MGC SPPS-204 Series Strobe Wall Speaker Instruction Manual

August 22, 2024
MGC

MGC SPPS-204 Series Strobe Wall Speaker

Specifications:

  • Operating temperature  0⁰C to 49⁰C (32⁰F to 122⁰F)
  • Humidity range 0% to 93%
  • Strobe flash rate 1 Hz (1 flash per sec.)*
  • Nominal strobe voltage  Regulated 24VDC/VFWR
  • Operating voltage range 16-33 VDC/VFWR
  • Nominal speaker voltage 25V or 70.7Vrms
  • Speaker Size 4”
  • Power Setting  ¼, ½, 1, 2 W
  • Speaker Frequency range 400 -4000 Hz
  • Terminal wire gauge 12-22 AWG

Product Usage Instructions

Setting the Candela:

  1. Pull out the candela selector from the device.
  2. Re-insert the selector tab into the notch labeled with the desired candela setting.
  3. Select the candela setting before installing the device on the mounting plate.

Setting the Dip Switches:

  1. Refer to Figure 3 for the location of the dip switches.
  2. Switch 1:
    • OFF: Synchronized input*
    • ON: Regulated 24VDC/ FWR (Non-sync.)
  3. Note: Use SYNC when flash synchronization is required, use NON-SYNC when synchronization is not needed.

Wiring:

  1. Refer to Figure 4 for wiring taps for models with strobe feature.
  2. Selectable Speaker Power (Watts)
  3. Connect speaker line between C and desired wire gauge.
  4. This device should be installed as per applicable requirements of the authorities having jurisdiction.

Frequently Asked Questions (FAQ):

  1. Q: How do I set the candela for the SPPS series?
    A: To set the candela, pull out the selector tab, re-insert it into the desired setting notch, and ensure to select before mounting.

  2. Q: When should I use the SYNC and NON-SYNC settings on the dip switch?
    A: Use SYNC when flash synchronization is needed, and use NON-SYNC when synchronization is not required.

  3. Q: What is the default setting for DIP switch 1?
    A: The default setting for DIP switch 1 is OFF for synchronized input.

  4. Q: How should I wire the device?
    A: Refer to the wiring taps in Figure 4 and connect the speaker line between C and the desired wire gauge. Follow applicable regulations during installation.

CAUTION / ATTENTION
DO NOT PAINT OR ALTER FACTORY APPLIED FINISH IN ANY WAY

ABOUT THIS MANUAL
This manual is included as a quick reference for installation. For further information on the use of this device with a FACP, please refer to the panel’s manual.
Note: This manual should be left with the owner/operator of this equipment.

SPEAKER/SPEAKER STROBE DESCRIPTION

The SPPS-204 speaker-strobe is designed to meet UL1480/ULC S541 requirements for speakers and UL1638 /ULC S526, UL 1638A/CSA C22.2 No.205 requirements for visual notification appliances. The SPP-204 speaker is designed to meet UL1480/ULC S541 requirements for speakers.

*Note: For FWR signaling use an MGC panel.

SETTING THE CANDELA (SPPS series only)

The candela can be set to 15, 30, 75, 110, 185, 15/75 for SPPS-204-25 and SPPS-204-70 models.
Note: 185cd setting is for General Signaling only.
The factory default setting is 15 for SPPS-204-25/70.

  1. Pull out the candela selector from the device.
  2. Re-insert the selector tab into the notch that is labeled with the desired candela setting (when removing or inserting the candela selector, ensure to keep it straight).

Note: Select the candela setting prior to installing the device in the mounting plate.

SETTING THE DIP SWITCHES

Table 2: DIP SWITCH

DIP OFF ON
Switch 1 Input* Synchronized Regulated 24VDC/ FWR (Non-sync.)

*Note: Use “SYNC” when flash synchronization is required, either through a sync module or built-in synchronization on the control unit.
Use “NON-SYNC” when the appliances do not need to be synchronized.

  • DIP switch 1 default setting is OFF, synchronized.
  • DIP switch 2 is not used. By default it is OFF.

