APsystems DS3D Microinverter Instruction Manual
- June 3, 2024
- APsystems
Table of Contents
- DS3D Microinverter
- Important Safety Instructions
- APsystems Microinverter System Introduction
- APsystems Microinverter DS3D Introduction
- Troubleshooting
- Replace a microinverter
- Technical Data
- DS3D – Wiring Diagram
- APsystems Microinverter Installation Map
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
DS3D Microinverter
Instruction Manual
DS3D Microinverter
ALTENERGY POWER SYSTEM Inc. latam.APsystems.com
Important Safety Instructions
This manual contains important instructions to follow during installation and
maintenance of the APsystems Photovoltaic Grid-connected Microinverter. To
reduce the risk of electrical shock and ensure a safe installation and
operation of the APsystems Microinverter, the following symbols appear
throughout this document to indicate dangerous conditions and important safety
instructions.
Specifications are subject to change without notice. Please ensure you are
using the most recent update found at
https://emea.apsystems.com/resources/library/
WARNING
This indicates a situation where failure to follow instructions may cause a
serious hardware failure or personnel danger if not applied appropriately. Use
extreme caution when performing this task.
NOTICE
This indicates information that is important for optimized microinverter
operation. Follow these instructions closely.
1.1 Safety Instructions
Only qualified professionals should install and/or replace APsystems
Microinverters.
Perform all electrical installations in accordance with local electrical
codes.
Before installing or using the APsystems Microinverter, please read all
instructions and cautionary markings in the technical documents and on the
APsystems Microinverter system and the solar array.
Do NOT disconnect the PV module from the APsystems Microinverter without
first disconnecting the AC power.
Be aware that the body of the APsystems Microinverter is the heat sink
and can reach a temperature of 80°C. To reduce risk of burns, do not touch the
body of the Microinverter.
Do NOT attempt to repair the APsystems Microinverter. If the
microinverter is suspected to be faulty, please contact your local APsystems
Technical Support to start troubleshooting and obtain a RMA (Return
Merchandise Authorization) number to start the replacement process if needed.
Damaging or opening the APsystems Microinverter will void the warranty.
Caution!
When connecting a microinverter, it is recommended to first connect the AC Bus
cable to the ground then connect the AC connector to ensure proper earthing of
the microinverter, then do the DC connections. When disconnecting a
microinverter disconnect the AC by opening the branch circuit breaker first
but maintain the protective earthing conductor in the branch circuit breaker
connected to the microinverter, then disconnect the DC inputs.
**Please install AC breakers on the AC side of the microinverter.
1.2 Radio Interference Statement
EMC Compliance :The APsystems Microinverter can radiate radio frequency
energy. If not installed and used in accordance with the instructions, it may
cause harmful interference to radio communication.
APsystems Microinverter complies with EMC regulations, which are designed to
provide reasonable protection against harmful interference in a residential
installation.
Nonetheless, if the Microinverter does cause harmful interference to radio or
television reception, you are encouraged to try to correct the interference by
one of more of the
following measures:
A) Reorient or relocate the receiving antenna
B) Increase the separation between the Microinverter and the receiver
C) Connect the Microinverter into an outlet on a circuit different from that
to which the receiver is connected
If none of the recommendations suggested above bring significant improvement
in terms of interference, please contact your local APsystems Technical
Support.
1.3 Symbols in lieu of words**
| Trademark.
---|---
| Caution, risk of electric shock.
****| Caution, hot surface.
| NOTICE, danger! This device directly connected with electricity generators
and public grid.
Qualified personnel| Person adequately advised or supervised by an
electrically skilled person to
enable him or her to perceive risks and to avoid hazards which electricity can
create. For the purpose of the safety information of this manual, a “qualified
person” is someone who is familiar with requirements for safety, electrical
system and EMC and is authorized to energize, ground, and tag equipment,
systems, and circuits in accordance with established safety procedures. The
inverter and complete system may only be commissioned and operated by
qualified personnel.
APsystems Microinverter System Introduction
The APsystems Microinverter is used in utility-interactive grid-tied applications, comprised of three key elements:
- APsystems Microinverter
- APsystems Energy Communication Unit (ECU)
- APsystems Energy Monitor and Analysis (EMA) web-based monitoring and analysis system
This integrated system improves safety, maximizes solar energy harvest,
increases system reliability, and simplifies solar system design,
installation, maintenance, and management.
Safety with APsystems Microinverters
In a typical string inverter installation, PV modules are connected in series.
