IMI Hydronic Engineering DN 65-125 TA-Smart 2-Way Control Valve Instruction Manual

June 12, 2024
IMI Hydronic Engineering

IMI Hydronic Engineering DN 65-125 TA-Smart 2-Way Control Valve Instruction Manual
IMI Hydronic Engineering DN 65-125 TA-Smart 2-Way Control
Valve

  • Intendend use: For measuring and control in heating and cooling systems.
  •  The water quality requirements described in VDI2035 should be respected
  • TA-Smart can be cleansed with a damped cloth and a lenient cleaning agent.
  • Insulated wires and cables shall retard flame propagation with a flammability RATING of UL 2556 VW-1 or equivalent.

24 VAC/VDC operating only with safety isolating transformer according EN 61558-2-6.
Electra Instructions

Service/Repair

IMI Hydronic Engineering

If the TA-Smart is used in any other application than specified by IMI Hydronic Engineering the protection provided by the equipment may be impaired.
Installation Instructions
Installation Instructions
Installation Instructions

We reserve the right to introduce technical alterations without prior notice

Technical specifiactions valid at an altitude of max. 2000 m

-20°C – +70°C (-4°F – +158°F) (5-95%RH, non-condensing

0°C – +50°C (32°F – +122°F) (5-95%RH, non-condensing

  • Input signal
  • Output signal
  • Control mode
  • Flow setting
  • Media
  • Characteristic

Symbols

BACnet MS/TP, BACnet IP, Modbus RTU, Modbus TCP

Proportional
0(2)-10 VDC 47 kΩ 0(4)-20 mA, 500 Ω

Power supply
24 VAC +6%/-10%, 50/60 Hz ±15% 24 VDC +15%/-10%

Power consumption

  • Operating
    DN 65-80: < 5.8 W (24 VDC); < 10 VA (24 VAC).
    DN 100-125: < 7.7 W (24 VDC); < 10.8 VA (24 VAC)

  • Standby

EN 61010

Contains Transmitter Module FCC ID: X8WBC840M

-10°C – +110°C (14°F – +230°F)
Water and water-glycol mixtures (0-57%)

PN 16/25 (Class 150)

DN PN 16 D [mm] L [mm] H [mm]
65 185 4 290 377
80 200 8 310 380
100 220 8 350 438
125 250 8 400 444

Dimensions
Dimensions
Instruction
Instruction

Art. No

DN 65-80 G1/4 322230-00400 L = 30 mm (1.18 in.)
DN 100-125 G3/8 322230-00402 L = 58 mm (2.28 in.)

Installations instructions
Installations instructions
Installations instructions
Installations instructions
Installations instructions

Pipe L Lt D
65-80 (2 1/2” – 3”) <15 mm<0.59 in. <22 mm<0.87 in. G1/4
100-125 (4” – 5” <30 mm<1.18 in. <22 mm<0.87 in. G3/8

Installations instructions
Installations instructions
Installations instructions
Installations instructions
Installations instructions
Installations instructions
Installations
Tools

Wiring diagrams

Terminal Description
L24 Power supply 24 VAC/VDC.
M* Neutral for power supply 24 VAC/VDC and signals.
XV Output signal 0(2)-10 VDC, max. 8 mA or min. load resistance 1.25 kΩ.
M (0V)* Neutral for signal.
Y Input signal 0(2)-10 VDC, 47 kΩ or 0(4)-20 mA, 500 Ω (selectable by jumper

XX).
Ethernet|
RX –| Ethernet connector wire position 6
RX +| Ethernet connector wire position 3
TX –| Ethernet connector wire position 2
TX +| Ethernet connector wire position 1
RS485|
A| RS485 Data +
B| RS485 Data –
M (0V)*| Neutral for signal.

USB Only for IMI use.
Serial Debug Only for IMI use.
All M terminals are internally connected.

Standard
Standard

24 VAC/VDC operating only with safety isolating transformer according EN 61558-2-6

Modbus RTU
Modbus RTU

Note:

  1. A, B and M terminals are NOT isolated from all other terminals.
  2. GND (M – 0V) is common to power supply, analog signals and RS 485.
  3. In case of AC power supply, L24 and M should be connected to the same phase for each TA-Smart.
  4. GND (0V) of RS 485 should be connected to 0 VAC/VDC on the controller side.
  5. GND (0V) of analog input/output should be connected to 0 VAC/VDC on the controller side.

24 VAC/VDC operating only with safety isolating transformer according EN 61558-2-6

Modbus TCP
Modbus TCP

Note:
Ethernet cable shall be Cat 5e or Cat 6 cable. Wire colour indication is for T568B pinout.

24 VAC/VDC operating only with safety isolating transformer according EN 61558-2-6.

LED

Instructions

LED Colour Description
**** Green – – – – – Status OK
Green – – – – – – – – – – Initiating (start up)
Red – – – – – Error (→ HyTune, Cloud, Bus)
Off No power supply
**** Blue –––––––––– Bluetooth active
Blue – – – – – Bluetooth active (no device connected)
Off Wireless disactivated (or no power supply)
**** Green –––––––––– Ethernet connected
Green – – – – – – – – – – Data being transferred (Ethernet or RS485, if

Ethernet not connected)
Off| | Ethernet and RS485 not connected (or no power supply)

Operation

Calibration

Identification

HyTune app

For setting of control parameters use HyTune app.

App Store Icon

Instructions

We reserve the right to introduce technical alterations without prior notice.