rotronic 1434017 CO2-Display Carbon Dioxide Detector Instruction Manual
- June 6, 2024
- ROTRONIC
Table of Contents
CO2-DISPLAY
Short Instruction Manual
GENERAL DESCRIPTION
This CO2 panel is an accurate wall mount and desktop data logger that displays and records the relative humidity, temperature and CO2. Date and time is additionally displayed.
PROGRAMMING
Most of the settings, such as memory clear, CO2 status indicator, units (°C/°F), sampling rate, pressure compensation and real-time clock can all be changed using the function keys.
POWER SUPPLY
The CO2 panel uses 12 VDC power adapter, which is included in the package.
DISPLAY
GOOD CO2value is in the “GOOD” range 2
NORMAL CO2 value is in the “NORMAL” range
POOR CO2 value is in the “POOR” range
% Unit of relative humidity
°C/°F Unit of temperature (Celsius/Fahrenheit)
REC Blinking in automatic logging mode
USB STICK CONNECTION
Recorded data can be easily downloaded to a USB stick and saved as *.XLS file. Easily analyze the recorded data through the free software HW4 or through Excel.
FUNCTIONS KEYS
START/ESC| • “START”, Press longer to start automatic logging mode
(REC is blinking)
• “ESC”, Press longer to stop logging mode
• “ESC”, Exits setup and calibration mode
---|---
SET| In normal mode, press longer to enter setup mode
UP| Press to select a unit or increase value in setup mode
DOWN / DOWNLOAD| • Press to select a unit or decrease the value in setup
• Press longer to download data to a USB stick
OPERATION
POWER ON/OFF
Once the 12VDC power adaptor is connected, the device will be automatically powered on. At power-on, it performs 30 seconds countdown for device warm-up, then enters normal mode with a real-time clock displayed. To power off, unplug the power adaptor.
DATE/TIME SETUP
When the device is powered on, hold down the “SET” key for 2 seconds until
entering device setup mode. Press “UP” or “DOWN” key to select the program (P
50, displayed in the right-middle panel) and press “SET” key to enter.
First, choose the time format as 24 hour or 12 hours by press the “UP” or
“DOWN” key and then pressing “SET” key to confirm. Now, start to input the
real-time clock value from year, month, day, hour to minute. Press the “UP” or
“DOWN” key to adjust and then press the “SET” key to confirm. After the date
and time are set, a clearance of the memory must be performed. Press the “UP”
or “Down” key to select P 10 and press the “SET” key to enter P11. Press the
“UP” or “Down” key to choose “YES” to clear previous memories and press “SET”
to confirm. Then, press the “ESC” key twice to return to normal mode.
UNIT SETUP
Hold down “SET” key for 2 seconds until entering meter setup mode. Press “UP” or “DOWN” key to select the program P 30 and press “SET” key to enter. Press “UP” or “DOWN” key to select °F or °Cand the press “SET” key to confirm. Press “ESC” key to return to normal mode.
TAKING MEASUREMENT
The device starts measurement when power on and updates readings every second.
CO2 CONDITION INDICATOR
The meter features a light bar indicator to have user easily recognize the indoor air quality. (See “Meter Setup” section for setting Normal & Poor threshold).
DATA LOGGING
The meter can automatically record readings of CO2/TEMP./RH for long time
environment monitoring. The memory capacity is 6000 points for each parameter.
Users can set up sampling rate from 1 minute to 12 hours and 59 minutes. The
factory default rate is 1 minute.
First, setup the data record mode you need. Hold down “SET” key for 2 seconds
until entering meter setup mode. Press “UP” or “DOWN” key to elect the
program P 10 and press “SET” key twice to enter P12. In P12, select the data
record mode as “STOP” or “LOOP”. Press “UP” or “DOWN” key to select and then
press “SET” to confirm.
“STOP”: The device stops logging while the memory space is full.
“LOOP”: After the memory is full, it starts to overwrite the oldest data.
Second, setup the sampling rate. Once finishing the P12 and press “SET” key,
it enters P13. Press “UP” or “DOWN” key to adjust the sample rate from hour
to minute and press “SET” key to confirm. Press “ESC” key to return to normal
mode. After sampling rate setting and data record mode are completed, press “
START” key for 2 seconds under normal mode to start logging. The “REC” LED
turn into green and flash on panel to indicate the logging is in process.
To terminate data logging, press “ ESC” key for 2 seconds and green LED light
vanish. Repeat above to start another run of logging. If the data record mode
is programmed as “STOP”, “REC” LED turn into red color and flash while the
logging memory space is full.
MEMORY DOWNLOAD
The meter features logged memory download function by using a USB stick
instead of connecting it with a computer. Before download, press “ESC” key
for 2 seconds to stop the logging. Plug USB stick (max. 8GB memory) to USB
slot on device left side, hold down “DOWN” for more than 2 seconds until
seeing ” USb” appears on panel and then “USb” starts flashing on panel to
indicate the downloading is in process. It will take minutes to fully download
the memory. The data downloading time depends on memory size and USB stick.
The download data is saved as *.XLS file in USB stick. Using free Rotronic
software HW4 or Excel to analyze the data. Suggest formatting your USB stick
as FAT32 before using. If error code E60 ~ E65 appears on panel, suggest
trying another model of USB memory stick.
Attention: In some cases when the size of the logged memory is large, it can happen that the display shows an error code (E60 – E65). Check the USB memory stick, the data transfer usually works. If not, repeat the process.