The voltage adds-up to reach high voltage value (from 600Vdc up to 1000Vdc) at
the end of the PV string. This extreme high DC voltage brings a risk of
electrical shocks or electrical arcs which could cause fire in a worst case
scenario. When using an APsystems microinverter, each 1 or 2 PV modules are
connected to DC input. Voltage at the back of each PV module never exceeds PV
modules Voc, which is lower than 60Vdc for most of PV modules used with
APsystems microinverters, which means the DC input voltage will never exceed
120Vdc, and this low voltage will reduce the risk of electrical shock,
electrical arcs and fire hazards.
APsystems Microinverters maximize PV energy production
Each input channel has individual Maximum Peak Power Tracking (MPPT) control,
which ensures that the maximum power is produced to the utility grid
regardless of the performance of the PV modules of other channels in the
array. When PV modules in the array are affected by shade, dust, different
orientation, or any situation in which one channel underperforms compared
with the other channels, the APsystems Microinverter ensures top performance
from the array by maximizing the performance of each channel individually
within the array.
More reliable than centralized or string inverters
The distributed APsystems Microinverter system ensures that no single point of
system failure exists across the PV system. APsystems Microinverters are
designed to operate Zat full power at ambient outdoor temperatures of up to
65 deg C (or 149 F). The inverter case is designed for outdoor installation
and complies with the IP67 environmental enclosure rating.
Simple to install
APsystems Microinvertes are compatible with most of 60 and 72 cell PV modules
or 120 and 144 half-cut cells PV modules. (In order to confirm compatibility
of PV module with APsystems microinverter, feel free to check our online
“E-decider” module compatibility tool or contact your local APsystems
Technical Support). Installation requires a minimum number of accessories and
microinverters offer a lot of versatility to the installer: microinverters can
indeed be installed on different roofs with different orientation or with
modules having different orientation. In the same way, end-users can extend
their system whenever they want with microinverters.
Smart system performance monitoring and analysis
The APsystems Energy Communication Unit (ECU) is installed by simply plugging
it into any wall outlet and providing an Ethernet or Wi-Fi connection to a
broadband router or modem. After installing and setting the ECU (see ECU
Instruction Manual), the full network of APsystems Microinverters
automatically reports to the APsystems Energy Monitor and Analysis (EMA) web
server.
APsystems Microinverter DS3D Introduction
APsystems expands its 3rd generation of dual microinverter series with the
DS3D. With unprecedented power outputs of 2000W, the DS3D connects to 4 high
power modules (2 by 2 in series). With 2 independent MPPTs, encrypted ZigBee
signal, the DS3D benefits from an entirely new architecture.
The innovative design makes the product unique while maximizing power
production. The components are encapsulated with silicone to reduce stress on
the electronics, facilitate thermal dissipation, enhance waterproof
properties and ensure maximum reliability of the system via rigorous testing
methods including accelerated life testing. A 24/7 energy access through apps
or web-based portal facilitate remote diagnosis and maintenance.
In addition, it provides 97% peak efficiency. DS3D is a game changer for multi
residential and commercial PV rooftops.
Key Product Features:
- 2 input channels with independent MPPT and monitoring function
- Single unit connects to 4 modules
- Maximum continuous output power up to 2000W
- Engineered to match the highest power modules available (Max input current 20A)
- Encrypted ZigBee Communication
- Safety protection relay integrated
APsystems Microinverter System Installation
A PV system using APsystems Microinverters is simple to install. Each
Microinverter easily mounts on the PV racking, directly beneath the PV
module(s). Low voltage DC wires connect from the PV module directly to the
Microinverter, eliminating the risk of high DC voltage. Installation MUST
comply with local regulations and technical rules.
Special Statement: we advise installation of an RCD breaker only if required
by the local electrical code.
WARNING
- Perform all electrical installations in accordance with local electrical codes.
- Be aware that only qualified professionals should install and/or replace APsystems Microinverters.
- Before installing or using an APsystems Microinverter, please read all instructions and warnings in the technical documents and on the APsystems Microinverter system itself as well as on the PV array.
- Be aware that installation of this equipment includes the risk of electric shock.
- Do not touch any live parts in the system, including the PV array, when the system has been connected to the electrical grid.
NOTICE Even if not required by local electrical code, we strongly
recommend to install surge protection devices in the dedicated AC box.
