rotronic HF5A High End HVAC Humidity and Temperature Transmitter Instruction Manual
- June 9, 2024
- ROTRONIC
Table of Contents
rotronic HF5A High End HVAC Humidity and Temperature Transmitter
Analog & Digital transmitter for humidity and temperature Wall Version
Congratulations on your purchase of the new state-of-the-art HygroFlexAdvanced 5-Series transmitter. Please read these short instructions carefu lly before install-ing the device.
GENERAL DESCRIPTION
The HygroFlexAdvanced 5-Series devices are universal transmit-ters for the transmission of humidity and temperature measure-ments. Compatible with all interchangeable HC2A probes. These short instructions are limited to a description of the main fu nctions and installation of the device. The detailed instruction manual can be found on ProcessSensing.com or by scanning the QR code.
DIMENSIONS / CONNECTIONS
MECHANICAL INSTALLATION
GENERAL RECOMMENDATIONS
Relative humidity is extremely temperature-dependent. In order to measure it precisely, the probe and sensors must be set exactly on the temperature level of the environment to be measured. The installation site can therefore have a significant influence on the performance of the device. Follow the guidelines below to ensure optimum performance:
- Select a representative installation site: Install the probe at a point where the humidity, temperature and pressure conditions are representative for the environment to be measured.
- Ensure sufficient air movement around the probe: An air flow of at least 1 meter/second accelerates and facilitates adjustment of the probe to changing temperatures.
- Avoid:
- Probe too close to heating elements, cooling coils, cold or hot walls, direct sunlight, etc.
- Probe too close to steam, injectors, humidifi ers or direct precipitation.
- Unstable pressure conditions with high air turbulence.
- Insert the probes as far as possible into the environment to be measured.
- Avoid accumulation of condensation at the contact wires of the sensor. Install the probe so that the tip points down. If that is not possible, install it in a horizontal position.
MOUNTING THE WALL VERSION
Alignment
Mount the transmitter so that the probe points down.
Mounting variant 1 (Drilling Plate)
Drill the necessary holes using the additional drill template printed on the
packaging. Then insert the plugs delivered with the device and mount the
transmitter with the screws.
MOUNTING THE WALL VERSION WITH A STANDARD PROBE
To avoid measurement errors, the probe should be inserted into the environment to be measured. If necessary, use the respective extension cable and mounting flange to install the standard probe:
Mounting flange | Probe diameter | Temperature range |
---|---|---|
AC5005 | 15 mm | 100 °C |
MOUNTING THE WALL VERSION WITH AN INDUSTRIAL PROBE
To avoid measurement errors, the probe should be inserted into the environment to be measured. If necessary, use the mounting flange to install the industrial probe:
Mounting flange | Probe diameter | Temperature range |
---|---|---|
AC1305 (AC1303-M) | 15 mm | 200 °C |
ELECTRICAL INSTALLATIONS
3-OR 4-WIRE SETUP
The new HygroFlex Advanced 5-Series HF5A-3 and HF5A-D can be used as a 3-wire and galvanically isolated 4-wire. With the additional Jumper J1, located on the PCB and indicated in section 4.4, can be chosen over 3-wire or 4-wire.
Default: 3-wire – J1 mounted, to change to 4-wire simply open up the transmitter and remove Jumper J1.
Recommendation Rotronic: 4-wire galvanically separated with unmounted Jumper J1 – with the benefit that the power supply and the outputs are separate galvanically isolated.
SUPPLY VOLTAGE / TECHNOLOGY
Type| Supply voltage| Load| Output
2- or 2×2- wire
HF5A-2| 18…36 VDC *| Max. 500 Ω| 4…20 mA
3- or 4-wire: 3 wire – J1 mounted
(Default) / 4 wire – Galvanically separated –
J1 unmounted
HF5A-3| 18…36 VDC| Max. 500 Ω| 4…20 mA
Max. 500 Ω| 0…20 mA
Min. 10 kΩ| 0…5 V
Min. 10 kΩ| 0…10 V
HF5A-D| Max. 500 Ω| 4…20 mA
Max. 500 Ω| 0…20 mA
Min. 10 kΩ| 0…5 V
Min. 10 kΩ| 0…10 V
–| Digital RS485
- V min = 0.024 mA Rload = 0.024 500Ω = 12 V
** ¾-wire Current Outputs: Output current monitoring from 100 Ω load guaranteed
TERMINAL CONFIGURATION / CONNECTION DIAGRAMS
The type is defined using the table Supply Voltage / Technology to then use the following connection diagrams:
PROGRAMMING
The basic settings of the devices are made in the factory. Customer-specific setting can be made via the HW5 soft ware together with an NFC to USB interface. The soft ware HW5 can be downloaded on the internet at: ProcessSensing.com.
The NFC interface is not password protected and can be used with the necessary
NFC-USB-READER and the soft ware HW5. Manipulations can be prevented by means
of activation of the write protection function, which can be set in the soft
ware HW5.
SCALING / FIRMWARE UPDATE / ADJUSTMENT
The following settings can be made with the help of the HW5 soft ware and an NFC to USB interface:
- New scaling of the outputs
- Firmware update
- Adjustment of a mounted Probe
LED STATUS MODE
The HF5A has a mounted LED on the front of the transmitter to indicate the actual status of the transmitter. Per default the simple LED status mode is activated:
- Green = Normal operation
- Orange = Simulation mode activated
- Red = Alarm (Error)
Further information about the simple and the detailted LED Status Mode can be found in the detailed HF5A manual (or by scanning the QR-Code).
PERIODIC CALIBRATION OF THE PROBE
Both the probe and the corresponding electronics are very stable and do not
normally need to be changed or calibrated after factory calibration. The long-
term stability of the Rotronic Hygromer humidity probes is typically better
than 1 %rh per year. For maximum accuracy we recommend calibration of the
probe about every 6 to 12 months.
More frequent calibration can be necessary in applications where the sensor is
exposed to pollutants. The calibration can be performed by the user himself on
site or in the laboratory / workshop. For routine calibrations the probe
should be checked at one or two points.
Technical data (Electronics operating range)
Temperature| Models with display: -10…60 °C / without display: -40…70 °C
Humidity| 0…100 %rh, non-condensing
Technical data (Mechanics)
Housing| Bottom: ABS Top: PMMA
Technical data probe
Depending on probe
DELIVERY PACKAGE
- Transmitter HF5A
- Screws and dowels together with drill template
- Short instruction manual / functional certifi cate
- Additional type plate and QR plates
References
- Measurement Devices & Monitoring Solutions Humidity Dewpoint etc. | PST
- Measurement Solutions - Humidity, Temperature, CO2 and Differential Pressure Measurement (EN_US)