SENECA Z102 Signal Converters Hiflex Instruction Manual
- June 1, 2024
- SENECA
Table of Contents
SENECA Z102 Signal Converters Hiflex
Product Information
Specifications
- Dimensions: 17.5 x 102.5 x 111 mm
- Weight: 110 g
- Enclosure: PA6, black
Product Usage Instructions
Module Layout
The module layout consists of various components indicated by numbers as
follows:
- PWR
- FAIL
- ZERO
- SPAN
- SW1
- SW2
Electrical Connections
- Power Supply: Use Vac / Vdc 1 and Vac / Vdc 2 for power input with caution to avoid exceeding upper limits.
- Inputs: Connect rheostat and potentiometer inputs as per the provided instructions.
- Outputs: Utilize ACTIVE connection for direct module-powered output loop or PASSIVE connection for external current loop supply.
Installation Regulations
The module is designed for vertical installation on a DIN 46277 rail with
proper ventilation. Avoid obstructions to ventilation slots and heat-
generating equipment.
FAQ
-
Q: What should I do if the LED status shows an error?
A: Check the input measuring range and ensure proper electrical connections are made as per the manual. -
Q: Can I modify the factory calibration error?
A: No, the factory calibration error should not be modified as it may affect the device’s accuracy.
INSTALLATION MANUAL
Z102
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions
that put the user’s safety at risk. The word ATTENTION preceded by the symbol
indicates conditions or actions that could damage the instrument or
connected equipment.
The warranty shall become null and void in the event of improper use or
tampering with the module or devices supplied by the manufacturer as necessary
for its correct operation, and if the instructions contained in this manual
are not followed.
WARNING: The full content of this manual must be read before any
operation. The module must only be used by qualified electricians. Specific
documentation is available using the QR-CODE shown on page 1.
The module must be repaired and damaged parts replaced by the Manufacturer.
The product is sensitive to electrostatic discharges. Take appropriate
measures during any operation.
Electrical and electronic waste disposal (applicable in the European Union and
other countries with recycling). The symbol on the product or its packaging
shows the product must be surrendered to a collection centre authorized to
recycle electrical and electronic waste.
SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY; Tel. +39.049.8705359 – Fax +39.049.8706287
CONTACT INFORMATION
Technical support supporto@seneca.it
Product information commerciale@seneca.it
This document is the property of SENECA srl. Copies and reproduction are
prohibited unless authorised. The content of this document corresponds to the
described products and technologies.
Stated data may be modified or supplemented for technical and/or sales
purposes.
MODULE LAYOUT
Dimensions LxHxD: 17.5 x 102.5 x 111 mm; Weight: 110 g; Enclosure: PA6, black
SIGNALS VIA LED ON FRONT PANEL
LED | STATUS | LED meaning |
---|---|---|
PWR | On | Device powered |
Off | Device not powered | |
FAIL | On | Input in error |
TECHNICAL SPECIFICATIONS
CERTIFICATIONS|
---|---
POWER SUPPLY| Voltage: 10 ÷ 40Vdc; 19 ÷ 28Vac 50 ÷ 60Hz, Absorption:
Max.: 2.0 W
INPUT| Resistor with rheostat connection (2 wires): fields 0 ÷ 300Ω (I =
6 mA), 0 ÷ 500Ω (I = 3.6 mA) and 0 ÷ 1KΩ (I = 1.8mA).
Resistor with potentiometer connection (3 wires): 200Ω ÷ 1MΩ (Vref = 1.8 Vcc).
OUTPUT| Current 0..20 / 4..20 mA, max load resistance 600Ω.
Voltage 0..5 V / 0..10 V / 1..5 V / 2..10 V, min load resistance 2000Ω.
ENVIRONMENTAL CONDITIONS| Operating temperature: from -25°C to +70°C Humidity: 10% ÷ 90% non condensing.
Storage temperature: from -30°C to +85°C
Protection rating: IP20
POWER SUPPLY/ OUTPUT PROTECTION| against impulse voltage
overload 400W/ms.
PASS-BAND| 15 Hz; Response time 10%-90%: 20ms
ERRORS RELATED TO THE INPUT MEASURING RANGE:
FACTORY CALI- BRATION ERROR| For rheostat input: 0.3%; For potentiometer
input: 1%.
THERMAL COEFFICIENT| 0.02%/°C
LINEARITY ERROR| 0.05%
ELECTRICAL CONNECTIONS
CAUTION
Switch the module off before connecting inputs and outputs.
To meet the electromagnetic immunity requirements:
- use shielded signal cables;
- connect the shield to a preferential instrumentation earth system;
- separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc…).
POWER SUPPLY
The upper power supply limits must not be exceeded, as this might cause
serious damage to the module.
The power supply source must be protected from any failures in the module by
means of a suitably sized fuse.
INPUTS
Rheostat connection (2 wires):
Potentiometer connection (3 wires):
NOTE: DIP 4 of DIP-SWITCH SW1 is reserved for internal uses.
OUTPUTS
INSTALLATION REGULATIONS
The module has been designed for vertical installation on a DIN 46277 rail.
For optimal operation and long life, adequate ventilation must be provided.
Avoid positioning ducting or other objects that obstruct the ventilation
slots. Avoid mounting modules over heat-generating equipment. Installation in
the bottom part of the electrical panel is recommended.
HARSH OPERATING CONDITIONS
The following constitute harsh operating conditions:
- High power supply voltage (> 30Vdc / > 26Vac).
- Sensor power supply at input.
- Using the impressed current output.
- When the modules are mounted side by side it may be necessary to separate them by at least 5 mm in the following cases:
- Panel temperature above 45°C in at least one of the above harsh operating conditions.
- Panel temperature above 35°C in at least two of the above harsh operating conditions.