easee Electric Car Charger User Manual
Specifications
- Residual Current Protection: Internal RCD Type A
- DC Fault Current Threshold: 6 mA
- Ground Fault Indicator: LED turns red
- Temperature Monitoring: Internal sensors for overheating prevention
- Critical Fault Mode: Audio and visual signals in case of voltage error or relay error
- Disconnection Times: Compliant with IEC 60364-4-41
Product Usage Instructions
Residual Current Protection
The charging station is equipped with an internal RCD Type A that disconnects the power supply if the DC fault current exceeds 6 mA.
Ground Fault Detection
If a ground fault is detected, the LED indicator will turn red, and all relays will open to isolate the output. Reset the RCD by disconnecting the charging cable.
Critical Fault Mode
In case of a critical fault mode (voltage error, ground fault, or relay error), the station will enter critical fault mode with audio and visual signals. Contact Easee support for examination.
Temperature Monitoring
Internal temperature sensors prevent overheating by shutting down the station if the temperature exceeds safety limits.
Content
Technical documentation of residual current protection by IEC 60364, for charging station Easee Charge Core.
Summary
IEC 60364-7-722:2018 describes methods for residual current protection. The charging station uses the following method:
- The use of an RCD type A in conjunction with a residual direct current detecting device (RDC-DD) complying with IEC 62955.
Easee ASA declares that the charging station will disconnect the power supply
if the DC fault current exceeds 6 mA. In combination with an internal RCD Type
A, this will provide equivalent or higher protection compared to an RCD Type
B.
This document is a functional description of how the charging station achieves
protection under IEC 60364:2018. The document contains excerpts from the
technical documentation made available for TÜV Rheinland, and that has been
used as the basis for testing and type certification per EN IEC 61851-1: 2019.
Residual current protection
The charging station has an internal RCD Type A under IEC 60947-2. The
charging station contains equipment for the detection of DC residual currents
(RDC-DD) following IEC 62955. Disconnection in the event of DC fault currents
above 6 mA is ensured through a common switch, which breaks the control
current to all the internal relays for simultaneous opening.
The internal DC fault protection is automatically tested at startup, between
each charging session, or at least every 24 hours. The disconnection times are
faster than using a modular Type B device.
In
cases where a ground fault is detected, the LED indicator on the charging
station will turn red, all relays will open, thus isolating the output to the
Type-2 connector. The RCD is reset by disconnecting the charging cable. When
the Type-2 connector is not connected to both the charging station and the
electric vehicle, all relay contacts are always open.
The disconnection times for ground faults comply with the requirements in IEC
60364-4-41, section 411.3.2.2, for TN-, TT-, and IT-supply systems. The
disconnection time for IT supply in Table 1 is derived from Norwegian standard
NEK 400, based on IEC 60364.
Technical design
Table 2 provides an overview of the main requirements for the standards used, and performance parameters.
Critical fault mode alarm
In the event of a voltage error on the vehicle, voltage error due to a ground
fault, or relay error, the charging station will enter critical fault mode
with audio and visual signals and will not be usable. The critical fault mode
cannot be reset by the user but must be examined by Easee support.
In the event of a critical fault mode, the opening of relays will be ensured
through two separate systems, thereby providing redundancy and increased
safety before or during an ongoing charging session.
Temperature monitoring
The charging station is equipped with internal temperature sensors that initiate actions in response to unexpected temperature rises. Should the temperature exceed a pre-defined safety limit will the charging station automatically shut down to prevent overheating, and the user will receive a notification.
Technical performance and design parameters
Table 2: RCD Performance overview and key parameters
An RCD detection module is used to detect both AC and DC fault currents. An
additional fault signal will be active if an internal error is detected in the
module. Any of the three fault signals will cause all relays to open, thereby
isolating the Type-2 connector from the input current, including the neutral
conductor.
Function
The opening of relays in the event of a ground fault is designed as a dual- channel system to provide redundancy and thereby increase reliability in case of failure. A ground fault can be indicated by the sensor, whether it is a fault current of 6 milliamperes direct current (DC), 30 milliamperes alternating current (AC), or a fault in the sensor itself. When such a fault is detected, signals are sent to both a Microcontroller Unit (MCU) and a Complex Programmable Logic Device (CPLD). These two units will immediately open all relays by disconnecting the 12-volt control voltage to the relays. This is done through their own, separate breaking circuits, which are connected in series and controlled completely independently of each other.
This means that in the event of a fault in the MCU unit or its software (SW), the CPLD unit will still open the relays. Similarly, if a fault occurs in the CPLD unit, the MCU unit will still ensure that the relays are opened. This system ensures that a ground fault will always lead to the relays being opened, even if one of the channels fails, thereby significantly increasing safety.
The purpose of this document is to describe the ground fault protection for
the charging station, to achieve safety levels in accordance with IEC
60364:2018. Easee asserts that the information in this document is correct.
Beyond this, Easee ASA, or its subsidiaries, do not assume any responsibility
related to the use of the information in the document.
No part of this publication may be republished, reproduced, transmitted, or
reused in any other form, by any means
or in any format, for your own or third-party use, unless otherwise agreed in
writing with Easee or its subsidiaries. Any permitted use must always be in
accordance with good practice and ensure that no harm can be done to Easee, or
by misleading the consumer.
Easee and Easee products, product names, trademarks, and slogans, whether
registered or not, are the intellectual property of Easee and may not be used
without Easee’s prior written permission. All other mentioned products and
services may be trademarks or service marks of their respective owners.
April 2024 – Version 1.00
© 2024 by Easee ASA. All rights reserved.
FAQ
Q: How often should the internal DC fault protection be tested?
A: The protection is automatically tested at startup, between each charging session, or at least every 24 hours.
Q: What actions should be taken if the station enters critical fault mode?
A: Contact Easee support for examination as the critical fault mode cannot be reset by the user.