4.1 Additional accessories supplied by APsystems
- AC Y3 Bus cable
- AC Y3 Bus Cable End Cap
- AC Y3 Bus Cable Y-CONN Cap
- AC Y3 Bus Cable Unlock Tool
- ECU
- AC connectors male/female
4.2 Other required accessories not supplied by APsystems
In addition to your PV array and its associated hardware, you may need the
following items:
- An AC connection junction box
- Mounting hardware suitable for module racking
- Sockets and wrenches for mounting hardware
4.3 Installation Procedures
4.3.1 Step 1 – Verify that grid voltage matches microinverter rating
4.3.2 Step 2 – Y3 AC Bus Cable distribution
a. Each connector drop of the AC Bus cable shall be matching the position of
the microinverter.
b. One end of the AC bus cable is used to access the junction box into the
power grid.
c. Wire the conductors of the AC bus: L – BROWN ; N – BLUE;PE – YELLOW GREEN.
WARNING Wiring color code can be different according to the local
regulation. Check all the wires of the installation before connecting to the
AC bus to be sure they match. Wrong cabling can damage irreparably the
microinverters: such damage is not covered by the warranty.
WARNING Do NOT carry the microinverter by the AC cable. This may cause
the AC cable to partially or fully disconnect from the unit, resulting in no
or poor operation . 4.3.3 Step 3 – Attach the APsystems Microinverters
to the Racking
a. Mark the location of the microinverter on the rack, with respect to the PV
module junction box or any other obstructions.
b. Mount one microinverter at each of these locations using hardware
recommended by your module racking vendor. WARNING
Install the microinverters (including DC and AC connectors) under the PV
modules to avoid direct exposure to rain, UV or other harmful weather events.
Allow a minimum of 1.5 cm (3/4’’) below and above the casing of the
microinverter to allow proper air flow. The racking must be properly grounded
as per local electrical code.
4.3.4 Step 4 – Ground the system
Y3 AC Bus cable has an embedded PE wire: this might be sufficient to ensure
proper grounding of the whole PV array. However in areas with special
grounding requirements, external grounding work may still be needed, using the
grounding lug supplied with the Microinverter. 4.3.5 Step 5 – Connect the APsystems microinverter
to AC bus cable
Insert the microinverter AC connector into the trunk cable connector. Make
sure to hear the “click” as a proof of robust connection. Best Practice: Use the Bus Cable
Unlock Tool of AC Bus to disconnect the connectors.
Figure 5
NOTICE
Check the microinverter technical data on page 20 to confirm maximum allowable
number of microinverters on each AC branch of the circuit.
AC connector interface as from left to right.
Figure 6
Cover any unused connectors with Bus Cable Y-CONN to protect the unused connectors.
Figure 7
4.3.6 Step 6 – Install a Bus Cable End Cap at the end of AC bus cable
Figure 8
4.3.7 Step 7 – Connect APsystems Microinverters to the PV Modules
Figure 9
NOTICE
Each channel connects 2 PV modules in series (For PV modules with Voc<60V).
The input channel will not work if connects to a single module(Voc<60V). That
means the quantity of PV modules in the sysem is even number.
NOTICE
When plugging in the DC cables, the microinverter should immediately blink
green ten times. This will happen as soon as the DC cables are plugged in and
will show that the
microinverter is functioning correctly. This entire check function will start
and end within 10 seconds of plugging in the unit, so pay careful attention to
these lights when connecting the DC cables.
WARNING
Double check to make sure all of the AC and DC wiring has been correctly
installed. Ensure that none of the AC and/or DC wires are pinched or damaged.
Make sure that all of the junction boxes are properly closed. WARNING
Each PV panel must be carefully connected to the same channel. Make sure to
not split positive and negative DC cables into two different input channels:
microinverter will be damaged and warranty will not apply.
4.4.8 Step 8 – Connect APsystems Microinverters to Grid
NOTICE
- Please install bi-polar circuit breakers with proper rated current or according to the local regulation, which are mandatory to connect to grid.
- Leakage current breakers or AFCI/GFCI breakers are not recommended to install.
4.4.9 Step 9 – AC Extension Cable
When AC extension cable is needed, users could connect the AC bus cable and AC
extension cable in a junction box or use a pair of male/female AC connectors
that APsystems provides as optional accessory.
4.3.10 Step 10 – Complete the APsystems installation map
a. Each APsystems Microinverter has 2 removable serial number labels.
b. Complete installation map by sticking ID label of each microinverter at the
right location.
c. The second serial number label, could be stuck on the solar module frame,
which could help later to confirm the position of the microinverter without
dismantling the PV module.
