Please note:
- This is a two-wire dimmer that needs to be connected as shown under the header Connection diagram.
- Installing the dimmer on a mains power supply of 230V needs to be done by a qualified professional and should take into account any national regulations. Ensure that the electricity is switched off during installation.
Input Voltage: 230V
Frequency: 50Hz
Maximum wattage: 250W
Minimum wattage: 0W
Dimming technology: Phase cut (trailing edge, R, C)
Dimmable led lamps: 0-250W
Bulbs with electronic transformers: 0-250W
Halogen and incandescent bulbs: 0-250W
Suitable brands of cover material
- Berker by Hager
- Busch-Jaeger
- GIRA
- JUNG
- Merten by Schneider
- NIKO
- PEHA
- KOPP
Features
- Suitable for new installations and retrofit bulbs.
- Multi-dim technology achieve multi-way dimming/switching with no extra wires
- Soft start system for longer lifespan of LED bulbs.
- Built-in protection against, overload and overheat protection.
- Suitable for one-way and multi-way dimming.
- Multiple dimmers can control the same set of lights, but each dimmer works independently and does not interfere with each other.
- Self adaption at the maximum brightness to ensure no flickering appears
Connection
Step 1: Always make sure that the electricity is turned off during installation. Then connect the power wires as indicated in the ” Connection diagram.”
Step 2: Now install the dimmer in the flush-mounting box.
Step 3: Switch the electricity back on. Switch on the connected lamps using the dimmer shaft. Now set the MIN, as indicated under “MIN set up”.
Step 4: Replace the cover frame and the dimmer knob on the dimmer.
Connection diagram
MIN. set light level
The minimum brightness is selected by a dip switch, which is convenient for the user to accurately control the brightness level of the lamp.
- Factory set min. brightness to 1
- All dimmers install in parallel must be set to the same dimming lever (switch position)
Reduction of connected load by PowerFactor
When calculating the LED connected load of the dimmer, take the PowerFactor of the dimmable LED lighting into account. See the global calculation below for this.
Nominal power = number of LED light sources * Nominal power
LED / -PowerFactor.
Example: 10 lamps * (5W per lamp / 0.8 PowerFactor) = 62.5 Watt