LEVITON ACxxx-Dxx Smart Ceiling Mount 0-10V Dimming Room Controllers Owner’s Manual

August 7, 2024
Leviton

LEVITON ACC-Dxx Smart Ceiling Mount 0-10V Dimming Room Controllers

Specifications

  • Product Name: ACxxx-Dxx Smart Ceiling Mount 0-10V Dimming Room Controllers (SRC)
  • Product Type: Self-Contained Lighting Control Solution
  • Features: PIR-Only Room Controller, Multi-Tech Room Controller, Light Pipe, Status Screen, Daylighting Screen
  • Manufacturer: Leviton Manufacturing Co., Inc.
  • Model Number: ACxxx-Dxx

Product Usage Instructions

Installation
Follow the provided placement and wiring diagrams to install the Smart Ceiling Mount Room Controller (SRC) correctly.

Configuration
Use the Smart Sensor App on your iOS or Android device for easy configuration of the room controller. The app allows for the customization of occupancy sensing, dimming, daylight harvesting, and other advanced features.

Room Configuration
Configure the sensor based on the space usage and energy code requirements. Use the Smart Sensor App for all configuration tasks.

Manual Control
Connect Low Voltage Keypads or Wireless Switches for manual control of lighting zones. Adjust settings to reduce false triggers and emergencies.

Expansion
Expand coverage by connecting additional Smart Ceiling Mount Sensors wirelessly. Adjust photocell settings for specified lighting designs.

Dimming and Daylighting
Utilize 0-10V dimming zones and daylight harvesting features for energy- efficient lighting control. Align daylight harvesting zones with natural light sources for optimal performance.

Easy-to-Install Self-Contained Lighting Control Solution

Description

  • The Leviton exclusive Smart Ceiling Mount Room Controller (SRC) offers high-performance, code-compliant, advanced room configuration in one easy-to-install device. Installers can download the Smart Sensor App for quick-and-easy room configuration with any iOS or Android device.
  • The SRC’s features meet advanced design requirements for standalone occupancy/vacancy sensing, dimming, and daylight harvesting applications, offering easy configuration and operational testing for one or two 0-10V dimming zones, options for one or two daylight harvesting zones, partial-ON, partial-OFF, area control, demand response, plug load or receptacle control, and UL924 emergency lighting.

Easy Room Configuration
SRC allows you to configure the sensor based on how the space is used and to meet energy code requirements. All of the configuration is done using the Smart Sensor App. The Leviton Smart Sensor App is compatible with both Android and iOS smartphones or tablets. The app is easy to use with simple, intuitive on-screen menu options.

  • Automatic Daylight Harvesting Calibration (AutoCal)
  • Passive infrared (PIR) and ultrasonic (U/S) sensor sensitivity adjustments to reduce false ONs and false OFFs
  • Ability to wirelessly network with other SRC and Smart Ceiling Mount Sensors to expand FOV coverage
  • Define inputs as manual control, demand response, or emergency lighting
  • PLVSW Low Voltage Keypads and SBK00 Wireless Switch and Dimmer can be used in manual-ON applications

Features

  • Can be used to comply with IECC, ASHRAE 90.1. and 2022 Title 24, Part 6 requirements:
  • Occupancy/vacancy sensing
  • 0-10V dimming
  • Daylight harvesting
  • Partial-ON, partial-OFF
  • Demand response
  • Plug load or receptacle control
  • Available in 450 to 2,000 square foot field-of-view units
  • All configuration is done using the Smart Sensor App
  • For larger spaces, up to five Smart Ceiling Mount Room Controllers and Smart Ceiling Mount Sensors can be connected wirelessly to expand the FOV up to 10,000 sq ft
  • Passive infrared (PIR) and multi-tech (PIR + ultrasonic) models avare ailable
  • Manual area control available for 3-way/multi-way applications with the PLVSW Low Voltage Keypads or SBK00 Wireless Switch and Dimmer (must all be the same style)
  • Manual control for independent dimming zones (dim primary and secondary daylighting zones up and down independently)
  • For dual relay models (ACY15-DIW and ACY20-DMW), two keypads can be connected for manual control of each relay/lighting zone
  • UL924 listed for emergency lighting:
  • Can be connected to BMS (Building Management System) or any contact closure to force the lights ffullyON in case of emergency
  • AutoCal feature—Digital Daylighting Level automatically calibrates photocell to specified lighting design
  • Simplified daylight harvesting control of primary and secondary daylighting zones with full range 0-10V dimming
  • PThe primaryzone dimmed up and down from photocell
  • SThe secondaryzone dimmed up and down with offset from the primary zone
  • Two light pipes are included for both open (angled) and closed-loop (flat and angled) daylight harvesting
  • The angled light pipe provides directional fine tuning and alignment to natural light source for closed loop applications
  • Includes two interchangeable lenses for 8-12’ mounting heights and 13-20’ mounting heights as well as aisleway masks.
  • Ladderless Commissioning™ and programming through Bluetooth-enabled iOS or Android smart devices
  • Visual RGB LED indicator for status and troubleshooting
  • Scheduling:
  • Change level, operating mode, daylighting mode (based on day of week and/or time of day)
  • Easily test room configuration using a smart device as a calibration, measurement, and testing tool
  • Connect an OPP20 Power Pack to a two-circuit room controller for a plug load control solution
  • Industry-exclusive H.I.S. (High Inrush Stability) technology
  • Tested to 1.2 million switching cycles under standard loads
  • Zero-crossing circuitry for extended life of the relay
  • Latching relay provides dependability and robust performance for all load types
  • Industry-exclusive “fail safe” circuitry: in the event of product failure, the return-to-close feature causes the relay to default ON which eliminates life safety concerns

Placement Diagrams

Open Loop Mode

  • Angled light pipe
  • Mounted within 4 feet of window

Closed Loop Mode

  • Flat light pipe
  • Mounted 6-8 feet from the window or within the primary daylighting zone
  • Mounted above the work surface

Closed Loop Mode

  • Angled light pipe is angled toward the work surface
  • Mounted 12 feet from window
  • Mounted in a location optimized to prevent false occupancy triggers

App Features

Download the Smart Sensor App to an iOS or Android smart device and pair it to the SRC using Bluetooth technology.

  • Create custom templates for quick multi-room replication of room controller settings
  • Select between auto-ON/auto-OFF and manual-ON/auto-OFF
  • Enable/disable partial-ON and partial-OFF and set the partial-ON and partial-OFF levels
  • Set occupancy sensor time-out
  • Set a secondary timer for partial-OFF to full-OFF state
  • Enable/disable receptacle/HVAC control for secondary relay
  • Initiate field-of-view walk test
  • Select sensing technology for either PIR, U/S, or multi-tech (PIR and U/S)
  • Set PIR or U/S sensitivity independently
  • Monitor the status of all inputs
  • Integrated occupancy sensor(s)
  • Integrated photocell
  • Local wall keypad
  • Plug load
  • Emergency UL924
  • Demand response
  • Enable 24-hour automatic daylight harvesting calibration
  • Set the offset of the secondary daylighting zone based on the primary daylighting zone.
  • Daylight harvesting adjustments: open loop, closed loop, increase/decrease DDL, fade rate, dim to min, dim to OFF
  • Manually adjust the DDL set point to fine-tune for room type after auto-configuration
  • Over-the-Air (OTA) updates: allows user to update SRC firmware in the field via the App
  • Reset to factory defaults

Wiring Diagrams

Product Data ACxxx-Dxx

Field of View Diagrams

Application Diagram

Classroom

Leviton Manufacturing Co., Inc. Lighting & Controls
10385 SW Avery Street, Tualatin, OR 97062 tel 800-736-6682 tech line (6:00 AM-4:00 PM PT Mon-Fri) 800-959-6004 ©2024 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.

Installation

  • Easy installation into junction boxes with Leviton-exclusive screw guides, coasters, and terminal blocks
  • The front cover snaps on and off for ease of installation
  • Sensors conveniently mount to a standard 4” x 4” square or octagon electrical box per NEC standards. The square junction box requires a mud ring
  • Color matching via a paintable front cover – does not affect the warranty as long as the room controller is properly masked

Dimensions

  • Available in switching or dimming. See ordering information for more information.
  • Available in 1, 2, and 4 button options. See ordering information or the Low Voltage Keypads data sheet for more information.

Specifications

Electrical 120V 277V
Input Voltage 120V 50/60Hz 277V 50/60Hz
Current Consumptions 8A, LED/Electronic Ballast/LED Driver, 800W (VA),
Tungsten, Ballast, 1/4 HP 5A, LED/Electronic Ballast/LED Driver, 1,200W (VA),

Ballast, 1/3 HP



Low Voltage Wiring

| Class 2 0-10V Wiring
18 gauge stranded recommended, 0-10V sinking 50mA max
Class 2 Low Voltage Wiring
18 gauge stranded recommended, maximum wiring: 500 feet total system, 0-28VDC, 2mA-50mA
General
Daylighting Zones| Single and dual zone daylighting available
Dimming Area Control| Single area control (independently control primary and secondary daylighting zones)
Field of View| PIR| MT
450 sq ft to 1,500 sq ft with included lenses| 500 sq ft and 2,000 sq ft
Ultrasonic Frequency| 32 Khz
Photocell| 0-200FC (0-2,000 LUX)
Wireless
Bluetooth| 2.4 Ghz, 50ft max
Environmental
Operating Temperature| 32 to 104°F (0 to 40°C)
Storage Temperature| -15 to 160°F (-26 to 71°C)
Relative Humidity| 0-90% non-condensing
Other


