CORDIVARI 4000 Ventana High Wall

Specifications

Ventana® HIGH WALL is a high-performance, high-efficiency fan coil unit for high wall installation, designed for operation with heat pump systems.
The unit can operate in heating and cooling mode. Brushless DC inverter motors. Maximum flexibility of configuration, connectivity, and control.

Fixing kit:
The Fan coil is protected with a recyclable cardboard box. Instructions for use and maintenance provided with the product. Always refer to the included installation notice.

Packaging:
The fan coil unit is protected by recyclable carton box.

Painting process:
Painted with ecological epoxy powders (Certificate DIN 55900-1,-2).

Cleaning:
Filters are easily removable, washable or replaceable.

Electrical specifications: Class 1.

Colors:
Standard color White RAL 9016-R02.

DIMENSION

Version

| 4000| 6000| 8000
---|---|---|---
STANDARD **** Art. nr. WHITE RAL 9016-R02|

3584776100020

|

3584776100021

|

3584776100022

CSP

with wall mounted stand-alone      Art. nr. WHITE RAL 9016-R02

|

3584776100042

|

3584776100043

|

3584776100044

Article numbers in the table refer to models in color WHITE RAL 9016-R02.

Dimensional data

Dimensional data|
---|---

MODEL

| Width

L [mm]

| Height

H [mm]

| Depth

P [mm]

4000| 915| 425| 130
6000| 1110| 425| 130
8000| 1300| 425| 130

TECHNICAL SHEET

MODEL

| VENTANA® HIGH WALL
---|---
4000 6000                               8000
Total output in heating mode SUPERMAX (1)| [W]| 1710| 2290| 3050
---|---|---|---|---
Water flow rate (1)| [l/h]| 274| 389| 538
Water pressure drop (1)| [kPa]| 17,4| 5,6| 15,8
Total output in cooling mode SUPERMAX (2)| [W]| 1450| 2100| 2900
Sensible output in cooling mode SUPERMAX (2)| [W]| 1050| 1700| 2350
Water flow rate (2)| [l/h]| 245| 330| 470
Water pressure drop (2)| [kPa]| 7,5| 3,1| 11

Total output in heating mode MAXIMUM (3)

|

[W]|

1450

|

2110

|

2810

Water flow rate (3)| [l/h]| 253| 367| 490
Water pressure drop (3)| [kPa]| 14,7| 4,2| 14,2
Total output in cooling mode MAXIMUM (4)| [W]| 1200| 1700| 2450
Sensible output in cooling mode MAXIMUM (4)| [W]| 890| 1480| 2250
Water flow rate (4)| [l/h]| 206| 292| 420
Water pressure drop (4)| [kPa]| 7| 2,5| 10

SUPERMAX SPEED SPECIFICATIONS

|  |  |  |
Sound pressure| [dB(A)]| 57| 58| 59
Maximum electrical power consumption| [W]| 20| 24| 27
Maximum air flow| [m3/h]| 370| 492| 592

MAXIMUM SPEED SPECIFICATIONS

|  |  |  |
Sound pressure| [dB(A)]| 54| 55| 56
Maximum electrical power consumption| [W]| 11| 14| 17
Maximum air flow| [m3/h]| 315| 450| 540

ELECTRICAL SPECIFICATIONS

|  |  |  |
Tension|  |  | 230 [V] AC 50 [Hz]|
Electrical Class|  |  | Class I|
Connectivity|  |  | Wi-Fi (optional)|
Other|  |  | 3 Way Bypass valve setting (optional)|

HYDRAULIC SPECIFICATIONS

|  |  |  |
Ambient operating temperature|  |  | From 5 [°C] to 35 [°C] – 60% RH|
Water inlet temperature|  |  | From 5 [°C] to 75 [°C]|
Working pressure|  |  | From 1 [bar] to 6 [bar]|
Hydraulic connections|  |  | G1/2” female|

  1. According to EN 1397: Water IN 45 / OUT 40 [°C], Air 20 [°C], Wet-bulb 15 [°C], Supermax speed
  2. According to EN 1397: Water IN 7 / OUT 12 [°C], Aria 27 [°C], Wet-bulb 19 [°C], Supermax speed
  3. According to EN 1397: Water IN 45 / OUT 40 [°C], Air 20 [°C], Wet-bulb 15 [°C], Maximum speed
  4. According to EN 1397: Water IN 7 / OUT 12 [°C], Aria 27 [°C], Wet-bulb 19 [°C], Maximum speed
    PLEASE NOTE: Supermax speed is not set by default but it can activated by managing the electronic board deepswitch