SENECA R-8AI-8DIDO Signals Via LED On Front Panel Instruction Manual

June 1, 2024
SENECA

SENECA R-8AI-8DIDO Signals Via LED On Front Panel

PRELIMINARY WARNINGS

The word WARNING preceded by the symbol indicates conditions or actions that put the user’s safety at risk. The word ATTENTION preceded by the symbol indicates conditions or actions that could damage the instrument or connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.SENECA-R-8AI-8DIDO-Signals-Via-LED-On-Front-Panel-
fig-2

SENECA-R-8AI-8DIDO-Signals-Via-LED-On-Front-Panel-
fig-3

CONTACT INFORMATION

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorized. The content of this document corresponds to the described products and technologies. Stated data may be modified or supplemented for technical and/or sales purposes.

MODULE LAYOUT

SENECA-R-8AI-8DIDO-Signals-Via-LED-On-Front-Panel-
fig-4

Weight: 170 g; Enclosure: UL94-V0 self-extinguishing PC/ABS material, black.

SIGNALS VIA LED ON FRONT PANEL

LED STATUS LED meaning
IO1/IO8 On Digital input/output active
Off Digital input/output not active
OUT SUP On Digital inputs/outputs powered
Off Digital inputs/outputs not powered

STS

(Status only version R-8AI-8DIDO)

| On| IP address set
Flashing| Waiting for the IP address from the DHCP
STS

(Status only version R-8AI-8DIDO-P)

| On| IP address set
Flashing| No configured IP address
COM

(only version R-8AI-8DIDO-P)

| Off| No Profinet communication
Flashing| Profinet communication present
FAIL| On| Digital output in FAIL / TC in Burn or out of range
RX

(only version R-8AI-8DIDO)

| On| RS485 port wiring error
Flashing| Reception of data packet completed on RS485
TX

(only version R-8AI-8DIDO)

| Flashing| Reception of data packet completed on RS485
ETH TRF (Yellow)| Flashing| Packet transit on Ethernet port
ETH LNK (Green)| Flashing| Ethernet port connected

TECHNICAL SPECIFICATIONS

CERTIFICATIONS

|

SENECA-R-8AI-8DIDO-Signals-Via-LED-On-Front-Panel-
fig-5

---|---

INSULATION

|

POWER SUPPLY| Voltage: 10 ÷ 40 Vdc; 19 ÷ 28 Vac; 50 ÷ 65 Hz; Absorption: 3 W

ENVIRONMENTAL CONDITIONS

| Operating temperature: from -25°C to +65°C Humidity: 10% ÷ 90% non condensing.

Storage temperature: from -30°C to +85°C

Protection rating: IP20

ASSEMBLY| 35mm DIN rail IEC EN60715
CONFIGURATION| With built-in WEB server (only version R-8AI-8DIDO)
CONNECTIONS / COMMUNICATION PORTS| 3.5 mm pitch terminal block, 1.5 mm2 max cable section

2 Ethernet (with LAN fault-bypass function) 100 base T on RJ45 1 RS485 port on terminals (only version R8AI–8DIDO)

DIGITAL INPUTS| Number of channels: 8; Voltage: Threshold ON: > 11 V; Threshold OFF:< 4 V; Vmax: 28 V; Impedance 9 kΩ Compliant with IEC61131-2 type 3.
DIGITAL OUTPUTS| Number of channels: 8, MOSFET, PNP; Max voltage/current: 0.2A; 9÷ 28 V

ANALOG INPUT

| Number of channels: 8; Type: voltage, current, thermocouple, Max. 1 PT100 resistance thermometer. Measuring range: Voltage: -30 V ÷ +30 V; -150 mV ÷ +150 mV

Current: -24 mA ÷ +24 mA (maximum loop power: 24 Vdc) Thermocouple: J, K, T, E, N, R, S, B, L

Resistance thermometer: PT100: -200 °C ÷ +650 °C (only for cold junction or

measurement compensation)

ELECTRICAL CONNECTIONS

CAUTION

The upper power supply limits must not be exceeded, as this could cause serious damage to the module. Switch the module off before connecting inputs and outputs.

To meet the electromagnetic immunity requirements

  • use shielded signal cables;
  • connect the shield to a preferential instrumentation earth system;
  • separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc…).

SENECA-R-8AI-8DIDO-Signals-Via-LED-On-Front-Panel-
fig-7

ANALOG INPUTS : The device has 8 analog inputs that can be configured via DIP-SWITCH:

SENECA-R-8AI-8DIDO-Signals-Via-LED-On-Front-Panel-
fig-8SENECA-R-8AI-8DIDO-Signals-Via-LED-
On-Front-Panel-fig-9

SETTING THE DIP-SWITCHES

WARNING
The DIP-switch settings are read only at boot time. At each change, perform a restart. For use and settings via DIP-SWITCH, see the user manual available on the website on the web page dedicated to the product.

DIP-SWITCH SW2 AND SW3 : ANALOG INPUT CONFIGURATION

SW2 SW3
1 2
AI1 AI2
  • DIP-SWITCHES SW2 and SW3 are located on the back of the device.

SW1 DIP-SWITCH: DEFAULT SETTINGS

SW1

DIP1| OFF| DEFAULT SETTINGS
DIP2| OFF

  • DIP-SWITCH SW1 is located on the front of the device.

INSTALLATION MANUAL

CAUTION
The input for the RTD thermoresistance is available only for the first channel. For channels 2 to 8 it is not available.

WARNING
The product is not suitable for connection to a dangerous voltage conductor. The maximum allowable voltage is 50 Vac / 75 Vdc concerning earth.

THERMORESISTANCE

  • The SW1 Dip-Switch selector 1 goes to the OFF position. Function valid only for analog input 1.

INSTRUCTIONS FOR ANALOG INPUTS
The analog inputs of this device are designed to measure voltages/currents on floating circuits that is not electrically connected. In the case of measurement with thermocouples, it is possible to obtain correct measurements even if they are applied to common metal parts. The temperature measurement using thermocouples can be affected by measurement errors due to the determination of the cold junction temperature carried out near the terminal. To eliminate any measurement errors it is necessary to wire the thermocouples on an isothermal terminal board separate from the device as shown in the diagram on the side. Input No.1 set as Pt100 (see the DIP- SWITCH table) will then be used to measure the cold junction temperature of said terminal block.

FEATURE SUMMARY

ANALOG INPUTS

 | Range| Effective resolution (at 400 ms)| Impedance| Precision| Temperature drift| Ext. current
Voltage (V)| -30 ÷ +30 Vdc| 0.05 mV| > 200 kΩ| 0.1% f.s.| 50 ppm|
Current (mA)| 0 ÷ +24 mA| 0.07 µA| 60 Ω| 0.1% f.s.| 50 ppm|
Voltage (mV)| -150 ÷ +150 mV| 0.5µV| > 10 MΩ| 0.1% f.s.| 50 ppm|
Thermocouple| -150 ÷ +150mV| 0.5µV| > 10 MΩ| 0.1% f.s.| 50 ppm|
PT100| -200 ÷ 650 °C| 6 mΩ (0.015°C at 0°C)|  | 0.1°C| 50 ppm| 250 µA
THERMOCOUPLE TYPE

 | Range [°C]| Standard| Internal cold junction error [°C]
J| -210..1200| EN 60584| 2
K| -200..1372| EN 60584| 2
T| -200..400| EN 60584| 2
E| -200..1000| EN 60584| 2
N| -200..1300| EN 60584| 2
R| -50..1768| EN 60584| 2
S| -50..1768| EN 60584| 2
B| 250..1820| EN 60584| 2
L| -200..800| GOST:8.585| 2

DAISY-CHAIN ETHERNET CONNECTION

WARNING
FUNCTION VALID ONLY FOR THE R-8AI/8DIDO-2 AND R-8AI-8DIDO-2-P MODELS

CAUTION
IT IS NOT ALLOWED TO CREATE LOOPS WITH ETHERNET CABLES Using the daisy- chain connection it is not necessary to use switches to connect the devices. The following examples show the correct connections.SENECA-R-8AI-8DIDO-
Signals-Via-LED-On-Front-Panel-fig-12

There must be no loops in the Ethernet cabling, otherwise the communication will not work. The modules and switches must be connected eliminating any loops. The following examples show the incorrect connections.SENECA-R-8AI-
8DIDO-Signals-Via-LED-On-Front-Panel-fig-13

The LAN fault-bypass function allows you to keep the connection between the two Ethernet ports of the device ON, in the event of a power failure. If a device turns off, the chain is not interrupted and the devices downstream of the switched-off one will still be accessible. This function has a limited duration: the connection remains active for a few days, typically 4. The fault-bypass function requires that the sum of the lengths of the two cables connected to the switched off module is less than 100m.

ETHERNET CONNECTION RULES

  • For the Ethernet cabling between the devices, the use of the unshielded CAT5 or CAT5e cable is required.

FACTORY IP ADDRESS (ONLY R-8AI-8DIDO)

  • The default module IP address is static: 192. 168. 90. 101

WEB SERVER

To access the maintenance Web Server, use the following credentials:

  • Default user: admin
  • Default password: admin

CAUTION
DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals