MEANWELL DR-UPS40 Power Supply Owner’s Manual
- August 22, 2024
- MeanWell
Table of Contents
MEANWELL DR-UPS40 Power Supply
Specifications
- Model: DR-UPS40
- DC Input / DC Voltage (Typ.): 24 ~ 29V
- DC Bus Rated Current: 40A
- Battery Input / Output:
- Voltage Range (Typ.): 21 ~ 29V
- Current Range: 0 ~ 40A
- Charge Current (Typ.): 2A
- External Battery (Typ.): 4 / 7 / 12AH / 24V
- Relay Contact Rating (Max.): 30VDC, 1A
- Dimensions: 55.5125.2100mm (WHD)
- Weight: 0.55Kg
Product Usage Instructions
Installation
- Ensure the DIN Rail UPS system is powered off.
- Mount the DR-UPS40 module on DIN Rail TS35/7.5 or TS35/15 securely.
- Connect the DC input within the specified voltage range (24-29V).
- Connect the external battery as per the recommended configurations.
Operation
- The LED indicators will show the status of DC BUS OK, Battery Fail, and Battery Discharge.
- Monitor the relay contact signals for any warnings or alerts related to the battery.
- Utilize the built-in battery test function periodically to ensure proper battery operation.
Maintenance
- Regularly check the battery polarity protection to prevent any damage.
- Clean the module and ensure proper ventilation for cooling by free air convection.
FAQ
- Q: How often should I perform the battery test function?
- A: It is recommended to perform the battery test function at least once every month to ensure battery health.
- Q: What should I do if the Battery Fail LED is lit?
- A: If the Battery Fail LED is lit, check the external battery connection and voltage levels to troubleshoot the issue.
GTIN CODE
- MW Search: https://www.meanwell.com/serviceGTIN.aspx
Features
- Battery controller for DIN Rail UPS system
- Parallel connection to DC BUS
- Suitable for 24V system up to 40A
- Installed on DIN Rail TS35 / 7.5 or 15
- Built-in battery test function
- Battery polarity protection
- Relay contact signal output and LED indicator for DC BUS OK Battery Fail, and Battery Discharge
- Cooling by free air convection
- 3 years warranty
SPECIFICATION
MODEL | DR-UPS40 |
---|---|
DC INPUT / DC BUS | DC VOLTAGE (Typ.) Note.5 |
RATED CURRENT | 40A |
BATTERY INPUT / OUTPUT
| VOLTAGE RANGE (Typ.)| 21 ~ 29V
CURRENT RANGE| 0 ~ 40A
CHARGE CURRENT (Typ.) Note.4| 2A
EXTERNAL BATTERY (Typ.)| 4 / 7 / 12AH / 24V
FUNCTION
| RELAY CONTACT RATING (max.)| 30VDC, 1A
DC BUS OK
| Relay contact: Short when DC voltage between 21~29V(±3%), relay contacts
LED(Green) : DC BUS OK : light ; DC BUS fail : dark
BATTERY FAIL Note.2
| Short when the battery voltage falls below 21.9V(±3%) or battery failure is
observed through the battery test function, relay contacts
LED(Red): Battery over-discharge warning or battery broken: light; Battery OK:
dark
BATTERY DISCHARGE
| Relay contact: Short when the battery is in discharge condition, relay
contacts
LED(Yellow):light : Battery discharging ; dark : Battery is not discharging or
discharging current<2.0A
ENVIRONMENT
| WORKING TEMP.| -20 ~ +70℃
WORKING HUMIDITY| 20 ~ 90% RH
STORAGE TEMP., HUMIDITY| -20 ~ +85℃, 10 ~ 95% RH
VIBRATION| Component : 10 ~ 500Hz, 2G 10min./1cycle, 60min. each X, Y,
and Z axes; Mounting: Compliance to IEC600068-2-6
SAFETY & EMC
(Note 3)
| WITHSTAND VOLTAGE| Terminal-Chassis :0.5KVAC, Relay Contacts-Terminal
:0.5KVAC
ISOLATION RESISTANCE| Terminal-Chassis :>100M Ohms / 500VDC / 25℃/ 70%
RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32) Class B, BS
EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, heavy
industry level, criteria A, EAC TP TC 020
OTHERS
| MTBF| 1365.7K hrs min. Telcordia SR-332 (Bellcore); 161.9K hrs
min. MIL-HDBK-217F (25℃)
DIMENSION| 55.5125.2100mm (WHD)
PACKING| 0.55Kg; 20pcs/12Kg/1.49CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at rated
load and 25℃ of ambient temperature.
2. Battery failure will only function in UPS mode with the battery connected. Every 25 seconds, the unit will send out a test signal through the “Battery Fail” relay contact and LED indicator once the battery fails.
3. The power supply is considered a component that will be installed into the final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re- confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
4. Battery charging will be in progress when DC input > battery voltage.
5. DR-UPS40 will be in operation when DC input is applied at the beginning.
6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitudes higher than 2000m(6500ft).
※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Dimension
Mechanical Specification
- Terminal Pin No. Assignment (TB1)
Pin No. | Assignment |
---|---|
1 | BATTERY INPUT + |
2 | BATTERY INPUT – |
3 | DC INPUT – |
4 | DC INPUT + |
- Terminal Pin No. Assignment (TB2)
Pin No. | Assignment |
---|---|
1 | BAT DISC 1 |
2 | BAT DISC 2 |
3 | BAT FAIL 1 |
4 | BAT FAIL 2 |
5 | DC OK 1 |
6 | DC OK 2 |
Block Diagram
Derating Curve
Suggested Application
- Backup connection for AC interruption
- Combine redundancy module (DR-RDN20) to back up AC interruption or failure of PSU