Energy Codes

| Can be used to comply with IECC, ASHRAE 90.1, and 2022 Title 24, Part 6 occupancy/vacancy sensing, 0-10V dimming, partial-ON, partial-OFF, daylight harvesting, demand response and plug load or receptacle control requirements
Listings| UL773A (Occupancy Standard), UL924 (Emergency Equipment), cUL Listed, NOM Certified, RoHS Compliant, NY LLC48 Compliant
Warranty| 5-Year Limited Warranty

Leviton Manufacturing Co., Inc. Lighting & Controls
10385 SW Avery Street, Tualatin, OR 97062 tel 800-736-6682 tech line (6:00AM-4:00PM PT Mon-Fri) 800-959-6004
©2024 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.

Ordering Information

Smart Ceiling Mount Room Controller

Cat. No.| Description
ACY15-DIW| Smart Ceiling Mount Room Controller, PIR, 0-10V dimming, 2-zone, 450-1,500 sq ft coverage, 120-277VAC
AC705-DMW| Smart Ceiling Mount Room Controller, Multi-tech, 0-10V dimming, 1-zone, 500 sq ft coverage, 120-277VAC
ACY20-DMW| Smart Ceiling Mount Room Controller, Multi-tech, 0-10V dimming, 2-zone, 2,000 sq ft coverage, 120-277VAC
Smart Sensor App| Download for free from Google Play or the Apple App Store
Wireless Companion Switch and Dimmer
Cat. No.| Description
SBK00-CSW| Wireless Companion Switch, Battery powered, White
SBK00-CDW| Wireless Companion Dimmer, Battery powered, White
Low Voltage Keypads
Cat. No.| Description
PLVSW-1LW| Low Voltage Keypad, 1-button ON/OFF controller for use with Smart Ceiling Mount Room Controllers and Smart Ceiling Mount Sensors
PLVSW-2LW| Low Voltage Keypad, 2-button ON/OFF controller for use with Smart Ceiling Mount Room Controllers and Smart Ceiling Mount Sensors
PLVSW-4LW| Low Voltage Keypad, 4-button ON/OFF controller for use with Smart Ceiling Mount Room Controllers and Smart Ceiling Mount Sensors
RDGSW-1Ex| 1-button Color Change Kit (blank)
RDGSW-2Ex
| 2-button Color Change Kit (blank)
RDGSW-4Ex| 4-button Color Change Kit (blank)
RDGSW-1Fx
| 1-button Custom Engraved Color Change Kit
RDGSW-2Fx| 2-button Custom Engraved Color Change Kit
RDGSW-4Fx
| 4-button Custom Engraved Color Change Kit

Replace x to indicate color: White (W), Ivory (I), Light Almond (T), Gray (G), Black (E) and Red (R). Color change kits are blank and available for custom engraving for button markings

MORE INFORMATION

Leviton Manufacturing Co., Inc. Lighting & Controls
10385 SW Avery Street, Tualatin, OR 97062 tel 800-736-6682 tech line (6:00AM-4:00PM PT Mon-Fri) 800-959-6004

Leviton Manufacturing Co., Inc. Global Headquarters
201 North Service Road, Melville, NY 11747-3138 tel 800-323-8920 tech line (8:00AM-10:00PM ET Mon-Fri, 9:00AM-7:00PM ET Sat, 9:00AM-5:00PM ET Sun) 800-824-3005

Visit our Website at: www.leviton.com/smartsensors
©2024 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice

FAQ

  • Q: Can the Smart Ceiling Mount Room Controller be used with both Android and iOS devices?
    • A: Yes, the Leviton Smart Sensor App is compatible with both Android and iOS smartphones or tablets for easy configuration.
  • Q: How can I expand the coverage area of the Smart Ceiling Mount Room Controller?
    • A: You can expand the coverage area by connecting additional Smart Ceiling Mount Sensors wirelessly to increase the field of view up to 10,000 sq ft.
  • Q: Is manual control possible with the Smart Ceiling Mount Room Controller?
    • A: Yes, manual control can be achieved by connecting Low Voltage Keypads or Wireless Switches to adjust settings and force lights to full ON in emergencies.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals