Z-KEY, Z-KEY-P Profinet IO Gateways
Installation Guide INSTALLATION MANUAL
Z-KEY
Z-KEY-P
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that
put the user’s safety at risk.
The word ATTENTION preceded by the symbol indicates conditions or actions that
might damage the instrument or the connected equipment. The warranty shall
become null and void in the event of improper use or tampering with the module
or devices supplied by the manufacturer as necessary for its correct
operation, and if the instructions contained in this manual are not followed.
| WARNING: The full content of this manual must be read before any
operation. The module must only be used by qualified electricians. Specific
documentation is available via QR-CODE shown on page 1.
---|---
| The module must be repaired and damaged parts replaced by the Manufacturer.
The product is sensitive to electrostatic discharges. Take appropriate
measures during any operation.
| Electrical and electronic waste disposal (applicable in the European Union
and other countries with recycling). The symbol on the product or its
packaging shows the product must be surrendered to a collection centre
authorized to recycle electrical and electronic waste.
CONTACT INFORMATION
Technical support
support@seneca.it
Product information
sales@seneca.it
This document is the property of SENECA srl. Copies and reproduction are
prohibited unless authorised.
The content of this document corresponds to the described products and
technologies.
Stated data may be modified or supplemented for technical and/or sales
purposes.
MODULE LAYOUT
Dimensions: 17.5 x 102.5 x 111 mm
Weight: 100 g;
Enclosure: PA6, black
SIGNALS VIA LED ON FRONT PANEL
LED | STATUS | LED meaning |
---|---|---|
PWR | ON | The device is powered correctly |
COM | Flashing | Profinet communication active |
Z-KEY-P version only | Off | No Profinet communication |
TX1 | Flashing | Data transmission on port #1 RS485 |
RX1 | Flashing | Data receipt on port #1 RS485 |
TX2 | Flashing | Data transmission on port #2 RS485/RS232 |
RX2 | Flashing | Data reception on port #2 RS485/RS232 |
ETH ACT Green | Flashing | Packet transmission on Ethernet port |
ETH LNK Yellow | ON | Ethernet connection present |
TECHNICAL SPECIFICATIONS
CERTIFICATIONS| https://www.seneca.it/products/z-key/doc/CE_declaration
---|---
INSULATION|
ENVIRONMENTAL
CONDITIONS| Temperature: -25 °C – + 65 °C; Humidity:;30%– 90% non condensing.
Altitude: Up to 2000 m above sea level; Storage temperature: -30 °C – + 85 °C
Protection rating: IP20 (Not evaluated by UL)
ASSEMBLY| IEC EN60715, 35mm DIN rail in vertical position.
POWER SUPPLY| Voltage: 11 – 40 Vdc; 19 – 28 Vac 50 – 60 Hz; Absorption: Max.
1,5W
CONNECTIONS| 3-way removable screw terminals, pitch 5 mm
Rear connector IDC10 for DIN bar 46277
RJ45 front connector
---|---
COMMUNICATION PORTS| TION
RS232 or RS485 switchable on terminal 10 – 11 – 12 (serial port 2)
Maximum Baud rate 115 k, maximum cable length RS232 < 3m
RS485 IDC10 rear connector: Maximum Baud rate 115 k. (serial port 1)
RJ45 front Ethernet connector: 100 Mbit/s, maximum distance 100 m
CONFIGURATION| Configuration and FW update via webserver;
Via DIP – SWITCH
Via EASY SETUP 2 configuration software
ATTENTION
The device may only be powered by a power supply unit with a limited energy
electric circuit max.
40Vdc / 28Vac Max output in accordance with CAN/CSA-C22.2 No. 61010-1-12 / UL
Std. No. 61010-1 (3rd Edition) chapter 6.3.1/6.3.2 and 9.4 or class 2
according to
CSA 223/UL 1310.
FACTORY IP ADDRESS
The default module IP address is static: 192.168.90.101
SETTING THE DIP-SWITCHES
WARNING
The DIP-switch settings are read only at boot time. At each change, perform a
restart.
SW2 DIP-SWITCH:
Through DIP-SWITCH-SW1 it is possible to set the IP configuration of the
device:
DESCRIPTION | DIP 1 | DIP 2 | DIP 3 | DIP 4 |
---|
To obtain the configuration from the Flash memory, both SW1 DIP switch
selectors must be set to OFF| | ****| RESERVED| RESERVED
To reset the device to factory settings both SW1 DIP switches must be set to
ON| | | RESERVED| RESERVED
To force the device’s IP address to the standard value of SENECA Ethernet
products: 192.168.90.101| | | RESERVED| RESERVED
Reserved| | | RESERVED| RESERVED
ATTENTION
DIP3 and DIP4, on models where they are present, must remain OFF. If set
otherwise, the instrument will not operate correctly.
KEY
1| ON|
0| OFF|
RS232/RS485 SETTING:
RS232 or RS485 configuration on terminals 10-11-12 (serial port 2)
SW2
1| ON| RS232 ACTIVATION
0| OFF| RS485 ACTIVATION
WEB SERVER
To access the maintenance Web Server with 192.168.90.101 factory IP address:
Default user: admin, Default password: admin, http://192.168.90.101
N.B.: For the Z-KEY-P version it is first necessary to activate webserver
mode
CAUTION
DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.
WEB SERVER AND PROFINET MODE (Z-KEY-P)
The device is normally in Profinet mode; in Profinet mode the device can be
configured only through the Easy Setup 2 software. In order to access the
internal webserver it is necessary to put the device in Webserver mode using
the Easy Setup 2 or Seneca Device Discovery software. It is also possible to
change the operating mode by pressing the side button following the procedure:
To force webserver mode:
- Keep the “PS1” button pressed until all LEDs are switched off
- Release the button
- The device restarts and the PWR and COM LEDs flash slowly to indicate webserver mode
To force Profinet mode:
- Keep the “PS1” button pressed until all LEDs are switched off
- Release the button
- The device restarts and the PWR and COM LEDs stop flashing slowly to indicate Profinet mode
INSTALLATION REGULATIONS
The module has been designed for vertical installation on a DIN 46277 rail.
For optimal operation and long life, adequate ventilation must be provided.
Avoid positioning ducting or other objects that obstruct the ventilation
slots. Avoid mounting modules over heat-generating equipment. Installation in
the bottom part of the electrical panel is
recommended.
ATTENTION
These are open-type devices and intended for installation in an end enclosure
/ panel offering mechanical protection and protection against spread of fire.
ELECTRICAL CONNECTIONS
CAUTION
To meet the electromagnetic immunity requirements:
– use shielded signal cables;
– connect the shield to a preferential instrumentation earth system;
– separate shielded cables from other cables used for power installations
(transformers, inverters, motors, etc…).
POWER SUPPLY|
---|---
SERIAL PORT 2: RS485 SW2 = OFF|
SERIAL PORT 2: RS232 SW2 = ON|
ATTENTION
Use only copper or copper-clad aluminium or AL-CU or CU-AL conductors
IDC10 CONNECTOR
The illustration shows the meanings of the various IDC10 connector pins if signals are to be sent via them directly.
http://www.seneca.it/products/z-key
http://www.seneca.it/products/z-key-p SENECA s.r.l.; Via Austria
26 – 35127 – PADOVA – ITALY
Tel. +39.049.8705359
– Fax +39.049.8706287