Figure 10
NOTICE
- The layout of the microinverters’ serial numbers installation map is only suitable for typical installation
- Installation Map is available in the last page appendix of this manual.
- Use ECU_APP (available in the EMA Manager) to scan the serial numbers on the map when setting up the ECU (see ECU instruction manual for more info).
Troubleshooting
Qualified personnel can use the following troubleshooting steps if the PV
system does not operate correctly:
6.1 Status Indications and Error Reporting
Assuming they are easily accessible and visible, Operation LEDs can give a
good indication of the microinverters status.
6.1.1 Start up LED
Ten short green blinks when DC power is first applied to the Microinverter
indicates a successful Microinverter startup.
6.1.2 Operation LED
Flashing Slow Green (5 sec. gap) – Producing power and communicating with
ECU
Flashing Slow Red (5 sec. gap) – Not producing power
Flashing Fast Green (2 sec. gap) – Not communicating with ECU over
60mins, but still producing power.
Flashing Fast Red (2 sec. gap) – Not communicating with ECU over 60mins
and not producing power.
Steady Red – default, DC side ground fault protection, see 6.1.3
6.1.3 GFDI Error
A solid red LED indicates the Microinverter has detected a Ground Fault
Detector Interrupter (GFDI) error in the PV system. Unless the GFDI error has
been cleared, the LED will remain red and the ECU will keep reporting the
fault. Please contact your local APsystems Technical Support.
6.2 ECU_APP
APsystems ECU_APP (available in the EMA Manager APP) is the recommended tool
to do on-site troubleshooting. When connecting the ECU_APP to the ECU hotspot
(please check ECU User Manual for more detailed information), installer can
check every microinverter status (production, communication) but also ZigBee
signal strength, grid profile and other insightful data helping the
troubleshooting.
6.3 Installer EMA (web portal or EMA Manager APP)
Before going on site for troubleshooting, installer can also check all
information remotely using his installer account, either on the web or using
the EMA Manager APP (see EMA Manager APP User Manual for more detailed
information). Having access to module data (DC, AC, voltages and currents)
gives the first indication on potential issues.
6.4 Trouble Shooting Guide
Professional installers can also refer to our Troubleshooting Guide
(https://emea.apsystems.com/resources/library/sectionlibraries) to have more
in depth guideline on how to troubleshoot and fix PV installations powered by
APsystems microinverters.
6.5 APsystems Technical Support
APsystems local Technical Support team is available to support professional
installers to get familiar with our products and to troubleshoot installations
when needed.
WARNING
Do not attempt to repair APsystems Microinverters. Please contact your local
APsystems Technical Support.
WARNING
- Never disconnect the DC wire connectors under load. Ensure that no current is flowing in the DC wires prior to disconnecting.
- Always disconnect AC power before disconnecting the PV module wires from the APsystems Microinverter.
- The APsystems Microinverter is powered by PV module DC power. AFTER disconnecting the DC power, when reconnecting the PV modules to the Microinverter, be sure to watch for the quick red light followed by ten short green LED flashes.
6.6 Maintenance
APsystems microinverters do not require any specific regular maintenance.
Replace a microinverter
Follow the procedure to replace a failed APsystems Microinverter
A. Disconnect the APsystems Microinverter from the PV Module, in the order
shown below:
- Disconnect the AC by turning off the branch circuit breaker.
- Disconnect the inverter AC connector from the AC Bus.
- Disconnect the PV module DC wire connectors from the microinverter.
- Remove the Microinverter from the PV array racking.
B. Install a replacement Microinverter to the rack. Remember to observe the
flashing green LED light as soon as the new Microinverter is plugged into the
DC cables.
C. Connect the AC cable of the replacement Microinverter to the AC bus.
D. Close the branch circuit breaker and verify proper operation of the
replacement Microinverter.
E. Update the microinverter in EMA Manager through “Replace” function and
update the system’s map with new serial number labels.
Technical Data
-
Be sure to verify that the voltage and current specifications of your PV module are compatible with the range allowed on APsystems Microinverter. Please check the
microinverter datasheet. -
DC operating voltage range of the PV module must be within allowable input voltage range of the APsystems Microinverter.
-
The maximum open circuit voltage of the PV module must not exceed the specified maximum input voltage of the APsystems.
