ABB ACS380 Machinery Drive Instruction Manual

June 4, 2024
ABB

ACS380 Machinery Drive
Instruction ManualABB ACS380 Machinery Drive

ACS380 Machinery Drive

ABB MACHINERY DRIVES
ACS380 drives
Quick installation and start-up guide

Safety instructions

WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur. If you are not a qualified electrical professional, do not do electrical installation or maintenance work.

  • Do not do work on the drive, motor cable, motor, or control cables when the drive is connected to the input power. Before you start the work, isolate the drive from all dangerous voltage sources and make sure that it is safe to start work. Always wait for 5 minutes after disconnecting the input power to let the intermediate circuit capacitors discharge.
  • Do not do work on the drive when a rotating permanent magnet motor is connected to it. A rotating permanent magnet motor energizes the drive, including its input and output terminals.

Unpack the delivery

Keep the drive in its package until you are ready to install it. After unpacking, protect the drive from dust, debris and moisture.
Make sure that these items are included:

  • drive
  • options, if ordered with an option code
  • installation accessories (cable clamps, cable ties, hardware, etc.)
  • mounting template (frames R3 and R4 only)
  • safety instructions
  • multilingual warning sticker sheet (residual voltage warning)
  • user interface guide (under the drive front cover)
  • quick installation and start-up guide
  • hardware and firmware manuals, if ordered with an option code.
    Make sure that there are no signs of damage to the items.

Reform the capacitors
If the drive has not been powered up for a year or more, you must reform the DC link capacitors. The manufacturing date is on the type designation label. Refer to Capacitor reforming instructions (3BFE64059629 [English]).

Select the cables and fuses

  • Select the power cables. Obey the local regulations.
  • Input power cable: ABB recommends using a symmetrical shielded cable (VFD cable) for the best EMC performance.
  • Motor cable: Use symmetrical shielded cable (VFD cable) for the best EMC performance. The symmetrical shielded cable also reduces bearing currents, wear, and stress on motor insulation.
  • Power cable types: In IEC installations, use copper or aluminum cables (if permitted). In UL installations, use only copper cables.
  • Current rating: max. load current.
  • Voltage rating: min. 600 V AC.
  • Temperature rating: In IEC installations, select a cable rated for at least 70 °C (158 °F) maximum permissible temperature of the conductor in continuous use. In UL installations, select a cable rated for at least 75 °C (167 °F).
  • Size: Refer to Fuses and typical power cable sizes for the typical cable sizes and to Terminal data for the power cables for the maximum cable sizes.
  • Select the control cables. Use double-shielded twisted-pair cable for analog signals. Use double-shielded or single-shielded cable for the digital, relay and I/O signals. Do not run 24 V and 115/230 V signals in the same cable.
  • Protect the drive and input power cable with the correct fuses. Refer to Fuses and typical power cable sizes.

Examine the installation area

The drive is intended for cabinet installation and has a degree of protection of IP20 / UL open type as standard.
Examine the site where you will install the driver. Make sure that:

  • The installation site is sufficiently ventilated and hot air does not recirculate.
  • There is sufficient free space around the drive for cooling, maintenance, and operation. For the minimum free space requirements, refer to Free space requirements.
  • The ambient conditions meet the requirements. Refer to Ambient conditions.
  • The installation surface is as close to vertical as possible and strong enough to support the weight of the drive. Refer to Dimensions and weights.
  • The installation surface, floor, and materials near the drive are not flammable.
  • There are no sources of strong magnetic fields such as high-current single-core conductors or contactor coils near the drive. A strong magnetic field can cause interference or inaccuracy in the operation of the drive.

Install the drive

You can install the drive with screws or to a DIN rail (top hat type, width × height = 35 mm × 7.5 mm [1.4 in × 0.3 in]).

  • Install R0 drives vertically. R0 drives do not have a cooling fan.
  • You can install drives with frame size R1…R4 tilted by a maximum of 90 degrees, from vertical to fully horizontal orientation.
  • Do not install the drive upside down.
  • You can install several drives side by side.

To install the drive with screws

  1. Make marks on the surface for the mounting holes. Refer to Dimensions and weights. Use the included mounting template for frames R3 and R4.

  2. Drill the holes for the mounting screws. If necessary, install suitable plugs or anchors into the holes.
    ABB ACS380 Machinery Drive - fig

  3. Install the mounting screws into the holes. Leave a gap between the screw head and the installation surface.

  4. Put the drive onto the mounting screws.

  5. Tighten the mounting screws.

To install the drive to a DIN rail

  1. Move the locking part to the left. If necessary, use a flat-head screwdriver.

  2. Push and hold the locking button down.

  3. Put the top tabs of the drive onto the top edge of the DIN rail.

  4. Put the drive against the bottom edge of the DIN rail.
    ABB ACS380 Machinery Drive - fig 1

  5. Release the locking button.

  6. Move the locking part to the right.

  7. Make sure that the drive is correctly installed.

To remove the drive, open the locking part and lift the drive from the DIN rail. M2

Measure the insulation resistance

Drive: Do not do voltage tolerance or insulation resistance tests on the drive, because this can cause damage to the drive.
Input power cable: Before you connect the input power cable, measure the insulation of the input power cable. Obey the local regulations.
Motor and motor cable:

  1. Make sure that the motor cable is connected to the motor and disconnected from the drive output terminals T1/U, T2/V, and T3/W.
  2. Use a voltage of 1000 V DC to measure the insulation resistance between each phase conductor and the protective earth conductor. The insulation resistance of an ABB motor must be more than 100 Mohm (at 25 °C [77 °F]). For the insulation resistance of other motors, refer to the manufacturer’s documentation.
    Moisture in the motor decreases the insulation resistance. If you think that there is moisture in the motor, dry the motor and do the measurement again

Make sure that the drive is compatible with the grounding system

You can connect all drive types to a symmetrically grounded TN-S system (center-grounded wye). The drive is delivered with the EMC and VAR screws installed. The material of the screws (plastic or metal) depends on the product variant. The table shows when to remove the metal EMC screw (disconnect the internal EMC filter) or metal VAR screw (disconnect the varistor circuit).

Screw label Factory default screw material Grounding systems
Symmetrically grounded TN-S systems (center-grounded wye) Corner-grounded
delta, midpoint-grounded delta, and TT systems IT systems

(ungrounded or
high-resistance
grounded)
EMC| Metal| Do not remove| Remove| Remove
Plastic 1)| Do not remove 2)| Do not remove| Do not remove
VAR| Metal| Do not remove| Do not remove| Remove
Plastic| Do not remove| Do not remove| Do not remove

  1. Drives sold in North America have a plastic EMC screw.
  2. Can install the metal screw (included in the drive delivery) to connect the internal EMC filter.
    ABB ACS380 Machinery Drive - fig 2

Connect the power cables

 Connection diagram (shielded cables)ABB ACS380 Machinery Drive - fig
3

  1. Disconnecting device.
  2. Two protective earth (ground) conductors. Drive safety standard IEC/EN 61800-5-1 requires two PE conductors if the cross-sectional area of the PE conductor is less than 10 mm2 Cu or 16 mm2 Al. For example, you can use the cable shield in addition to the fourth conductor.
  3. Use a separate grounding cable or a cable with a separate PE conductor for the line side, if the conductivity of the fourth conductor or shield does not meet the requirements for the PE conductor.
  4. Use a separate grounding cable for the motor side, if the conductivity of the shield is not sufficient, or if there is no symmetrically constructed PE conductor in the cable.
  5. 360-degree grounding of the cable shield is required for the motor cable and brake resistor cable (if used). It is also recommended for the input power cable.
  6. Brake resistor and resistor cable (optional).

Connection procedure (shielded cables)
For the tightening torques, refer to Terminal data for the power cables.

  1. Remove the screw on the drive front cover, then remove the front cover.

  2. Attach the residual voltage warning sticker in the local language to the drive.

  3. Strip the motor cable.

  4. Ground the motor cable shield under the grounding clamp.

  5. Twist the motor cable shield into a bundle, mark it and connect it to the grounding terminal.

  6. Connect the phase conductors of the motor cable to terminals T1/U, T2/V and T3/W.
    ABB ACS380 Machinery Drive - fig 4

  7. If you use a brake resistor, connect the brake resistor cable to terminals R- and UDC+. Use a shielded cable and ground the shield under the grounding clamp.

  8. Make sure that the R- and UDC+ terminal screws are tightened. Do this step also if you do not connect cables to the terminals.

  9. Strip the input power cable.

  10. If the input power cable has a shield, ground the shield under the grounding clamp. Then twist the shield into a bundle, mark it and connect it to the grounding terminal.

  11. Connect the PE conductor of the input power cable to the grounding terminal. If necessary, use a second PE conductor.
    ABB ACS380 Machinery Drive - fig 5

  12. In 3-phase drives, connect the phase conductors of the input power cable to terminals L1, L2, and L3. In 1-phase drives, connect the phase and neutral conductors to terminals L1 and L2.

  13. Mechanically attach the cables on the outside of the drive.

Connect the control cables

Do the connections according to the default control connections of the application macro that you select. Keep the signal wire pairs twisted as near to the terminals as possible to prevent inductive coupling. The tightening torque for the terminal connections is 0.5 … 0.6 N·m (4.4 … 5.3 lbf·in).

  1. Strip a part of the outer shield of the control cable for grounding.

  2. Use a cable tie to ground the outer shield to the grounding tab.

  3. Use metal cable ties for 360-degree grounding.

  4. Strip the control cable conductors.
    ABB ACS380 Machinery Drive - fig 6

  5. Connect the conductors to the correct control terminals.

  6. Connect the shields of the twisted pairs and grounding wires to the SCR terminal.

  7. Mechanically attach the control cables on the outside of the drive.

Default I/O connections (ABB standard macro)
The ABB standard macro is the default macro. The connection diagram for the ABB standard macro is shown below. If you have a drive variant that does not have the BMIO-01 module, connect only the terminals that are on the base unit.
ABB ACS380 Machinery Drive - fig 71) x = on base unit, empty = on BMIO-01 module.
Embedded Fieldbus connection
You can connect the drive to an EIA-485 serial communication link through the embedded Fieldbus interface on the BMIO-01 I/O module. The embedded Fieldbus interface supports the Modbus RTU protocol. To configure Modbus RTU communication with the embedded Fieldbus:

  1. Connect the Fieldbus cables and the necessary I/O signals.
  2. Use the jumpers to set the termination and bias settings.
  3. Power up the drive and set the necessary parameters.

A connection example is shown below.ABB ACS380 Machinery Drive - fig
8

  1. The devices at the ends of the Fieldbus must have a termination on. All other devices must have termination off.
  2. One device must have a bias on it. It is recommended that this device is at the end of the Fieldbus.
  3. Attach the cable shields together at each drive, but do not connect them to the drive. Connect the shields only to the grounding terminal in the automation controller.
  4. Connect the signal ground (BGND) conductor to the signal ground reference terminal in the automation controller. If the automation controller does not have a signal ground reference terminal, you can connect the signal ground to the cable shields through a 100-ohm resistor, preferably near the controller.

Start up the drive

WARNING! Before you start up the drive, make sure that the installation is completed. Make sure also that it is safe to start the motor.
Disconnect the motor from other machinery, if there is a risk of damage or injury.
For information on the user interface, refer to the ACS380 User interface guide (3AXD50000022224 [English]), which is delivered with the drive.

  1. Power up the drive. The drive software automatically identifies the connected adapter (BMIO-01 module or some of the Fieldbus modules) and sets the applicable parameters.

  2. Select the units (international or US). In the Motor data view, select the motor type:
    Asian: Asynchronous motor
    PMSM: Permanent magnet synchronous motor
    SynRM: Synchronous reluctance motor.
    ABB ACS380 Machinery Drive - fig 9

  3. Set the motor control mode:
    Vector: Speed reference. This is suitable for most cases.
    Scalar: Frequency reference. Do not use this mode for permanent magnet synchronous motors. Use this mode when:
    • The number of motors can change.
    • The nominal motor current is less than 20% of the nominal drive current.

  4. Set the nominal motor values.

  5. Start the motor and check the direction of rotation.
    ABB ACS380 Machinery Drive - fig 10If the direction is incorrect, you can:
    • change the Phase order setting, or
    • change the phase order of the motor cable.
    Note: In vector control mode the drive does an automatic standstill ID run at the first start.

  6. In the Motor control view, set the start and stop mode.

  7. Set the acceleration and deceleration times.

  8. Set the maximum and minimum speeds.

  9. In the Control macros view, select the applicable macro. To configure Fieldbus communications, refer to Fieldbus communication.

  10. Tune the drive parameters to the application. You can also use an assistant control panel (ACS-AP-…) or the Drive Composer PC tool.

WARNING! If you activate the automatic fault reset or automatic restart functions of the drive control program, make sure that no dangerous situations can occur. These functions reset the drive automatically and continue operation after a fault or supply break. If these functions are activated, the installation must be clearly marked as defined in IEC/EN 61800-5-1, subclause 6.5.3, for example, “THIS MACHINE STARTS AUTOMATICALLY”.

 Fieldbus communication
Fieldbus communication with the BMIO-01 I/O module

  1. Select Modbus RTU from the Control macros view. The drive changes some parameter values automatically.
  2. Configure Fieldbus communication from the parameter list. The minimum set of parameters for Modbus RTU configuration:
No. Name Value
20. Excel commands Embedded Fieldbus
22. Excel speed refl (vector) EFB refl
28. Excel frequency refl (scalar) EFB refl
31. Fault reset selection Dell
58. Protocol enable Modbus RTU
58. Node address 1 (default)
58. Baud rate 19.2 kbps (default)
58. Parity 8 EVEN 1 (default)

Fieldbus communication with a Fieldbus adapter module
The drive automatically identifies the connected adapter and selects the correct Fieldbus control macro. If necessary, configure the adapter-specific settings.
Refer to the applicable Fieldbus adapter documentation.
Warnings and faults

Warning Fault Description
A2A1 2281 Warning: Current calibration is done at the next start. Fault:

Output phase current measurement fault.
A2B1| 2310| Overcurrent: The output current is more than the internal limit. This can be caused by an earth fault or phase loss.
A2B3| 2330| Earth leakage: A load unbalances that is typically caused by an earth fault in the motor or the motor cable.
A2B4| 2340| Short circuit: A short circuit in the motor or the motor cable.
–| 3130| Input phase loss: The intermediate DC circuit voltage oscillates.
–| 3181| Cross connection: The input and motor cable connections are incorrect.
A3A1| 3210| DC link overvoltage: Intermediate DC circuit voltage too high.
A3A2| 3220| DC link undervoltage: Intermediate DC circuit voltage too low.
–| 3381| Output phase loss: All three phases are not connected to the motor.
ASAO| 5091| Safe torque off The Safe torque off (STO) function is active.
–| 6681| EFB communication loss: A loss in embedded Fieldbus communications.
–| 7510| FBA A communication loss: A loss in communications between the drive and the Fieldbus adapter.
AFF6| | Identification run: Motor ID run occurs at the next start.
–| FA81| Safe torque off 1: Safe torque off circuit 1 is broken.
–| FA82| Safe torque off 2: Safe torque off circuit 2 is broken.

Ratings

ACS38O-04xx Input ratings Output ratings

No
choke| With
choke| Max.
current| Nominal use| Light-duty use| Heavy-duty use
4| 4| /max| 44| ch| kd| lid| ‘Hd| PhD
A| A| A| A| kW| A| kW I hp| A| kW| hp
1-phase UN = 230 V|
02A4-1| 5.0| 4.| 3.| 2.| 0.37| 2.| 0.37| 0.5| 2.| 0.25| 0.33
03A7-1| 7.| 6.| 4.| 37| 0.55| 4.| 0.55| 0.8| 2.| 0.37| 0.5
04A8-1| 9.| 8.| 7.| 5.| 0.75| 5.| 0.75| 1.0| 4.| 0.55| 0.75
06A9-1| 12.0| 12.| 9.| 7.| 1.10| 7.| 1.10| 2.| 5.| 75| 1.0
07A8-1| 14.| 14.| 12.| 8.| 2.| 7.| 2.| 2.0| 7.| 1.| 2.
09A8-1| 187| 17.0| 14.0| 10.| 2.| 9.| 2.| 3.0| 8.| 2.| 2.0
12A2-1| 25.| 21.| 18.| 12.| 3.0| 12.| 3.0| 3.0| 10.| 2.| 3.0
3-phase UN = 230 V|
02A4-2| 4.| 2.| 3.| 2.| 0.37| 2.| 0.37| 0.5| 2.| 0.25| 0.33
03A7-2| 5.| 37| 4.| 4.| 0.55| 3.| 0.55| 0.75| 2.| 0.37| 0.5
04A8-2| 6.| 5.| 7.| 5.| 75| 5.| 75| 1.0| 37| 0.55| 0.75
06A9-2| 8.| 7.| 9.| 7.| 1.| 7.| 1.| 2.| 5.| 35| 1.0
07A8-2| 10.| 8.| 12.| 8.| 2.| 8.| 2.| 2.0| 7.| 1.| 2.
09A8-2| 14.| 10.| 14.0| 10.| 2.| 9.| 2.| 2.0| 8.| 2.| 2.0
12A2-2| 17.| 12.| 18.| 12.| 3.0| 12.| 3.0| 3.0| 10.| 2.| 3.0
17A5-2| 22.| 18.| 22.0| 18.| 4.0| 167| 4.0| 5.0| 12.| 3.0| 3.0

Related documents

| | ABB ACS380 Machinery Drive - qr code 2
---|---|---
https://search.abb.com/library/Download.aspx?DocumentID=9AAK10103A6193&LanguageCode
=en&DocumentPartId=1&Action=Launch
| https://youtube.com/playlist?list=PLL7dUsU7kD1qnKggydyiT-OrAnhKDK067| https://ecodesign.drivesmotors.abb.com/

3AXD50000018553 Rev E EN 2021-07-01
Original instructions.
© Copyright 2021 ABB. All rights reserved. ABB ACS380 Machinery Drive - bar
code

ACS38O
-04xx-
—| Input ratings| Output ratings
---|---|---
No choke| With choke| Max. current| Nominal use| Light-duty use| Heavy-duty use
‘1| ‘1| /max| ‘N| Pn| ‘Ld| /Hd| ‘Hd| PHd
A| A| A| A| kW| A| kW        hp| A| kW| hp
1-phase UN = 230 V|
02A4-1| 5.0| 4.| 3.| 2.| 0.37| 2.| 0.37| 0.5| 2.| 0.25| 0.33
03A7-1| 7.| 6.| 4.| 37| 0.55| 4.| 0.55| 0.8| 2.| 0.37| 0.5
04A8-1| 9.| 8.| 7.| 5.| 0.75| 5.| 0.75| 1.0| 4.| 0.55| 0.75
06A9-1| 12.0| 12.| 9.| 7.| 1.10| 7.| 1.10| 2.| 5.| 75| 1.0
07A8-1| 14.| 14.| 12.| 8.| 2.| 7.| 2.| 2.0| 7.| 1.| 2.
09A8-1| 187| 17.0| 14.0| 10.| 2.| 9.| 2.| 3.0| 8.| 2.| 2.0
12A2-1| 25.| 21.| 18.| 12.| 3.0| 12.| 3.0| 3.0| 10.| 2.| 3.0
3-phase UN = 230 V|
02A4-2| 4.| 2.| 3.| 2.| 0.37| 2.| 0.37| 0.5| 2.| 0.25| 0.33
03A7-2| 5.| 37| 4.| 4.| 0.55| 3.| 0.55| 0.75| 2.| 0.37| 0.5
04A8-2| 6.| 5.| 7.| 5.| 75| 5.| 75| 1.0| 37| 0.55| 0.75
06A9-2| 8.| 7.| 9.| 7.| 1.| 7.| 1.| 2.| 5.| 35| 1.0
07A8-2| 10.| 8.| 12.| 8.| 2.| 8.| 2.| 2.0| 7.| 1.| 2.
09A8-2| 14.| 10.| 14.0| 10.| 2.| 9.| 2.| 2.0| 8.| 2.| 2.0
12A2-2| 17.| 12.| 18.| 12.| 3.0| 12.| 3.0| 3.0| 10.| 2.| 3.0
17A5-2| 22.| 18.| 22.0| 18.| 4.0| 167| 4.0| 5.0| 12.| 3.0| 3.0

I1…………..Input current for 230 V and 400 V with motor power PN (kW), and for 480 V with motor power PLd (hp).
Imax Maximum output current. Available for 2 seconds every 10 minutes when the output frequency is less than 9 Hz.
IN………………….. Nominal output current. Maximum continuous RMS output current (no overload).
ILd…………. Continuous RMS output current. Allows 10% overload for 1 minute every 10 minutes.
IHd………………….. Continuous RMS output current. Allows 50% overload for 1 minute every 10 minutes.
PN………………… Typical motor power in nominal use (no overload)
PLd……………… Typical motor power in light-duty use (10% overload)
PHd………………. Typical motor power heavy-duty use (50% overload)
The kilowatt ratings are applicable to most IEC 4-pole motors. The horsepower ratings are applicable to most NEMA 4-pole motors.
Fuses and typical power cable sizes

ACS380 -04xx- Fuses Cable conductor sizes (Cu) Frame size
gG gR UL class T1) 2) 3) 4)
ABB type Bussmann type Bussmann/ Edison type mm2

1-phase 44i = 230 V
02A4-1| OFAF000H10| 170M2695| DN/TJNIO| 3×1.5 + 1.5| 16| RO
03A7-1| OFAF000H10| 170M2695| DN/TJN110| 3×1.5 + 1.5| 16| RO
04A8-1| OFAF000H16| 170M2696| DN/TJN20| 3×1.5 + 1.5| 16| RI
06A9-1| OFAF000H20| 170M2697| DN/TJN20| 3×1.5 + 1.5| 16| RI
07A8-1| OFAF000H25| 170N12698| JJN/TJN25| 3×1.5 + 1.5| 16| RI
09A8-1| OFAF000H32| 1701.| DN/111125| 3×2.5 + 2.5| 14| R2
12A2-1| OFAF000H35| 170M2698| DN/TJN35| 3×2.5 + 2.5| 14| R2
3-phase 4/N = 230 V
02A4-2| OFAF000H6| 1701,12694| DS/T)56| 3×1.5 + 1.5| 16| RI
03A7-2| OFAF000H10| 170M2695| J)5/T)510| 3×1.5 + 1.5| 16| RI
04A8-2| OFAF000H10| 170M2695| J)5/T)510| 3×1.5 + 1.5| 16| R1
06A9-2| OFAF000H16| 1701.| DS/73520| 3×1.5 + 1.5| 16| RI
07A8-2| OFAF000H16| 170N12696| DS/TJ520| 3×1.5 + 1.5| 16| RI
09A8-2| OFAF000H16| 1701.| DS/73520| 3×2.5 + 2.5| 14| RI
12A2-2| OFAF000H25| 170M2697| )JS/T)525| 3×2.5 + 2.5| 14| R2
17A5-2| OFAF000H32| 1701.| )JS/T)535| 3×6 + 6| 10| R3
25A0-2| OFAF000HSO| 1701.| 775/11550| 3x 6 + 6| 10| R3
032A-2| OFAF000 H63| 170M2700| J)S/T)S60| 3×10 + 10| 8| R3
048A-2| OFAF000H100| 1701.| DS/T35100| 3×25 + 16| 4| R4
055A-2| OFAF000H100| 1701.| DS/735100| 3×25 + 16| 4| R4
3-phase 444 = 400 V or 480 V
01A8-4| OFAF000H4| 170M2694| D5/1-356| 3×1.5 + 1.5| 16| RO
02A6-4| OFAF000H6| 1701.| DS/TJS6| 3×1.5 + 1.5| 16| RI
03A3-4| OFAF000H6| 1701.| DS/TJS6| 3×1.5 + 1.5| 16| RI
04A0-4| OFAF000H10| 170M2695| JJS/TJS10| 3×1.5 + 1.5| 16| R1
05A6-4| OFAF000H10| 170M2695| JJS/TJS10| 3×1.5 + 1.5| 16| RI
07A2-4| OFAF000H16| 1701.| DS/TJS20| 3×1.5 + 1.5| 16| RI
09A4-4| OFAF000H16| 1701.| DS/TJS20| 3×2.5 + 2.5| 14| RI
12A6-4| OFAF000H25| 170M2697| 7JSMS25| 3×2.5 + 2.5| 14| R2
17A0-4| OFAF000H32| 1701.| DS/TJS35| 3x 6 + 6| 10| R3
25A0-4| OFAF000HSO| 1701.| JJS/TJS40| 3x 6 + 6| 10| R3
032A-4| OFAF000 H63| 170M2700| JJS/TJS60| 3×10 + 10| 8| R4
038A-4| OFAF000H80| 170M2701| JJS/TJS80| 3×16 + 16| 6| R4
045A-4| OFAF000H100| 170M2702| DS/115100| 3×25 + 16| 4| R4
050A-4| OFAF000H100| 170M2702| DS/TJS100| 3×25 + 16| 4| R4

  1. The recommended branch protection fuses must be used to maintain the IEC/EN/UL 61800-5-1 listing.
  2. The drive is suitable for use on a circuit capable of delivering not more than 100000 symmetrical amperes (RMS) at 480 V (480 V drives) or 240 V (240 V drives) maximum when protected by the fuses given in this table.
  3. As an alternative to Class T fuses, you can use Class J or Class CF fuses of the same voltage and current rating for branch circuit protection of 3-phase drives.
  4. Refer to Alternate Fuses, MMPs and Circuit Breakers for ABB Drives (3AXD50000645015 [English]) for additional UL fuses and circuit breakers that can be used as branch circuit protection.

Terminal data for the power cables

Frame size Li, L2, L3, Ti/U, T2/V, T3/W, R-, R+/UDC+, UDC- PE

Min. wire size
(solid/
stranded)| Max. wire size
(solid/
stranded)| Tightening
torque| Max. wire size
(solid/
stranded)| Tightening
torque
mm2| AWG| mm2| AWG| N•rn| lbf•in| mm2| AWG| N1•m| lbf•in
RO| 0.5/0.5| 18| 4/2.5| 10| 0.5…0.6| 5| 6/4| 10| 1.| 11
R1| 0.5/0.5| 18| 4/2.5| 10| 0.5…0.6| 5| 6/4| 10| 1.| 11
R2| 0.5/0.5| 18| 4/2.5| 10| 0.5…0.6| 5| 6/4| 10| 1.| 11
R3| 0.5/0.5| 18| 10/6| 6| 1.2…1.5| 11…13| 6/4| 10| 1.| 11
R4| 0.5/0.5| 18| 25/16| 2| 2.5…3.7| 22…32| 25/16| 4| 3.| 26

Notes:

  • The minimum specified wire size does not necessarily have sufficient current carrying capacity at maximum load.
  • The terminals do not accept a conductor that is one size larger than the maximum specified wire size.
  • The maximum number of conductors per terminal is 1.

Free space requirements

Frame size Above Below Sides 1)
mm in mm in mm
RO R4 75 3 75 3
  1. A side-mounted option requires approximately 20 mm (0.8 in) of space on the right side of the drive.

Ambient conditions

Requirement During operation (installed for stationary use)
Installation site altitude 230 V drives:

0 … 2000 m (0 … 6562 ft) above sea level. 400/480 V drives:
0 … 4000 m (0 … 13123 ft) above sea level. At altitudes above 2000 m (6562 ft):
•only TN-S and TT grounding systems are permitted
•the maximum permitted voltage for the relay output ROI decreases. At 4000 m (13123 ft), it is 30 V.
Derating:
The output current must be derated 1% for each 100 m (328 ft) above 1000 m (3281 ft).
Surrounding air temperature| Frame RO:
-10 … +50 °C (14 … 122 °F). No frost is permitted.
Frames R1…R4:
-10 … +60 °C (14 … 140 °F). No frost is permitted.
The output current must be derated at temperatures above +50 °C (122 °F) as follows:
•Types 055A-2, 038A-4 and 050A-4: 2% for each added 1 °C (1.8°F)
•Other types: 1% for each added 1 °C (1.8°F).
Relative humidity| 5 … 95%. No condensation is permitted. The maximum permitted relative humidity is 60%in the presence of corrosive gases.
Contamination levels| No conductive dust is permitted.
Shock or free fall| Not permitted.

Dimensions and weights

ABB ACS380 Machinery Drive - fig 11

Frame
size| Dimensions| Weights
---|---|---
HI| H2| H3| W| D1| M1| M2
mm| in| mm| in| mm| in| mm| in| mm| in| mm| in| mm| in| kg| lb
RO| 205| 8.| 223| 9.| 170| 7.| 70| 3.| 176| 7.| 50| 2.0| 191| 8.| 1.| 3.
R1| 205| 8.| 223| 9.| 170| 7.| 70| 3.| 176| 7.| 50| 2.0| 191| 8.| 1.| 3.
R2| 205| 8.| 223| 9.| 170| 7.| 95| 4.| 176| 7.| 75| 3.0| 191| 8.| 2.0| 4.
R3| 205| 8.| 223| 9.| 170| 7.| 169| 7.| 176| 7.| 148| 6.| 191| 8.| 3.| 7.
R4| 205| 8.| 240| 10.| 170| 7.| 260| 10.| 181| 7.| 234| 9.| 191| 8.| 5.| 12.

Markings

The applicable markings are shown on the type label of the productABB ACS380
Machinery Drive - icon

Safe torque off (STO)
The drive has a Safe torque-off function (STO) in accordance with IEC/EN 61800-5-2. It can be used, for example, as the final actuator device of safety circuits that stop the drive in case of danger (such as an emergency stop circuit).
When activated, the STO function disables the control voltage of the power semiconductors of the drive output stage, thus preventing the drive from generating the torque required to rotate the motor. The control program generates an indication as defined by parameter 31.22. If the motor is running when Safe torque off is activated, it coasts to a stop. Closing the activation switch deactivates the STO. Any faults generated must be reset before restarting.
The STO function has a redundant architecture, that is, both channels must be used in the safety function implementation. The safety data given is calculated for redundant use, and does not apply if both channels are not used.
WARNING! The STO function does not disconnect the voltage from the main and auxiliary circuits of the drive.

Notes:

  • If stopping by coasting is not acceptable, stop the drive and machinery using the appropriate stop mode before activating the STO.
  • The STO function overrides all other functions of the drive.

Wiring
The safety contacts must open/close within 200 ms of each other. Double- shielded twisted-pair cable is recommended for the connection. The maximum length of the cabling between the switch and the drive control unit is 300 m (1000 ft). Ground the shield of the cable at the control unit only.
Validation
To ensure the safe operation of a safety function, a validation test is required. The test must be carried out by a competent person with adequate expertise and knowledge of the safety function. The test procedures and report must be documented and signed by this person. Validation instructions of the STO function can be found in the drive hardware manual.

Technical data

  • The minimum voltage at IN1 and IN2 to be interpreted as “1”: 13 V DC
  • STO reaction time (shortest detectable break): 1 ms
  •  STO response time: 2 ms (typical), 5 ms (maximum)
  • Fault detection time: Channels in different states for longer than 200 ms
  • Fault reaction time: Fault detection time + 10 ms
  • STO fault indication (parameter 31.22) delay: < 500 ms
  • STO warning indication (parameter 31.22) delay: < 1000 ms
  • Safety integrity level (EN 62061): SIL 3
  • Performance level (EN ISO 13849-1): PL e

The drive STO is a type A safety component as defined in IEC 61508-2. For the full safety data, exact failure rates and failure modes of the STO function, refer to the drive hardware manual.

Declarations of conformityABB ACS380 Machinery Drive - fig
12

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ABB User Manuals

Related Manuals