes.WhentheUPSisoff,longpress ofthepowerswitchtolightupthe displayscreenforafewseconds. ThisdoesnotturnontheUPS.Referto BASICOPERATIONsectiontocorrectly turnontheUPS.

TheUSB/serialcableisnot connected.

ConnectthecabletoyourUPSand computer.Usethecablethatcamewith theunitifyourowncommunication cabledoesnotwork.

PowerPanelBusiness isinactive.

TheserialcableorUSBcable isconnectedtothewrongor defectedport.

Tryanotherportonthecomputer.

Shutdownthecomputerandturnthe UPSisnotprovidingbatterypower. UPSoff.Wait10secondsandturnthe
UPSbackontoresettheunit.

TROUBLESHOOTING – CONTINUED

Problem

Possible Cause

“ServiceBattery”message appearsondisplayscreen.

TheBatteryReplacementDate hasreachedtherecommended maintenanceperiod.

“Fault”or”Error” messageisappearing ondisplayscreen.

Aninternalmalfunctionmay haveoccurred.

Solution
Performaruntimeestimationvia PowerPanelBusinesssoftwareto verifybatterycapacityissufficientand acceptable.
Ifbatterieshavebeenrecentlyreplaced, resettheBatteryReplacementDate usingPowerPanelBusinesssoftwareor RMCARDinterface;youcanalsoreset theBatteryChangeDateinAdvanced SetupMenuthroughLCDmodule.
PleaserefertoFaultWarningDisplayand AlarmintheLCDOPERATIONGUIDE section.Ifthefaultpersists,takenote andcontactCyberPowerforrepair.

Thesizeofgeneratorisnot suitableforcurrentload.

Thecontinuousgeneratorcapacityrating mustbeatleasttwicethetotalload, includingtheUPSandallotherdevices attachedtothegenerator;otherwise,the generatormaynotbeabletoholdthe voltageandfrequencywithintheinput toleranceoftheUPS,causingtheUPS switchingfromutilitytobatterymode backandforth.Reducetheconnected loadorupgradethegenerator.

UPScannotworkproperly whileattachedtoa generator.
TheUPSistoosensitiveto powerevents.

Thequalityandstabilityofthegenerator powermaynotbeasgoodasyour localutility.Thefrequentblackouts andwaveformdistortionscouldlead theUPStoconsidertheinputpower inappropriateandwillswitchtobattery modetoprovidecleanpowerto attachedload,drainingthebattery.Refer toLCDOPERATIONGUIDEsectionto desensitizetheUPSviaLCDmodule, PowerPanelBusinesssoftwareor RMCARDinterface(ifinstalled).
Note:Loweringthesensitivitysetting makestheUPStoleratemorepower events,butitalsoincreasesthetransfer timeoftheUPS.Somesensitive equipmentcannotacceptextended transfertime.Testtocheckifthereisa loaddropwhentheUPSisswitchingto batterymode.

Additionaltroubleshootinginformationcanbefoundat”Support”atwww.CyberPowerSystems.com

CYBERPOWER GREENPOWER UPSTM TECHNOLOGY

Advanced Energy-Saving Patented Bypass Technology

CyberPower’spatentedGreenPowerUPSTMwithBypassTechnologyreducesUPSenergy

costsbyupto75%comparedtoconventionalUPSmodels.Evenwhenutilitypower

isnormal,conventionalUPSmodelsconstantlypasspowerthroughatransformer.

Bycontrast,undernormalconditionstheadvancedcircuitryofaGreenPowerUPSTM

bypassesthetransformer.Asaresult,thepowerefficiencyissignificantlyincreased whiledecreasingwasteheat,usinglessenergy,andreducingenergycosts.Whenan

GREENPOWER UPSTM
EnergySavingTechnology

abnormalpowerconditionoccurs,theGreenPowerUPSTMautomaticallyrunspower

throughitstransformertoregulatevoltageandprovide”safe”power.Sinceutilitypower

isnormalover88%ofthetime,theGreenPowerUPSTMoperatesprimarilyinitsefficientbypassmode.The

GreenPowerUPSTMisalsomanufacturedinaccordancewiththeRestrictiononHazardousSubstances(RoHS)

directivemakingitoneofthemostenvironmentallyfriendlyonthemarkettoday.