DS3D Microinverter Datasheet
Model | DS3D |
---|---|
Region | BRAZIL |
Input Data (DC) | 1 |
Peak Power Tracking Voltage | 68V-90V |
Operating Voltage Range | 52V-120V |
Maximum Input Voltage | 120V |
Maximum Input Current | 20A x 2 |
Output Data (AC)
Maximum Continuous Output Power | 2000W |
---|---|
Nominal Output Voltage/Range¹ | 220V/176V-242V |
Adjustable Output Voltage Range | 170V-278V |
Nominal Output Current | 9A |
Nominal Output Frequency/ Range¹ | 60Hz/57.5-62Hz |
Adjustable Output Frequency Range² | 55Hz-65Hz |
Maximum Units per 6mm² Branch | 3 |
Efficiency
Peak Efficiency | 97% |
---|---|
CEC Efficiency | 96.70% |
Nominal MPPT Efficiency | 99.50% |
Night Power Consumption | 20mW |
Mechanical Data
Operating Ambient Temperature Range³ | -40 °C to +65 °C |
---|---|
Storage Temperature Range | -40 °C to +85 °C |
Dimensions (W x H x D) | 284mm X 234mm X 50.2mm |
Weight | 4.3kg |
AC Bus Cable | 6mm² (35A) |
DC Connector Type | Stäubli MC4 PV-ADBP4-S2&ADSP4-S2 |
Cooling | Natural Convection – No Fans |
Enclosure Environmental Rating | IP67 |
Features
Communication (Inverter To ECU) | Encrypted ZigBee |
---|---|
Isolation Design | High Frequency Transformers, Galvanically Isolated |
Energy Management | Energy Management Analysis (EMA) system |
Warranty | 15 Years Standard ; 25 Years Optional |
Compliances
Compliance| ABNT NBR 16149:2013; ABNT NBR 16150:2013;
ABNT NBR IEC 62116: 2012
---|---
- Nominal voltage/frequency range can be extended beyond nominal if required by the utility.
- Limits may vary. Refer to local requirements to define the number of microinverters per branch in your area.
- The inverter may enter to power de-grade mode under poor ventilation and heat dissipation installation environment.
- Recommend no more than 80 inverters register to one ECU for stable communication.
- To be eligible for the warranty, APsystems microinverters need to be monitored via the EMA portal. Please refer to our warranty T&Cs available on latam.APsystems.com.com.
2022/08/08 Rev1.2
© All Rights Reserved
Specifications subject to change without notice please ensure you are using
the most recent update found at web :
latam.APsystems.com
DS3D – Wiring Diagram
9.1 Sample Wiring Diagram – Single Phase
NOTICE
Each channel connects 2 PV modules in series (For PV modules with
Voc<60V).The input channel will not work if connects to a single
module(Voc<60V).
That means the quantity of PV modules in the sysem is even number.
APsystems Microinverter Installation Map
The APsystems Installation Map is a diagram of the physical location of each microinverter in your PV installation. Each APsystems microinverter has two serial number labels. Peel the one label and affix it to the respective location on the APsystems installation map. Installation Map Template
Installer:| PV module type: City:| Sheet of| N
---|---|---|---
Owner:| Microinverter type: City:
| Column 1| Column 2| Column 3| Column 4| Column 5| Column 6| Column 7
Row 1| | | | | | |
Row 2| | | | | | |
Row 3| | | | | | |
Row 4| | | | | | |
Row 5| | | | | | |
Row6| | | | | | |
Row 7| | | | | | |
Row 8| | | | | | |
Row 9| | | | | | |
Rowl0| | | | | | |
APsystems
APsystems Guadalajara:
AV. Lazaro Cardenas 2850-5º Piso, Colonia Jardines del Bosque
P. 44520, Guadalajara, Jalisco
TEL: 52 (33) -3188-4604
EMAIL: info.latam@APsystems.com
© All Rights Reserved
http://q-r.to/1OrC
Please scan this QR code to have access to our APPs and
Products information
References
- Home - APsystems EMEA
- APsystems Global | The global leader in multi-platform MLPE technology
- APsystems Latin America | El líder global en la tecnología multi-plataforma MLPE
- latam.APsystems.com.com
- EMEA Documents Library - APsystems EMEA
- Documents Library – APsystems Global | The global leader in multi-platform MLPE technology
- CENTRO DE DESCARGA - APsystems LATAM
- CENTRO DE DESCARGA - APsystems LATAM
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>