LUTRON Wireless Fixture Controls User Manual

June 7, 2024
Lutron

**LUTRON Wireless Fixture Controls User Manual

**

Limelight by Lutron Wireless Fixture Controls

The Limelight by Lutron radio sensor modules are radio-frequency (RF) control devices integrated into fixtures by OEMs. They control 0-10V electronic LED drivers in exterior (outdoor) fixtures such as those in parking garages and parking lots. They are often connected to a PIR sensor assembly to receive motion and daylight sensor signals. A Limelight Gateway is required to enable wireless fixture controls and sensor functions. A Limelight Gateway connects fixture controls and sensors into a high performance wireless system.

Features

  • Fixtures can be grouped together to turn an entire floor on at once to make sure parking areas have plenty of light available.
  •  Limelight by Lutron uses sensors to intelligently reduce power consumption and will email monthly reports of energy usage.
  • Radio Sensor Module is available with an internal antenna (inside the enclosure) (LL-EN-INTMOUNT), or with an output terminal for an external antenna (supplied) (LL-EN-INTMOUNT-A). An external antenna version does not require fixture RF validation.
  • Limelight by Lutron does not require wireless repeaters and typical jobs are completed with a single gateway. A cellular gateway option eliminates the need to get an Ethernet connection.
  • Single sign-on for Lutron interior and exterior controls when connected to Enterprise Vue.
  • Either an LL-EN-INTMOUNT or an LL-EN-INTMOUNT-A control device is integrated into the fixture with an (optional) LL-PIR sensor assembly.
  • Fully metallic fixtures generally integrate LL-EN-INTMOUNT- A. Fixtures with considerable plastic may use LL-EN-INTMOUNT.
Model Number Installation to Fixture Description
LL-EN-INTMOUNT-A OEM Limelight by Lutron Radio Sensor Module with External

Antenna
LL-EN-INTMOUNT| OEM| Limelight by Lutron Radio Sensor Module with Internal Antenna
LL-PIR-L| OEM| Limelight by Lutron PIR Sensor Assembly – for 8 to 15 ft (2.4 to 4.6 m) mounting height
LL-PIR-M| OEM| Limelight by Lutron PIR Sensor Assembly – for >15 to 30 ft (>4.6 to 9.1 m) mounting height
LL-PIR-H| OEM| Limelight by Lutron PIR Sensor Assembly – for >30 to 40 ft (>9.1 to 12.2 m) mounting height

System Components

Limelight by Lutron Enabled Luminaire

The Limelight by Lutron wireless radio sensor module (RSM) is integrated into a variety of luminaires. Fixtures with an integrated RSM can turn on/off and provide dimming capability using 0–10 V. A Limelight by Lutron enabled fixture requires no special communication wiring or special installation instructions. Installation is equivalent to a simple (non-Limelight) luminaire. When AC (120–277 V~) power is applied, the fixture powers up with a factory default setting of 100% light output until the Limelight by Lutron commissioning  process begins.

Contact Lutron for assistance in identifying current OEM fixture offerings for your application at 1.844.LUTRON1.

Limelight by Lutron System Compatibility

Lutron’s RSMs are compatible with the entire Limelight by Lutron product line and can be designed into Limelight systems with various modules. The same High Density Mesh technology is shared across Limelight by Lutron products allowing a network to be created between all Limelight modules. A Gateway serves as the communication hub between the RSMs, other modules, and the Web  User Interface. A Gateway can support up to 800 modules. Additional system details and other model numbers can be ound here:
http://www.lutron.com/en-US/Products/Pages/ WholeBuildingSystems/Limelight/Overview.aspx

Limelight by Lutron Radio Sensor Module (RSM)

Every RSM has a fully integrated wireless radio.
The radios use HDM (High Density Mesh) wireless technology to ensure extremely reliable, long-range performance in outdoor environments. These radios provide:

  • A robust, redundant communications scheme.
  • Communication among multiple floors above or below in parking facilities.

Each radio communicates to the “neighbor” radios around it, creating a high- density mesh.

This redundant communications system enables Limelight by Lutron to be self- healing. If a radio ever stops functioning or is vandalized, the other radios will immediately search out and establish communication with other neighbors in the mesh. This high-density  mesh system enables the Limelight by Lutron control system to operate smoothly even in the most difficult conditions

  • Motion Sensor: LL-PIR, a passive infrared motion sensor, is an optional addition to OEM fixtures with LL-EN-INTMOUNT and LL-EN-INTMOUNT-A
    • Maximizes motion sensor coverage.
    • Captures all sensing activity (time of day and fixture number) in a centralized database for activity reporting and analysis.
  • Daylight Sensor: Daylight harvesting capabilities are supported.
    • Measures daylight every 15 minutes (programmable).
    •  Measures foot candles per fixture to analyze for maximum harvesting capability.