FCC COMPLIANCE STATEMENT
Thisdevicecomplieswithpart15oftheFCCrules.Operationissubjecttothefollowingtwo conditions:(1)thisdevicemaynotcauseharmfulinterference,and(2)thisdevicemustaccept anyinterferencereceived,includinginterferencethatmaycauseundesiredoperation.
Note:ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassAdigital device,pursuanttopart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonable protectionagainstharmfulinterferencewhentheequipmentisoperatedinacommercialenvironment. Thisequipmentgenerates,uses,andcanradiateradiofrequencyenergyand,ifnotinstalledandusedin accordancewiththeinstructionmanual,maycauseharmfulinterferencetoradiocommunications.Operation ofthisequipmentinaresidentialareaislikelytocauseharmfulinterferenceinwhichcasetheuserwillbe requiredtocorrecttheinterferenceathisownexpense.
Important:Changesormodificationsnotexpresslyapprovedbythepartyresponsibleforcompliancecould voidtheuser’sauthoritytooperatetheequipment.
Canadian Compliance Statement – CANICES3(A)/NMB3(A)
VCCI Compliance StatementVCCIA

LIMITED WARRANTY AND CONNECTED EQUIPMENT GUARANTEE
Pleasevisitwww.CyberPowerSystems.comforacopyoftheLimitedWarrantyandConnected EquipmentGuarantee.
Where Can I Get More Information?
TheapplicationoftheUnitedNationsConventionofContractsfortheInternationalSaleofGoodsisexpressly excluded.CyberPoweristhewarrantorunderthisLimitedWarranty.Forfurtherinformationpleasefeelfreeto contactCyberPowerat:CyberPowerSystems(USA),Inc.424112thAveE.,STE400,Shakopee,MN55379; callusat(877) 297-6937;orsubmitawebticketonlineatcyberpowersystems.com/support.
Disposal
CyberPowerSystems(USA),Inc.encouragesenvironmentallysoundmethodsfordisposal andrecyclingofitsUPSproducts.Pleasedisposeand/orrecycleyourUPSandbatteriesin accordancetothelocalregulationsofyourstate.
TheWasteElectricalandElectronicEquipment(WEEE)Directiveaimstocontributeto sustainableproductionandconsumptionbycontributingtotheefficientuseofresourcesandtheretrievalof secondaryrawmaterialsthroughreuse,recycling,andotherformsofrecovery.Thesymbolonthisproduct and/oritspackagingindicatesthattheproductmustbedisposedofseparatelyfromordinaryhousehold wastesatitsendoflife.ContactyourrelatedWEEEmanagementauthority,localoffice,oryourhousehold wastedisposalserviceaboutinformationontherecyclingdropoffsite.
Thisproductcontainsnonspillableleadacidbatteries.Theusedbatteriesareconsideredhazardouswaste andmustbedisposedthroughrecycling.Donotdisposeofusedbatterieswithyourordinaryhousehold wastes.Disposeofthebatteriesaccordingtolocalregulations.Note:Mostretailersthatsellleadacid batteriescollectusedbatteriesforrecycling,asrequiredbylocalregulations.

WARNING:ThisproductcanexposeyoutochemicalsincludingbisphenolA(BPA)andstyrene,whichisknowntothe StateofCaliforniatocausereproductiveharmandcancer.Formoreinformation,gotowww.P65Warnings.ca.gov.
©2024CyberPowerSystems(USA),Inc.PowerPanel®PersonalisatrademarkofCyberPowerSystems(USA)Inc. Allrightsreserved.Allothertrademarksarethepropertyoftheirrespectiveowners.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>