SENECA R-32DIDO-2 Digital I O Modules Instruction Manual
- June 1, 2024
- SENECA
Table of Contents
SENECA R-32DIDO-2 Digital I O Modules
Product Information
Specifications
- Weight: 170 g
- Enclosure: UL94-V0 self-extinguishing PC/ABS material, black
Module Layout
- Dimensions: 106.6 mm x 32.2 mm x 90.0 mm
Signals via LED on Front Panel
LED | Meaning |
---|---|
PWR | Device powered |
IO1/IO32 | Digital input/output active |
Technical Specifications
- Insulation: 1500 Vac
- Configuration: With integrated WEB Server / from Profinet environment
- Connections: 3.5 mm pitch terminal block, 1.5 mm2 max cable section
Communication Ports:
- 2 Ethernet ports (with LAN fault-bypass function) 100 base T on RJ45
- 1 RS485 port on terminals 23-24-25 (only R-32DIDO-2versions)
Product Usage Instructions
Installation
- Ensure to read the full content of the manual before proceeding with any operation.
- The module should only be installed by qualified electricians.
Maintenance
Any repairs or part replacements should be done by the Manufacturer to
maintain product integrity.
Frequently Asked Questions (FAQ)
Q: Can the module be used by non-electricians?
A: No, the module must only be used by qualified electricians for safety and
proper operation.
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that
put the user’s safety at risk.
The word ATTENTION preceded by the symbol indicates conditions or actions that
might damage the instrument or the connected equipment. The warranty shall
become null and void in the event of improper use or tampering with the module
or devices supplied by the manufacturer as necessary for its correct
operation, and if the instructions contained in this manual are not followed
- WARNING : The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available via QR-CODE shown on page 1
- The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
- Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.
SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY; Tel. +39.049.8705359 – Fax +39.049.8706287
CONTACT INFORMATION
- Technical support
- Product information
This document is the property of SENECA srl. Copies and reproduction are
prohibited unless authorised.
The content of this document corresponds to the described products and
technologies. Stated data may be modified or supplemented for technical and/or
sales purposes.
MODULE LAYOUT
Weight: 170 g; Enclosure: UL94-V0 self-extinguishing PC/ABS material, black.
SIGNALS VIA LED ON FRONT PANEL
LED | STATUS | LED meaning |
---|---|---|
PWR | On | Device powered |
Off | Device not powered | |
IO1/IO32 | On | Digital input/output active |
Off | Digital input/output not active | |
OUT SUP | On | Digital inputs/outputs powered |
Off | Digital inputs/outputs not powered |
STS
(R-32DIDO-2 version only)
| On| IP address set
Flashing| Waiting for the IP address from the DHCP
STS
(R-32DIDO-2-P version only)
| On| IP address set
Flashing| No IP address configured
COM
(R-32DIDO-2-P version only)
| Off| No Profinet communication
Flashing| Profinet communication present
FAIL| On| Digital output in FAIL
Off| Digital output OK
RX
(R-32DIDO-2 version only)
| On| RS485 port wiring error
Flashing| Reception of data packet completed on RS485
TX
(R-32DIDO-2 version only)
| Flashing| Transmission of data packet completed on RS485
ETH TRF (Yellow)| Flashing| Packet transit on Ethernet port
ETH LNK (Green)| Flashing| The Ethernet port is connected (LINK)
TECHNICAL SPECIFICATIONS
POWER SUPPLY| Voltage: 10÷40Vdc; 19÷28Vac; 50÷60Hz; Absorption: 3W max;
Dissipation: 6.5W max
---|---
ENVIRONMENTAL CONDITIONS| Operating temperature: from -25°C to +65°C;
Humidity: 10% ÷ 90% non condensing. Storage temperature: from -30°C to +85°C;
Protection rating: IP20
CONFIGURATION| With integrated WEB Server / from profinet environment
CONNECTIONS/ COMMUNICATION PORTS| 3.5 mm pitch terminal block, 1.5 mm2
max cable section
2 Ethernet (with LAN fault-bypass function) 100 base T on RJ45 1 RS485 port on terminals 23-24-25 (only R-32DIDO-2 versions)
DIGITAL INPUTS
| Number of channels: 32; Voltage: Threshold ON: >11 Vdc; Threshold OFF: < 4 Vdc; Vmax: 24 Vdc; Impedance 9kΩ,
Individually configurable. Complies with IEC61131-2 type 3.
Alimentazione esterna separata per i due gruppi di uscita: V EXT: 12÷24 Vdc
DIGITAL OUTPUTS| Number of channels: 32, MOSFET, PNP; Max voltage/current: 0.2 A / 24 Vdc Individually configurable
Separate external power supply for the two output groups: V EXT: 12÷24 Vdc
COUNTERS:| Number of counters: 32 at 32 bit, maximum speed: 500 Hz (only R-32DIDO-2 versions)
ELECTRICAL CONNECTIONS
The upper power supply limits must not be exceeded, as this could cause serious damage to the module. Switch the module off before connecting inputs and outputs.
To meet the electromagnetic immunity requirements:
- use shielded signal cables;
- connect the shield to a preferential instrumentation earth system;
- separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc.).
Connection to the RS485 port.
Polarity is not standardised; in some devices of other brands it may be
inverted
CAUTION
The power supply must be sized according to the expected load at the
outputs. Terminals 18-64 and 19-65 can be connected together on the same power
supply. Only a Vdc power supply is permitted.
CAUTION
For correct instrument operation, power the I/Os via the I/O Ext Supply 1
(18-19) and 2 (64-65) terminals at the same time. The ‘OUT SUP’ LED lights up
to verify a correct power supply.
EXAMPLE:
In the diagram below we have an application example of a system with four
digital inputs and three digital outputs externally powered at 12Vdc and three
digital outputs and two digital inputs powered at 24Vdc.
ATTENTION
The external IO Ext 1 and IO Ext 2 supplies must be powered simultaneously
within a range of 12÷24Vdc. The external IO Ext 1 and IO Ext 2 supplies can
have different voltages.
DAISY-CHAIN
CAUTION IT IS NOT ALLOWED TO CREATE LOOPS WITH ETHERNET CABLES
- Using the daisy-chain connection it is not necessary to use switches to connect the devices.
- The following examples show the correct connections.
- There must be no loops in the Ethernet cabling, otherwise the communication will not work. The modules and switches must be connected eliminating any loops. The following examples show the incorrect connections.
- The LAN fault-bypass function allows you to keep the connection between the two Ethernet ports of the device ON, in the event of a power failure. If a device turns off, the chain is not interrupted and the devices downstream of the switched-off one will still be accessible. This function has a limited duration: the connection remains active for a few days, typically 4. The fault-bypass function requires that the sum of the lengths of the two cables connected to the switched-off module is less than 100m.
ETHERNET CONNECTION RULES
- For the Ethernet cabling between the devices, the use of the unshielded CAT5 or CAT5e cable is required.
- CAT6 for industrial environments.
FACTORY IP ADDRESS (R-32DIDO-2 ONLY)
- The default module IP address is static: 192. 168. 90. 101
WEB SERVER
Use the following credentials to access the Maintenance Web Server:
- Default user: admin
- Default password: admin
CAUTION
DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.
DIP – SWITCH SETTINGS
- The DIP-switch settings are read-only at boot time. At each change, perform a restart.
- For operation and settings via DIP-SWITCH see the user manual available on the product webpage
Read User Manual Online (PDF format)