EasyLine XLP000 performance at Ith = 125A

The XLP000 has defined an Ith =125A at the following condition:

  • The XLP000 fulfills the requirements according to test sequence V in IEC 60947-3. This overload performance has been successfully tested with le=125A and a 125A fuse link. The test has been performed with maximum cross section 35mm2 and without the additionally feeding clamp. This setup has a continuous thermal current Ith =100A.
  • Continuously use at Ith=125A requires the use of an feeding clamp equivalent to the 1SEP407811R0001
  • The use of a feeding clamp is also required to fulfill the requirements according to IEC 60947-3 regarding the cable connection capacity. (50mm2)

Dimension

Warning! Hazardous voltage! Installation by a person with electrotechnical expertise only.