MEANWELL DR-UPS40 Power Supply Owner’s Manual

August 22, 2024
MeanWell

MEANWELL DR-UPS40 Power Supply

MEANWELL-DR-UPS40-Power-Supply-product

Specifications

  • Model: DR-UPS40
  • DC Input / DC Voltage (Typ.): 24 ~ 29V
  • DC Bus Rated Current: 40A
  • Battery Input / Output:
    • Voltage Range (Typ.): 21 ~ 29V
    • Current Range: 0 ~ 40A
    • Charge Current (Typ.): 2A
    • External Battery (Typ.): 4 / 7 / 12AH / 24V
  • Relay Contact Rating (Max.): 30VDC, 1A
  • Dimensions: 55.5125.2100mm (WHD)
  • Weight: 0.55Kg

Product Usage Instructions

Installation

  1. Ensure the DIN Rail UPS system is powered off.
  2. Mount the DR-UPS40 module on DIN Rail TS35/7.5 or TS35/15 securely.
  3. Connect the DC input within the specified voltage range (24-29V).
  4. Connect the external battery as per the recommended configurations.

Operation

  • The LED indicators will show the status of DC BUS OK, Battery Fail, and Battery Discharge.
  • Monitor the relay contact signals for any warnings or alerts related to the battery.
  • Utilize the built-in battery test function periodically to ensure proper battery operation.

Maintenance

  • Regularly check the battery polarity protection to prevent any damage.
  • Clean the module and ensure proper ventilation for cooling by free air convection.

FAQ

  • Q: How often should I perform the battery test function?
  • A: It is recommended to perform the battery test function at least once every month to ensure battery health.
  • Q: What should I do if the Battery Fail LED is lit?
  • A: If the Battery Fail LED is lit, check the external battery connection and voltage levels to troubleshoot the issue.

GTIN CODE

Features

  • Battery controller for DIN Rail UPS system
  • Parallel connection to DC BUS
  • Suitable for 24V system up to 40A
  • Installed on DIN Rail TS35 / 7.5 or 15
  • Built-in battery test function
  • Battery polarity protection
  • Relay contact signal output and LED indicator for DC BUS OK Battery Fail, and Battery Discharge
  • Cooling by free air convection
  • 3 years warranty

SPECIFICATION

MODEL DR-UPS40
DC INPUT / DC BUS DC VOLTAGE (Typ.) Note.5
RATED CURRENT 40A

BATTERY INPUT / OUTPUT

| VOLTAGE RANGE (Typ.)| 21 ~ 29V
CURRENT RANGE| 0 ~ 40A
CHARGE CURRENT (Typ.) Note.4| 2A
EXTERNAL BATTERY (Typ.)| 4 / 7 / 12AH / 24V






FUNCTION

| RELAY CONTACT RATING (max.)| 30VDC, 1A


DC BUS OK

| Relay contact: Short when DC voltage between 21~29V(±3%), relay contacts
LED(Green) : DC BUS OK : light ; DC BUS fail : dark


BATTERY FAIL Note.2

| Short when the battery voltage falls below 21.9V(±3%) or battery failure is observed through the battery test function, relay contacts
LED(Red): Battery over-discharge warning or battery broken: light; Battery OK: dark


BATTERY DISCHARGE

| Relay contact: Short when the battery is in discharge condition, relay contacts
LED(Yellow):light : Battery discharging ; dark : Battery is not discharging or discharging current<2.0A



ENVIRONMENT

| WORKING TEMP.| -20 ~ +70℃
WORKING HUMIDITY| 20 ~ 90% RH
STORAGE TEMP., HUMIDITY| -20 ~ +85℃, 10 ~ 95% RH
VIBRATION| Component : 10 ~ 500Hz, 2G 10min./1cycle, 60min. each X, Y, and Z axes; Mounting: Compliance to IEC600068-2-6


SAFETY & EMC

(Note 3)

| WITHSTAND VOLTAGE| Terminal-Chassis :0.5KVAC, Relay Contacts-Terminal :0.5KVAC
ISOLATION RESISTANCE| Terminal-Chassis :>100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, heavy industry level, criteria A, EAC TP TC 020


OTHERS

| MTBF| 1365.7K hrs min.       Telcordia SR-332 (Bellcore); 161.9K hrs min.       MIL-HDBK-217F (25℃)
DIMENSION| 55.5125.2100mm (WHD)
PACKING| 0.55Kg; 20pcs/12Kg/1.49CUFT
NOTE| 1.  All parameters NOT specially mentioned are measured at rated load and 25℃ of ambient temperature.

2.  Battery failure will only function in UPS mode with the battery connected. Every 25 seconds, the unit will send out a test signal through the “Battery Fail” relay contact and LED indicator once the battery fails.

3.  The power supply is considered a component that will be installed into the final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re- confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”

(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )

4.  Battery charging will be in progress when DC input > battery voltage.

5.  DR-UPS40 will be in operation when DC input is applied at the beginning.

6.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitudes higher than 2000m(6500ft).

※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Dimension

Mechanical Specification

MEANWELL-DR-UPS40-Power-Supply-fig-3

  • Terminal Pin No. Assignment (TB1)
Pin No. Assignment
1 BATTERY INPUT +
2 BATTERY INPUT –
3 DC INPUT –
4 DC INPUT +
  • Terminal Pin No. Assignment (TB2)
Pin No. Assignment
1 BAT DISC 1
2 BAT DISC 2
3 BAT FAIL 1
4 BAT FAIL 2
5 DC OK 1
6 DC OK 2

Block Diagram

MEANWELL-DR-UPS40-Power-Supply-fig-4

Derating Curve

MEANWELL-DR-UPS40-Power-Supply-fig-5

Suggested Application

  1. Backup connection for AC interruptionMEANWELL-DR-UPS40-Power-Supply-fig-6
  2. Combine redundancy module (DR-RDN20) to back up AC interruption or failure of PSU

MEANWELL-DR-UPS40-Power-Supply-fig-7

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>