Specification
Power Voltage: 9-24VDC
Power Consumption: 1W
Frequency : 125kHz + 13.56MHz
RF Reading Range: 5-15 cm
Dimension (mm) : EU : 88(H)X86(W)X34(D)
US:110(H)X81(W)X34(D)
Connector Table
CN1 8PIN Cable
Function | Dip-switch | Wire | Color | Description |
---|---|---|---|---|
SW1 | SW2 | |||
ABA13 | ON | ON | ||
WG34/64 | ON | OFF | ||
ABA10 | OFF | ON | ||
WG26/64 | OFF | OFF | ||
CN1 Main | WG Output | 1 | Blue White | WG DATA 1 Output |
2 | Green White | WG DATA 0 Output | ||
Card Present | 3 | White | Card Present ( Low output) | |
LED | 4 | Orange | LED Red Input (Input Low) | |
5 | Purple | LED Green Input (Input Low) | ||
Buzzer | 6 | Gray | Transistor Output Max. 12V/100mA |
(Open Collector Active Low)
Power| 7| Thick Red| DC 12V
8| Thick Black| DC 0V
CN2 2PIN Cable
Function | Wire | Color | Description |
---|---|---|---|
RS-485 Port | 1 | Thick Green | RS-485(B-) |
2 | Thick Blue | RS-485(A+) |
Diagram
Installation
- Pull the cables from the square holes of the EVA foam gasket and mounting plate.
- Use a screwdriver to screw the mounting plate B onto the wall with Flat Head Cap Philips Tapping Screws (Excluded, the Installer should prepare before installation.
- Connect the cables to the backside of body C and attach C to B at the lower position of B. Push C up to make the cogging hooked completely.
- Use the Allen key and screws to assemble the body C onto the mounting plate B. Attach the Back Cover D to C.
- Hands-off and clear any objects around the 888 Series. Turn on the power and LED will light up and a beep will sound. Wait for the Touch IC to start for 10 sec. to operate.
Cable selection:
Use AWG 22-24 Shielded Twist the Pair to avoid star wiring. Use CAT5 for
TCP/IP connection.
Flush Mount Illuminated dual-band Access Reader
Documents / Resources
|
SOYAL AR-888-US Proximity Controller
Keypad
[pdf] User Guide
AR-888-US Proximity Controller Keypad, AR-888-US, Proximity Controller Keypad,
Proximity Controller, Proximity Keypad, Controller Keypad, Keypad
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>