CyberPower BPS Series UPS Battery Cabinet Tower Installation Guide
- July 25, 2024
- CyberPower
Table of Contents
- CyberPower BPS Series UPS Battery Cabinet Tower
- Product Usage Instructions
- SAFETY INSTRUCTIONS
- INTRODUCTION
- INSTALLATION
- EXTENDED BATTERY MODULE INSTALLATION
- EXTENDED BATTERY MODULE INSTALLATION
- MAINTENANCE
- TECHNICAL SPECIFICATIONS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
CyberPower BPS Series UPS Battery Cabinet Tower
Specifications
- Model Numbers: BPS240V7A, BPS240V9A, BPS192V7A, BPS192V9A
- DC plug-and-play power connectors for easy installation
- Increases battery runtimes during power outages
Product Usage Instructions
Installation
Before starting the installation process, ensure that you have read and understood the safety instructions provided in the manual.
Hardware Installation
Follow the hardware installation instructions provided in the manual to securely set up the UPS Extended Battery Module.
Extended Battery Module Installation
To install the Battery Module:
- Connect the Battery Module to the UPS using the provided DC plug-and-play power connectors.
- Configure the Extended Battery Modules based on your requirements as outlined in the manual.
Maintenance
Regular maintenance of the UPS Extended Battery Module is essential for optimal performance. Refer to the manual for maintenance instructions. FAQ
Q: Can I connect multiple Extended Battery Modules to a single UPS system?
A: Yes, you can daisy-chain additional EBMs to a UPS system using the DC plug- and-play power connectors.
Q: How many people are recommended for handling operations and installation?
A: At least two people are required for all handling operations, including unpacking, lifting, and installation in a rack system.
SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
Please read this manual and follow the instructions for installation and
operation.
PRODUCT SAFETY
CAUTION
A battery can present a risk of electric shock and high short circuit current.
The following precaution should be observed when working on batteries:
- Remove watches, rings or other metal objects.
- Use tools with insulated handles.
- Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect the AC power prior to connecting or disconnecting terminals.
Ensure the ground terminal is disconnected during installation and maintenance
to reduce likelihood of shock. If the battery is installed and grounded,
disconnected the ground terminal before working on the UPS.
RISK OF ELECTRIC SHOCK
See Installation Instructions Before Connecting To The Supply. Do Not
Disconnect the Battery Connector Under Load. Batteries are replaceable by
SERVICE PERSONNEL.
BATTERY
Do not dispose of batteries in a fire as the battery may explode.
Do not open or mutilate the battery, released electrolyte is harmful to the
skin and eyes.
INTRODUCTION
UPS EXTENDED BATTERY MODULES
Extended Battery Modules (EBMs) from CyberPower (BPS240V7A, BPS240V9A, BPS192V7A, BPS192V9A) increase battery runtimes during power outages. The DC plug-and-play power connectors allow to daisy- chain additional EBMs to a UPS system.
UNPACKING PROCEDURES
Information, advice, help
The equipment is very heavy, please handle it with care. Wear safety shoes and use a hydraulic equipment lift if one is available. At least two people are required for all handling operations, including unpacking, lifting, and installation in a rack system. Do not use the lifting straps to carry the unit around; they are provided to manually unpack the unit only. Inspect it for shipping damage. If any shipping damage is found, report it to the carrier and your local dealer immediately. Check the accessories included against the packing list. If there is any discrepancy, contact your local dealer immediately.
WHATS IN THE BOX
# | CONTENT | QTY |
---|---|---|
1 | EBM | 1 |
2 | User’s Manual | 1 |
3 | Phone Cable | 1 |
4 | L-shaped Plate | 2 |
5 | M4X10L Screws | 4 |
UNPACKING PROCEDURES
Information, advice, help
The equipment is very heavy, please handle with care. Wear safety shoes and
use a hydraulic equipment lift if one is available. At least two people are
required for all handling operations, including unpacking, lifting, and
installation in a rack system. Do not use the lifting straps to carry the unit
around; they are provided to manually unpack the unit only.
Inspect the EBM for shipping damage. If any shipping damage is found, report
it to the carrier and your local dealer immediately.
Check the accessories included against the packing list. If there is any
discrepancy, contact your local dealer immediately.
- Cut the straps.
- Remove the carton upward.
- Remove the buffering packaging and loosen four M4X10L screws between EBM and Pallet.
- Put the wood board as shown below. Make sure that the slide rests firmly against the pallet so it remains in place during unloading operations. Pull the EBM from the front with caution when sliding it off the pallet. For safety concerns, once your EBM is firmly in place, fixing the EBM on the floor by using an L-shaped Plate is highly recommended.
INSTALLATION
HARDWARE INSTALLATION
Caution – Important Instructions: Must always be followed.
The EBM is very heavy. Please handle it with care. For safety concerns, fixing the EBM on the floor by using an L-shaped Plate is highly recommended.
EXTENDED BATTERY MODULE INSTALLATION
BATTERY MODULE
EXTENDED BATTERY MODULE INSTALLATION
CONNECTION WITH UPS
-
UPS with one Extended Battery Module (EBM)
- Step 1: Turn off the DC breaker on the EBM.
- Step 2: Loosen the two screws to remove the battery cable retention bracket of the UPS.
- Use the output cable of the EBM to connect the EBM to the UPS.
- Step 3: Use the phone cable to connect the “BATT DEP.” port between UPS and EBM for EBM quantity auto-detection.
- Step 4: Turn on the DC breaker of the EBM.
-
UPS with multiple Extended Battery Modules (EBMs)
EXTENDED BATTERY MODULES CONFIGURATION
Extended Battery Modules can be configured by the user to display correct estimated battery runtimes.
CONFIGURATION ITEM| AVAILABLE SETTING| DEFAULT SETTING|
NOTE
---|---|---|---
C25 – EBM Number
|
Autodetect, 0-10 pack(s)
|
Autodetect
| Autodetect is used only for CyberPower EBMs. If more than 3 EBMs are connected, auto- detection does not function.
MAINTENANCE
STORAGE
To store your EBM for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to ensure battery life.
SAFETY PRECAUTIONS
Warning: High voltage – Risk of Electric Shock
- CAUTION! Only use replacement batteries that are certified by Cyber Power Systems. Use of incorrect battery type is an electrical hazard that could lead to explosion, fire, electric shock, or short circuit.
- CAUTION! Batteries contain an electrical charge that can cause severe burns. Before servicing batteries, please remove any conductive materials such as jewelry, chains, wrist watches, and rings.
- CAUTION! Do not open or mutilate the batteries. Electrolyte fluid is harmful to the skin/eyes and may be toxic.
- CAUTION! To avoid electric shock, turn off and unplug the UPS from the wall receptacle before servicing the battery.
- CAUTION! Only use tools with insulated handles. Do not lay tools or metal parts on top of the UPS or battery terminals.
BATTERY DISPOSAL
Do Not Discard
Batteries are considered hazardous waste and must be disposed of properly.
Contact your local government for more information about proper disposal and
recycling of batteries.
Do not dispose of batteries in fire.
Cyber Power Systems encourages environmentally sound methods for disposal and
recycling of its UPS products.
Please dispose and/or recycle your UPS and batteries in accordance with local
regulations.
BATTERY REPLACEMENT
For battery procurement, go to www.CyberPower.com, or contact your local
dealer.
When the Replace Battery the LCD displays Service Battery, use PowerPanel
Business Agent software or log on to the RMCARD to perform a runtime
calibration to verify battery capacity is sufficient and acceptable.
Please read and follow the Safety Instructions before servicing the battery.
Battery replacement should be performed by trained personnel who are familiar
with the procedures and safety precautions. Make a note of the Replacement
Battery part number.
TECHNICAL SPECIFICATIONS
Models | BPS240V7A | BPS240V9A | BPS192V7A | BPS192V9A |
---|
CONFIGURATION
DC Output Voltage| 240 Vdc| 192 Vdc
PHYSICAL
Dimensions (mm)| W x H x D = 270 x 520 x 460
BATTERY
Specifications| 12V x 20 pcs x 2 sets| 12V x 16 pcs x 2 sets
ENVIRONMENT
Operating Temperature| 32 °F to 104 °F ( 0 °C to 40 °C)
Operating Relative Humidity| 0 to 90% Non-Condensing
Cyber Power Systems, Inc.
www.cyberpower.com
11F., No.26, Jinzhuang Rd., Neihu Dist., Taipei City 114, Taiwan
Copyright © 2023 Cyber Power Systems, Inc. All rights reserved.
CyberPower and the CyberPower logo are trademarks of Cyber Power Systems,
Inc., and/ or affiliates, which are registered in many countries and regions.
All other trademarks are the property of their respective owners.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>