Technical Specifications
HMW39/RF
Product type | RF wireless microwave DALI sensor (tri-level control) |
---|---|
Operating voltage | 120∼277VAC 50/60Hz |
Rated load | Maximum 20pcs DALI devices, Maximum 40mA |
Power consumption | ‹ 1.5W |
Detection angle | 360° |
Detection area (Max.)* | Installation Height : 20m (forklift) 15m (person) |
Detection Range (0) :20m
Detection range| 10% / 50% / 75% / 100%
Hold time| 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time| Os/ 10s/ 1nnin / 5nnin/ 10min/ 30min/ 1h/+co
Stand-by dimming level| 10% / 20% / 30% / 50%
Daylight threshold| 2 ∼ 500Lux, Disable
RF transmission distance| 30 meters in the open area
RF frequency| 868MHz (FSK mode)
Warming up time| 20s
Operating temperature| -20°C ∼ +50°C
IP rating| IP65
HC034RF
Product type | RF wireless receiver |
---|---|
Operating voltage | 220-240V 50Hz |
Rated load | Capacitive:400W; Resistive:1200W |
IP rating | IP20 |
Installation
Warnings:
- Installation must be carried out by a qualified engineer in accordance with local regulations.
- Disconnect power supply before installing.
- Install to a solid surface – vibrations may cause is-triggering.
- Ensure environmental conditions are suitable for electronic equipment
A. Ceiling mount
B. Screw to the Luminaire by conduit
C. Attach to the shade by clamp
HC034RF (RF receiver)
Rotary Switch for RF grouping
15 channels are available for fast grouping via a rotary switch on both
HMW39/RF and HC034RF. By simply selecting the same channel on each unit, the
grouping is automatically completed.
Noted: channel “0” is not for fast grouping, and sensors can only be
grouped by remote control.
Functions
4.1 Tri-level Control (Corridor Function)
Hytronik builds this function inside the motion sensor to achieve tri-level
control, for some areas it requires a light change notice before switch-off.
It offers 3 levels of light: 100%–>dimmed light–>off; and 2 periods of
selectable waiting time: motion hold-time and stand-by period; Selectable
daylight threshold and freedom of detection area.
4.2 Lux Off Function
The built-in daylight sensor can read ambient natural light and switch off the
fixture automatically whenever artificial light is not required (natural light
lux level exceeds daylight threshold).
Note: if the stand-by time is preset at “+∞”, the fixture never switches
off even when natural light is sufficient.
4.3 Load Indication
The light will flash ONCE rapidly after receiving the command from the remote
controller.
Note: There is no load indication (the light will not flash) when the
button ON/OFF, POWER 100% or POWER 80% is pressed.
RF grouping
Short press the “Learn/Erase” button on RC to the receiver to activate pairing
mode, and the receiver unit will beep once every second for 3min.
Note: up to 30 units can be paired.
Short press the “Transmit” button on RC to the commander, the red indicator on the commander unit will flash for 3 times to send the transmission signal.
Upon receiving the transmission signal, the indicator on the receiver unit
will flash quickly then slowly to indicate the success of pairing. One more
short press on the “Learn/Erase” button to the receiver unit to complete the
pairing process, the receiver unit will quit the pairing mode.
Erase:
Long press the “Learn/Erase” button for 3s to the sensor unit, the indicator
rapidly flashes 12 times, all commands that it has received before will be
erased.
Wiring Diagram
Detection Pattern
Ceiling mounted detection pattern (m)
- For a single person walking across, the detection range is reduced by 1/3.
Descriptions of the Button Functions (remote control HRC-11)
Permanent OWOFF [buttonC) 1
Press button 1 to select permanent ON or permanent OFF mode.
- Press button 2/4 to resume automatic operation.
The mode will change to AUTO Mode after power failure.
RESET[ button 2]
Press button( 2 ) , all settings go back to the default setting :
HMW39RF:Detection range:100%, hold time:1min, stand-by time:5min,stand-by
dimming level:20%, daylight sensor:lux disable, RX 100% HCO34RF: Detection
range:100%, hold time:10min, stand-by time:30min,stand-by dimming level:20%,
daylight sensor:lux disable, RX 100%
Shift [ button3
Press button 3 , the LED on the top left corner will flash to indicate
mode selection.
