SENECA R-SG3 Analog I and O Modules Instruction Manual
- June 1, 2024
- SENECA
Table of Contents
- SENECA R-SG3 Analog I and O Modules Instruction Manual
- Product Usage Instructions
- PRELIMINARY WARNINGS
- CONTACT INFORMATION
- MODULE LAYOUT
- SIGNALS VIA LED ON FRONT PANEL
- SETTING THE SW1 DIP-SWITCHES
- SW2 DIP-SWITCH SETTINGS
- IDC10 CONNECTOR
- WEB SERVER (ONLY ZE-SG3)
- ELECTRICAL CONNECTIONS
- Load cell
- Read More About This Manual & Download PDF:
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SENECA R-SG3 Analog I and O Modules Instruction Manual
Product Information
- Product Name: Z-SG3 ZE-SG3
- Manufacturer: SENECA srl
- Contact Information:
- Technical Support: supporto@seneca.it
Product Information:
commerciale@seneca.it – Module Dimensions:
17.5 x 102.5 x 111 mm (LxHxD) – Module Weight: 110 g – Enclosure Material:
PA6, black
Product Usage Instructions
Installation
Before any operation, read the full content of the installation manual. – The
module should only be installed by qualified electricians. – Refer to the
specific documentation available using the QR-CODE shown on page 1. – If any
repairs are needed or damaged parts need to be replaced, contact the
manufacturer
for assistance. – Take appropriate measures to avoid electrostatic discharges
during any operation. – For electrical and electronic waste disposal,
surrender the product to a collection center authorized to recycle such waste.
2.
Module Layout: – The module has dimensions of 17.5 x 102.5 x 111 mm (LxHxD). – It weighs 110 g. – The enclosure is made of black PA6 material.
Signals via LED on Front Panel
PWR / FAIL LED: – ON: Device is powered correctly. – Flashing: Load cell overload. – RX (ZE-SG3) LED: – Flashing: Reception of packet completed on RS485. – ON: Anomaly / Check connection on RS485. – TX (ZE-SG3) LED: – Flashing: Transmission of packet completed on RS485. – ON: Anomaly / Check connection on RS485. – RX (Z-SG3) LED: – Flashing: Reception of packet completed on RS485 / USB. – ON: Anomaly / Check connection on RS485. – TX (Z-SG3) LED: – Flashing: Transmission of packet completed on RS485. – ON: Anomaly / Check connection on RS485. – ETH TRF (ONLY ZE-SG3) LED: – Flashing: Packet transmission on Ethernet port. – ON: Ethernet connection present. – ETH LNK (ONLY ZE-SG3) LED: – Flashing: Ethernet connection present. – ON: Ethernet connection present.
Technical Specifications
Certifications: Not specified in the provided text. – Insulation: – Z-SG3 USB: 1500 V~ – Z-SG3 RS485: 1500 V~ – ZE-SG3 RS485: 1500 V~ – Communication: – Serial communication ports: – RS485 (on terminal and IDC10) – Front micro USB (only Z-SG3) – Ethernet port 10/100 Mbit/s (only ZE-SG3) – Power Supply: Not specified in the provided text.
Analog Input Characteristics: – Cell supply voltage: 5 Vdc (supplied by the device) – Resolution: ADC 24bit – Error: 0.01% of the electrical full scale in factory calibration mode * Note: The provided text does not contain complete information for all sections. Additional information may be available in the complete user manual.
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that
put the user’s safety at risk. The word ATTENTION preceded by the symbol
indicates conditions or actions that could damage the instrument or connected
equipment.
The warranty shall become null and void in the event of improper use or
tampering with the module or devices supplied by the manufacturer as necessary
for its correct operation, and if the instructions contained in this manu-al
are not followed.
- WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available using the QR-CODE shown on page 1.
- The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
- Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.
SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY; Tel. +39.049.8705359 – Fax +39.049.8706287
CONTACT INFORMATION
Technical support
supporto@seneca.it
Product information
commerciale@seneca.it
This document is the property of SENECA srl. Copies and reproduction are
prohibited unless authorised. The content of this document corresponds to the
described products and technologies.
Stated data may be modified or supplemented for technical and/or sales
purposes.
MODULE LAYOUT
Dimensions LxHxD : 17.5 x 102.5 x 111 mm;
Weight: 110 g; Enclosure: PA6, black
SIGNALS VIA LED ON FRONT PANEL
ANALOGUE INPUT
CHARACTERISTICS
| Input impedance: > 1MΩ; Full scale: ± 30mV ÷ ± 460mVError: 0.01% of the electrical full scale in “factory calibration” mode * Thermal stability: 0.0010%/C° of full scale.
Cell supply voltage: 5 Vdc (supplied by the device) Resolution: ADC 24bit Response time with activated filter: 2 ÷ 850ms configurable
---|---
LOAD CELL CHARACTERISTICS| 4 or 6 wires;Cell minimum impedance: 87 Ω
equivalent (possibly deriving from several load cells in parallel) Cell
sensitivity: From ±1 mV/V to ±64 mV/V;
ANALOGUE OUTPUT| Voltage output: Configurable between 0 ÷ 10Vdc,
minimum load resistance 2kΩ Current output: Configurable between 0 ÷ 20mA,
maximum load resistance: 500 Ω Retransmission error: 0.1 % of maximum field;
Response time (10%…90%): 5 ms
DIGITAL IN/OUT| Opto-insulated digital input: Min. voltage: 12 V /
Max. voltage: 30 V Opto-insulated digital output: Max. current: 50 mA / Max.
voltage: 30 V
- In the case of “calibration with sample weight” mode, the accuracy is given by the linearity error (0.003% of the electric full scale)
SETTING THE SW1 DIP-SWITCHES
The position of the DIP-switches defines the Modbus communication parameters of the module: Address and Baud Rate The following table shows the values of the Baud Rate and the address according to the setting of the DIP-switches:
SW2 DIP-SWITCH SETTINGS
WARNING
The DIP-switch settings are read only at boot time. At each change, perform
a restart.
For use and settings via DIP-SWITCH, see the user manual available on the
website on the web page dedicated to the product.
PS BUTTON1
The tare is reset using the PS1 button. To reset the tare it is necessary to
hold down the PS1 button for three seconds. The update of the value will be
viewable via the Webserver page and/or Modbus.
IDC10 CONNECTOR
The illustration shows the meanings of the various IDC10 connector pins if signals are to be sent via them directly.
WEB SERVER (ONLY ZE-SG3)
To access the maintenance Web Server, use the following credentials: Default user: admin; Default password: admin
CAUTION
DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.
FACTORY IP ADDRESS (ONLY ZE-SG3)
The default module IP address is static: 192. 168. 90. 101
USB PORT (ONLY Z-SG3)
The module is designed to exchange data according to the modes defined by the
MODBUS protocol. It has a micro USB connector and can be configured using
applications and/or software programs. The USB serial port uses the following
communication parameters: 38400 BAUD, 8BIT, NO PARITY, 1 STOP BIT, ModBUS
ADDRESS 1.
The USB communication port responds exactly like the RS485 port with the
exception of the communication parameters. While using the USB port, the RS485
port is disabled.
ELECTRICAL CONNECTIONS
CAUTION
The upper power supply limits must not be exceeded, as this could cause
serious damage to the module. To meet the electromagnetic immunity
requirements:
- use shielded signal cables;
- connect the shield to a preferential instrumentation earth system;
- separate shielded cables from other cables used for power installations (inverters, motors, induction ovens, etc…).
Load cell
Connection to the load cell via 4 or 6 wires: The terminals have the following meaning:
- 13: Load cell positive supply
- 11: Load cell positive supply reading
- 9: Cell reading positive
- 12: Load cell negative supply reading
-
- 14: Load cell negative supply
- 10: Cell reading negative
- For the connections, the use of screened cables is required.
Read More About This Manual & Download PDF:
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>