IMI Hydronic Engineering STAD-C Balancing Valve Installation Guide

October 27, 2023
IMI Hydronic Engineering

STAD-C Balancing Valve
Installation Guide
309 734-01

09.2014

STAD-C Balancing Valve

Rekommenderad installation
  Aanbevolen installatie
IMI Hydronic Engineering STAD-C Balancing Valve - 3IMI Hydronic Engineering STAD-C Balancing Valve -
4 STAD-C

Fig. 1. Valve closed.
Fig. 2. Opened 2.3 turns.
Fig. 3. Fully open valve.

Presetting

The presetting of a valve for a certain pressure drop e.g. corresponding to the presetting position 2.3 should be carried out as follows:

  1. Close the valve fully (Fig. 1).
  2. Set the valve at position 2.3 (Fig. 2).
  3. Using a 3 mm Allen key, turn the inner spindle clockwise until stop.
  4. The valve is now preset.

A pressure drop diagram is available for each valve size, showing the pressure drop curves for various settings and flows.
→ = Recommended direction of flow for best accuracy.

Measuring

The measuring points are double-secured. When measuring (fig 4):

  1. Connect the measuring hoses.
  2. Open the measuring points 0.5-1 turn with a 13 mm key.
  3. Close the measuring points after finished measuring.
  4. Disconnect the measuring hoses.

STAD-C Solder

When soldering cover valve body with wet cloth to prevent pre- mature deterioration of the internal valve components. Solder the valve body to the pipe, using silver solder.

We reserve the right to introduce technical alterations
without previous notice.
www.imi-hydronic.com

Documents / Resources

| IMI Hydronic Engineering STAD-C Balancing Valve [pdf] Installation Guide
STAD-C Balancing Valve, STAD-C, Balancing Valve, Valve
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

IMI Hydronic Engineering User Manuals

Related Manuals