All values/settings in RED are invalid for 20 seconds.
Auto Mode [ button 4)]
Press button 4 to initiate automatic mode. The sensor starts working and
all settings remain as before the light was switched ON/OFF.
Note: the function of semi-auto is disabled.
Power output [ button5)]
Press button 5 , the light output shifts between 80% and 100%. Note: the
function of “Sensor off” and “Twilight” are disabled.
Brightness +/- [ button6]
Press button 6 to adjust the light brightness between 10%-100%.
Scene prog. [ zone 7 ) ] (One-key-commissioning)
- Press button “start” to program.
- Select the buttons in 8 “Detection range”, 9 )/ 10 )”Daylight hreshold”, ( 11 “Hold time”,( 12 )”Stand-by time”,( 13 )”Stand-by dimming level” to set all parameters.
- Press the button “Memory” to save all the settings programmed in the remote control.
- Press the button “Apply” to set the settings for each sensor unit(s). For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +00, stand-by dimming level 30%, the steps should be as follows: Press button 7 Start, button 8 100%. 10 Disable, 3 Shift, 11 5min, 3 Shift, 12 +∞ 13 30%, 7 Memory. By pointing to the sensor unit(s) and pressing 7 Apply, all settings are passed on the sensor(s).
Detection range [ zone 8]
Press buttons in zone ® to set detection range at 100% / 75% / 50% / 10%.
Note: Disabled for HCO34RF.
Daylight threshold [ zone 9) ]
Press buttons in zone 0 to set the daylight sensor at 2Lux / 10Lux / 50Lux / 100Lux / 300Lux / 500Lux or Disable. Note:
- To set daylight sensor at 100Lux / 300 Lux / 500Lux, press the button ® Shift at first.
- Disabled for HCO34RF.
Ambient daylight threshold [ button 10)]
- Press the button 3 Shift, the red LED is on for indication.
- Press button 10 , the ambient lux level is sampled and set as the new daylight threshold.
Hold time [ zone 11]
Press buttons in zone (11)t o set the hold time at 2s / 30s / lmin / 5min / 10min / 15min / 20min / 30min.
Note:
- To set hold-time at 30s / 5min / 15min / 30min, press button®Shift at first.
- 2s is for testing purposes only, stand-by period and daylight sensor settings are disabled in this mode.
*To exit from Test mode, press button 2 or any button in zone 11.
Stand-by time [ zone 12]
Press buttons in zone 12 to set the stand-by period at Os / lOs / 1min /
5min / 10min / 30min / 1h / +0c.
Note: “Os” means on/off control; “+00” means bi-level control, 100% on when
motion is detected and remains at the stand-by dimming level when no presence
is detected after hold-time.
Stand-by dimming level [ zone 13]
Press buttons in zone 13 to set the stand-by dimming level at 10% / 20% /
30% / 50%. Note.the function of 24h / 12h / 4h / 30s are disabled.
Dual tech & RF mode [ zone 14]
- HF, PIR, HF+PIR, HF/PIR are disabled.
- Short press the button “Learn/Erase” to activate pairing mode on all receiver (slave) units to be paired. Note: up to 30 units can be paired.
- Short press button “Transmit” at the commander unit(master), the LED will flash for 3 times to indicate that the transmission signal has been sent. The receiver units will rapidly beep for 3 times in 1s to indicate the success of pairing.
- Long press the “Learn/Erase” button for 3s, and the receiver unit clears all commands it has received before.
- Press button RX100%, the light on receiver unit is 100% on upon receiving RF on signal; Press “RX STBY%” button, the light(s) goes to preset stand-by dimming level directly.
Troubleshooting
MALFUNCTION CAUSE REMEDY | CAUSE | REMEDY |
---|---|---|
The fixture does not light up | Incorrect daylight threshold setting | Adjust |
daylight threshold setting
Faulty fixture| Replace fixture
No power supply| Check power to the sensor
Detection zone not targeted| Check detection area setting
The fixture is always on| Continous movement in the detection zone| Check
detection area setting
The fixture is on when it should not| Sudden change in temperature due to
weather (wind, rain, snow) or air expelled from fans, open windows| Adjust
zone, change installation site