WIRING

Note: This device should be installed as per applicable requirements of the authorities having jurisdiction.
Use the information in this document to determine the total power or current of the devices. The total power or current of the devices must not exceed the output rating of the panel. Refer to the FACP installation guide for the wire size required according to the loop length and devices power usage. For maximum strobe operating current, please refer to Table 5.

*Note: When using with MGC panel or sync module, use MP-300 (3.9K).
Note: Wiring must be in accordance with CSA C22.1, Canadian Electrical Code, Part I, Safety Standard for Electrical Installations section 32 and NFPA 70.

CAUTION
FOR ALL TERMINAL TAPS USED FOR SYSTEM SUPERVISION, DO NOT USE LOOPED WIRE UNDER TERMINALS. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.

CAUTION
DO NOT LOOP SIGNAL CIRCUIT FIELD WIRES AROUND TERMINALS. ELECTRICAL SUPERVISION REQUIRES WIRE RUN TO BE BROKEN AT EACH END.
Note: When using with MGC panel or sync module, use MP-300 (3.9K).

Correct: Wire run is broken
Wrong: Wire is looped around terminal

MOUNTING

MGC recommends spacing speaker strobe appliances in compliance with CAN/ULC S524 and NFPA72.

  1. Attach the mounting plate to the electrical box with the 2 included mounting screws.
  2. Insert the device to the mounting plate with 2 screws.
  3. Attach the top cover with the included securing screw and snap the nameplate over the securing screw.

Note: Select the candela setting prior to installing the device in the mounting plate.

AUDIBLE RATINGS

Table 3: SOUND PRESSURE LEVEL OUTPUT

SPPS-204 SERIES

**WATT Tap| UL Reverberant (dBA@10ft)| ULC Anechoic (dBA@3m)
70| 25| 70| 25
2| 88.4| 88.4| 86.5| 85.8
1| 86.1| 86.3| 83.9| 83.5
1/2| 83.4| 83.6| 81.1| 80.7
1/4| 80.1| 80.3| 77.9| 77.5
SPP-204 SERIES
****
WATT Tap| UL Reverberant (dBA@10ft)| ULC Anechoic (dBA@3m)**
70| 25| 70| 25
2| 88.5| 88.5| 85.5| 86.5
1| 86.2| 86.5| 81.9| 83.1
1/2| 83.4| 83.7| 79.2| 80.3
1/4| 80.2| 80.5| 76.0| 76.9

Table 4: DIRECTIONAL SOUND CHARACTERISTICS
(Representative of both horizontal and vertical Axis)

SPPS-204 SERIES

ANGLE| dBA
+76°, -75°| -3
+–°, -87°| -6
±90°| -6.3
SPP-204 SERIES
ANGLE|
±80°| -3
±–°| -6
±90°| -5.3

STROBE RATINGS

Table 5: STROBE OPERATING RMS CURRENTS (mA)

Candela Regulated 24VDC Regulated 24VFWR
15 33 27
30 55 53
75 98 93
110 193 177
185 268 241
15/75 102 98

Table 6: LIGHT DISPERSION

**Degrees** % of Candela Rating
Horizontal Dispersion Vertical Dispersion, Wall to Floor
± 0 155
± 5 147
± 10 145
± 15 140
± 20 135
± 25 131
± 30 124
± 35 116
± 40 105
± 45 99
± 50 95
± 55 92
± 60 88
± 65 84
± 70 78
± 75 82
± 80 86
± 85 80
± 90 53
Compound ± 45 39

Note: The values in Table 6 are shown as percentages of the rated light output at any candela setting.

Model Numbers

  • SPPS-204-25 Wall mounted speaker strobe 25V white
  • SPPS-204-70 Wall mounted speaker strobe 70V white
  • SPPS-204-25R Wall mounted speaker strobe 25V red
  • SPPS-204-70R Wall mounted speaker strobe 70V red
  • SPP-204-25 Wall mounted speaker 25V white
  • SPP-204-70 Wall mounted speaker 70V white
  • SPP-204-25R Wall mounted speaker 25V red
  • SPP-204-70R Wall mounted speaker 70V red

Accessories
MP-300 End of line resistor 3.9k Ohm

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)