METER SETUP
Hold down “ SET” key for more than 2 seconds until entering setup mode. To exit setup, press “ESC” to return to normal mode. The available meter setup program is shown in below. Press “UP” or “DOWN” key to select the program (P10, P20, P30, P40 or P50) in the main menu and press “SET” key to enter the sub-menu. Press “SET” key to select different sub-menu (P11, P12, P13 or P14), programmable setting then flashes on panel. Press “UP” or “DOWN” key to adjust and press “SET” to confirm. To leave without saving, press “ESC” key to return.
P 10 (Lo9) Logging related setup| Note:
•DONE: displayed while memory is cleared
•STOP: Stop while memory is full
•LOOP: Overrides oldest values when
Note:
•Factory preset at 1 minute
•The format is Hour: Min
---|---
P 11 (CLr), Clear logging memory Choose YES/NO
memory is full
P12 (End), Data record mode
Choose STOP/LOOP
P13 & P14 (rATE), Logging sampling rate Choose from 00:01 to 12:59
P 20 (CO2) CO2 related setup| Note:
•Adjustable level is 400 to 1700 ppm
preset at 1000 ppm
•Adjustable level is 1000 to 2000 ppm
preset at 1700 ppm
•ABC preset as ON
P 21 (Nor) lower limit of “NORMAL” icon
P 22 (Poor) lower limit of “POOR” icon
P 23 (AbC) ABC function on/off
P 30 (uniT) Temperature unit setup| Note:
•Factory preset °C
P 31, choose °C/°F
P 40 (PrES) Pressure compensation| Note:
•Factory preset at 1013 hpa
•The adjustable scale is every 1 hpa
P41 (hPA) Choose from 700 to 1990 hpa
P 50 (rTC) Real-Time Clock setup| Note:
•Factory preset at 12 H
•Factory preset at 2013.01.01, 12:00
P 51 choose 12 or 24 hour format
P 52-54 Input Year/Month/Day
P 55-56 Input Hour/Minute
HUMIDITY CALIBRATION
This meter can be calibrated either via 35 % rH & via 80 % rH humidity
standards. The ambient condition is recommended as stable 25 °C.
Caution: Do not calibrate the humidity without the default humidity
standards. Otherwise, it will cause permanent damage. Contact Rotronic for
humidity standards or services. Single point calibration will cause error code
E11 or inaccurate reading. Always do dual point calibration to complete a
process. Suggest starting calibration from low humidity.
Pull out the humidity probe from panel
Before calibration, pull out the humidity probe from the cover in the panel
rear side.
CALIBRATION VIA HUMIDITY STANDARDS
Power on the device, plug the sensor probe into 35% humidity standard. Press
“SET” +”START”+” DOWN” keys simultaneously for 3 seconds to enter calibration
mode. Press “UP” or “DOWN” key to select 350 (35.0% calibration) and press
“SET” to start. “Calibrating value” (35.2% if at 25°C) is blinking on the
LCD.
Waiting for 60 minutes to complete the 35% calibration. To quickly save, press
“SET” key any time.
800 (80.0% calibration) comes right after 35% calibration is done. Within 20
minutes, press “SET” key to start 80.0% calibration. “calibrating value” are
blinking on the LCD. Waiting for 60 minutes to complete the 80% calibration.
To quickly save, press “SET” key any time. Now, the device is well calibrated.
To abort without saving, press “ESC” to quit without saving.
CO2 CALIBRATION
Caution: Do not calibrate the meter in the air with an unknown CO2 concentration. Otherwise, it will be wrongly calibrated and lead to inaccurate measurements.
The meter can be calibrated in fresh outdoor air (on a sunny day) at 400 ppm CO2. Besides the 400 ppm, the meter can also be calibrated at 0 ppm or any value under 990 ppm. The latest calibration point is treated as final and the meter will ignore the previous calibration data.
Press “SET” +” START”+” DOWN” keys simultaneously for 3 seconds to enter
calibration mode. Press the “UP” or “DOWN” key to select 400 (400 ppm) or 0 (0
ppm) CO2 calibration. 0 ppm function is only for 0ppm CO2 calibration. For
other CO2 values, please choose 400 ppm and press SET” to enter. Once
choosing the calibration value, 2 press SET to start and see “CAL” and CO2
value blink on LCD.
Wait about 10 minutes until the blinking stops to indicate the calibration is
complete
To abort calibration without saving, press “ESC” at any time.
TROUBLESHOOTING
Error | Messages | Solution |
---|---|---|
0.00E+00 | The CO2 sensor is out of order | Turn off meter and re-start again |
0.00E+00 | The CO2 sensor is out of order | Retry CO2 calibration |
0.00E+00 | The measured value is under a range | Put meter in normal condition |
0.00E+00 | The measured value is over a range | Put meter in normal condition |
Ell | RH calibration error | Retry humidity calibration |
0.00E+00 | Temp. sensor or AD damaged | Return for repair |
0.00E+00 | Memory IC damaged | Return for repair |
0.00E+00 | RH sensor or circuit damaged | Return for repair |
E60-E65 | USB download error | Suggest to format USB stick or try a new type of |
memory stick.
TECHNICAL DATA
Humidity/accuracy | 0.1-99.9 %/±3 %(10-95 %@25 °C). ±5 %(others) |
---|---|
Temperature/accuracy | 0…50 °C/±0.3 °C@5-40 °C |
CO2 /accuracy | 0…9999 ppm/±(30 ppm+5% of reading)@0-5000 ppm |
Storage and transit | -20…60 °C/10…90 %rh, non condensing |
Operating limit at electronics | 0…50 °C |
Memory | 6000 records auto logging for each parameter |
Dimension, mm | 330(L) x 250(W) x 50(H) |
Weight | 1400 g |
Power consumption | Max. 0.7 A |
DC power type | 12 V DC |
PC connection | USB stick |