MEAN WELL MDR-40-5 Series 40W Single Output Industrial DIN Rail Power Supply Owner’s Manual

June 15, 2024
MEAN WELL

MEAN WELL MDR-40-5 Series 40W Single Output Industrial DIN Rail Power

Supply

Product Information

Specifications

  • Product Name: 40W Single Output Industrial DIN Rail Power Supply
  • Model: MDR-40 series
  • GTIN CODE: [insert GTIN code]
  • Input Voltage: Universal AC input/Full range
  • Protections: Short circuit / Overload / Over voltage
  • Cooling: Free air convection
  • Mounting: DIN rail TS-35/7.5 or 15
  • Hazardous Locations: Class I, Div 2
  • T4 LED indicator for power on
  • DC OK relay contact
  • No load power consumption

Frequently Asked Questions

  • Q: Can the power supply be used in hazardous locations?
    • A: Yes, this power supply is suitable for Class I, Div 2 hazardous locations.
  • Q: What is the no load power consumption of the power supply?
    • A: The power supply has a no load power consumption feature, which means it consumes minimal power when there is no load connected.
  • Q: How can I troubleshoot if the LED indicator or relay contact is not functioning?
    • A: Please refer to the troubleshooting section of the user manual for detailed instructions on how to troubleshoot LED indicator and relay contact issues.

Product Usage Instructions

Installation

  1. Choose a suitable location for installing the power supply.
  2. Ensure that the DIN rail TS-35/7.5 or 15 is securely mounted.
  3. Slide the power supply onto the DIN rail until it clicks into  place.
  4. Verify that the power supply is firmly attached to the DIN rail.

Electrical Connections

  1. Before connecting any wires, ensure that the power supply is turned off.
  2. Connect the input wires to the appropriate AC power source terminals.
  3. Connect the output wires to the load terminals.
  4. Double-check all connections to ensure they are secure.

Operation

  1. Turn on the AC power source.
  2. The T4 LED indicator will light up, indicating that the power supply is receiving power.
  3. Verify that the DC OK relay contact is closed, indicating that the output voltage is within the specified range.
  4. If the LED indicator or relay contact does not function as expected, refer to the troubleshooting section of the user manual.

Maintenance

To ensure optimal performance and longevity of the power supply, follow these maintenance guidelines:

  • Regularly inspect the power supply for any signs of damage or wear.
  • Clean the power supply periodically to remove dust or debris that may affect cooling.
  • Do not attempt to repair or modify the power supply yourself. Contact a qualified technician for any repairs or servicing.

Features

  • Universal AC input/Full range
  • Protections: Short circuit / Overload / Over voltage
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Class I, Div 2 Hazardous Locations T4
  • LED indicator for power on
  • DC OK relay contact
  • No load power consumption<0.75W
  • 100% full load burn-in test
  • 3 years warranty

GTIN CODE

SPECIFICATION

MODEL MDR-40-5 MDR-40-12 MDR-40-24 MDR-40-48







OUTPUT

| DC VOLTAGE| 5V| 12V| 24V| 48V
RATED CURRENT| 6A| 3.33A| 1.7A| 0.83A
CURRENT RANGE| 0 ~ 6A| 0 ~ 3.33A| 0 ~ 1.7A| 0 ~ 0.83A
RATED POWER| 30W| 40W| 40.8W| 39.8W
RIPPLE & NOISE (max.) **Note.2| 80mVp-p| 120mVp-p| 150mVp-p| 200mVp-p
VOLTAGE ADJ. RANGE| 5 ~ 6V| 12 ~ 15V| 24 ~ 30V| 48 ~ 56V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME Note.5| 500ms, 30ms/230VAC           500ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)**| 50ms/230VAC           20ms/115VAC at full load




INPUT

| VOLTAGE RANGE| 85 ~ 264VAC           120 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 78%| 86%| 88%| 88%
AC CURRENT (Typ.)| 1.1A/115VAC           0.7A/230VAC
INRUSH CURRENT (Typ.)| COLD START 30A/115VAC           60A/230VAC
LEAKAGE CURRENT| <1mA / 240VAC



PROTECTION

| ****

OVERLOAD

| 105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed


OVER VOLTAGE

| 6.25 ~ 7.25V| 15.6 ~ 18V| 31.2 ~ 36V| 57.6 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
FUNCTION| DC OK SIGNAL| Relay contact rating(max.): 30V/1A resistive




ENVIRONMENT

| WORKING TEMP.| -20 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6



SAFETY & EMC

(Note 4)

| SAFETY STANDARDS| UL508, UL62368-1, TUV BS EN/EN62368-1,Class I, Div. 2 Group A, B, C, D Hazardous Locations T4, EAC TP TC 004, BSMI CNS14336-1, AS/NZS 60950.1 ,IS13252(Part1)/IEC60950-1(except 48V)approved
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class B
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2, 3, 4, 5, 6, 8, 11, BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3, heavy industry level, EAC TP TC 020


OTHERS

| MTBF| 2418.5K hrs min.       Telcordia SR-332 (Bellcore) ; 301.7K hrs min.       MIL-HDBK-217F (25℃)
DIMENSION| 4090100mm (WHD)
PACKING| 0.3Kg; 42pcs/13.6Kg/0.82CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

3. Tolerance : includes set up tolerance, line regulation and load regulation.

4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)

5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.

6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Mechanical Specification

MEAN-WELL-MDR-40-5-Series-40W-Single-Output-Industrial-DIN-Rail-Power-
Supply-fig-2

Block Diagram

MEAN-WELL-MDR-40-5-Series-40W-Single-Output-Industrial-DIN-Rail-Power-
Supply-fig-3

DC OK Relay Contact

Contact Close PSU turns on / DC OK.
Contact Open PSU turns off / DC Fail.
Contact Ratings (max.) 30V/1A resistive load.

Derating Curve

MEAN-WELL-MDR-40-5-Series-40W-Single-Output-Industrial-DIN-Rail-Power-
Supply-fig-4

Output Derating VS Input Voltage

SCAN

Documents / Resources

| MEAN WELL MDR-40-5 Series 40W Single Output Industrial DIN Rail Power Supply [pdf] Owner's Manual
MDR-40-5 Series 40W Single Output Industrial DIN Rail Power Supply, MDR-40-5 Series, 40W Single Output Industrial DIN Rail Power Supply, Industrial DIN Rail Power Supply, Rail Power Supply, Power Supply
---|---