Specifications

Limelight by Lutron
Radio Sensor Module (RSM) with Internal or External Antenna

Model

  • LL-EN-INTMOUNT with internal antenna
  • LL-EN-INTMOUNT-A with external antenna

Standards

  • RoHS Compliant
    cULus Recognized for internal mounting at a fixture OEM

  • FCC 15.247/IC RSS-247

Power Requirements

  • Input power: 120–277 V~ (± 10%) 50/60 Hz (phase-to-phase possible)
  • Device consumption: 1.0 W (load enabled)0.5 W (load disabled)
  •  Maximum Load: 5 A at 120 V~ (600 W)3.65 A at 277 V~ (1000 W)

Operating Temperature

  •  -40 °F–158 °F (-40 °C–70 °C)

Features

  • Power Measurement: Accurate to + / – 5% with  loads above 10 W
  • Non-class 2 isolated 0–10 V- dimming output, capable of sinking up to 1.0 mA of 0–10 V- signal
  • On board temperature sensor accurate to + / –2 ˚C
  • 4-pin terminals for remote connection to LL-PIR
  • Works with ballasts and drivers whose inrush current does not exceed NEMA410 standards forelectronic ballast / driver
  • Integrated HDM radio transceiver
    •  IC and FCC approved Title 47 Part 15 Subpart B and Subpart C section 15.247 for Digital Transmission Systems Operating within the band 2400-2483.5 MHz
    •  RF transmissions security: 128 AES plus application layer
  • Can be configured to control non-dim loads

OEM Integration

  • All fixtures integrated with LL-EN-INTMOUNT have an internal antenna and are required to undergo Lutron’s RF validation test detailed in the “Limelight by Lutron OEM Integration Guide” (P/N 041684) at https://www.lutron.com/en-US/pages/default.aspx
  • All fixtures integrated with LL-EN-INTMOUNT-A are supplied with an external antenna* that must be used in fixture integration. They do not require additional RF validation testing, provided the antenna is installedby following  requirements in the “Limelight by Lutron OEM Integration Guide”  (P/N041684) at https://www.lutron.com/en-US/pages/default.aspx
  • All fixtures require an IP65 or UL Wet Location rating

Water Ingress

  • The antenna supplied with LL-EN-INTMOUNT-A is rated to IP65 and UL Wet Location standards.

Warranty

Model

  • LL-PIR-(L/M/H)

Standards

  • cULus Recognized (for internal mounting at a fixture OEM)
  • IP65 and UL Wet Location capable (when lens assembly is installed correctly at OEM on a fixture with corresponding water ingress ratings)

Power

  • 2.7–3.3 V- (Non-Class 2 isolated supply provided by LL-EN-INTMOUNT/LL-EN-INTMOUNT-A)
  • 50 mW maximum (20 mW typical)

Operating Temperature

  • -40 °F–158 °F (-40 °C–70 °C)
  • Significantly hot or cold temperatures can substantially reduce the sensitivity of motion sensors.

Motion Sensor Assembly

  • UL rated silicone washer for water and dust seal (rated for IP65 and UL Wet Locations)
  • Threaded nut for secure fit
  • 4-wire harness with low profile connector (10 in [254 mm])

Warranty

Features

  •  Energy savings from motion sensing
  • Small footprint allows it to fit almost anywhere
  • Wide or narrow field of view with wireless settings adjustment
  • Wirelessly choose between multiple sensitivity profiles to optimize settings for various environments (flat lot, parking deck, high wind, various heights 8–40 ft [2.4–12.2 m])
  •  Integrated Daylight Sensor measures light up to 1500 fc
  • Built in LED to provide user feedback when motion is detected
  • Wireless field re-programmable
  • Recommended mounting heights (8–40 ft [2.4–12.2 m])
    •  Low: 8–15 ft (2.4–4.6 m) (ex. parking garage)
    •  Medium: >15–30 ft (>4.6–9.1 m) (ex. pole lights)
    • High: >30–40 ft (>9.1–12.2 m) (ex. specialty poles)
  • Motion detection can be disabled (disabled by default, requires system activation to enable)
    • Daylight Sensor can be disabled independently of motion detection  (disabled by default, requires system activation to enable)

OEM Integration

  • LL-PIR is an optional sensor that can be integrated when accompanied by an LL-EN-INTMOUNT orLL-EN-INTMOUNT-A
  • All fixtures require an IP65 or UL Wet Location rating.

Dimensions

Dimensions shown as in (mm)

  1. LL-EN-INTMOUNT
    Dimensions

  2. LL-EN-INTMOUNT-A
    Dimensions

  3. LL-PIR-(L/M/H)
    Dimensions

  4. LL-PIR-L Lens
    Dimensions

  5. LL-PIR-M Lens
    Dimensions

  6. LL-PIR-H Lens
    Dimensions
    Dimensions

Note: Adherence to specified maximum fixture thickness is required to maintain IP65 and UL Wet Locations ratings. See P/N 041684 for more details at https://www.lutron.com/en-US/products/pages/ wholebuildingsystems/limelight/overview.aspx

Limelight External Mount Antenna

  • Antenna cable length = 18 in (457.2 mm)
  • Antenna opening size = 0.6875 in (17.5 mm)

Note: Antenna cable extensions are not supported.

Wiring

  • Wiring Diagram (LL-INTMOUNT / LL-PIR)
    Wiring

  • Wiring Diagram (LL-EN-INTMOUNT-A / LL-PIR)
    Wiring

Note: 0-10 V LED drivers used with these products must support switching power to turn on/off.

Coverage

All units on the graph are shown in ft (m)

Limelight by Lutron PIR

Limelight by Lutron PIR can be configured wirelessly to have different sensitivity levels depending on its environment.

  •  Sensor sensitivity can be adjusted (in the software) to reduce coverage.
  • Significantly hot or cold temperatures can substantially reduce the sensitivity of motion sensors.
  • Mounting height greater than 15 ft (4.6 m) reduces the likelihood of a motion sensor detecting a pedestrian. Sensors for pole mounted area fixtures are intended to detect vehicular motion.
  • Insufficient spacing between fixtures can create gaps in motion  sensor coverage where motion will not be detected.
  1. Height: 8 ft (2.4 m), LL-PIR-L
    Coverage

  2. Height: 20 ft (6.1 m), LL-PIR-M
    Coverage

  3. Height: 40 ft (12.2 m), LL-PIR-H
    Coverage

Technical System Overview

Log in using Enterprise Vue (sold separately) or access directly via www.limelightbylutron.com website (included with system).

Web-Based Interface Capabilities

  •  Turn all fixtures on (via override) with a single button
  • Run diagnostics on a fixture
  • Check fixture status and identify errors
  • Flash any fixture
  • See the total number of connected luminaries
  • Group fixtures
  •  Change system settings (time clocks, motion sensing groups, light levels, and more)
  • View a live map showing the status of all fixtures
  •  Perform manual overrides

Gateway

  • Wireless high-density mesh to luminaries
  • Cellular or Ethernet to the cloud
  • Wall-mounted inside a facility utility closet

Limelight by Lutron Enabled Luminaire

  • Each luminaire is shipped with the Limelight by Lutron radio and sensor (optional) integrated into the luminaire
  • A retrofit (external mount) is also available
  • Each Limelight by Lutron sensor has motion and daylight sensing
  • Up to 800 luminaires controlled by a single Gateway as long as no other range  restrictions are violated *

Web-based Interface

  • Standalone system (www.limelightbylutron.com)
    OR

  • Connect to Enterprise Vue for single login and navigation. See the Enterprise Vue Software spec submittal (3691076) at www.lutron.com for more information.

Wireless Range Best Practices Diagram

Wireless Range Best Practices

RF range recommendations| Parking Garage (except open top level)| Flat Lot (or open top level of parking garage)
---|---|---
3 nodes within this distance of the Gateway| 50 ft (15.2 m)| 150 ft (45.7 m) horizontal (LL-EN-INTMOUNT)
300 ft
(91.4 m) horizontal (LL-EN-INTMOUNT-A)
Max distance from the Gateway to any one node| 500 ft (152.4 m) horizontal / 4 floors vertical| 3000 ft (914.4 m) horizontal (both node types)
Max distance from node to node| 50 ft (15.2 m) horizontal / 1 floor vertical| 150 ft (45.7 m) horizontal (LL-EN-INTMOUNT)
300 ft (91.4 m) horizontal (LL-EN-INTMOUNT-A)
Gateway proximity to dense metal obstructions (including electrical panels)| Minimum 2 ft (0.6 m) away| Minimum 2 ft (0.6 m) away
Max number of luminaires controlled by a single Gateway| Up to 800| Up to 800

If the gateway is not at or above ground level or there is more than one wall between the gateway and nodes, the 50 ft (15.2 m) spacing guideline should be used.

SPECIFICATION SUBMITTAL

Job Name: __
Job Number:

Model Numbers: ____   
____     

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals