Schreder Ecoblast 3 LED Solution for Sports Lightning Instruction Manual
- June 4, 2024
- Schreder
Table of Contents
- INSTALLATION INSTRUCTIONS
- PRODUCT OVERVIEW
- GEARBLAST – DRIVER OVERVIEW
- LAYOUT AND MOUNTING
- Minimum screw requirement:
- DRIVER CONNECTION-DRIVER MOUNTED ON FORK
- MAINS CONNECTION
- DALI
- DMX
- OPTICAL BLOCK
- DRIVER CONNECTION – REMOTE DRIVER INSTALLATION
- ANGLE ADJUSTMENT
- OFFSET LAYOUT INSTALLATION
- OFFSET LAYOUT LIMITATIONS
- INRUSH DATA AND LUMINAIRES PER CIRCUIT BREAKER
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Eco blast 3 LED Solution for Sports Lightning
Instruction Manual
INSTALLATION INSTRUCTIONS
PRODUCT OVERVIEW
***** Weights correspond to remote driver installation, with QPD connector for ECO BLAST 3-4, with Junction box for ECO BLAST 5-6. Attached driver means an additional 7.1kg (15.7 lbs) for ECO BLAST 3-4, an additional 7.5kg (16.5 lbs) for ECO BLAST 5-6 (including driver holder plates). Tolerance on weight values is +/-5%.
GEARBLAST – DRIVER OVERVIEW
LAYOUT AND MOUNTING
**ECOBLAST 3
ECOBLAST 4-5-6
SAFETY CABLE
**
-
For installations over 3 meters in height:
the secondary safety system application is mandatory, which is appropriated for the luminaire load (for example steel safety cable) -
600mm safety cable can be optionally ordered with the luminaire
Minimum screw requirement:
Vibration standard | IEC 0.5g / ANSI 1.5g | ANSI 3g |
---|---|---|
Minimum fastener requirement | 1x M20 8.8 or A2-70 | |
DIN9021 large plain washer | 1x M20 8.8 or A2-70 + 1x M10 8.8 or A2-70 DIN125 |
plain washers
Tightening torques| M20: 150-175 Nm| M20: 150-175 Nm
M10: 35-40 Nm
Recommended using an anti-seizing agent (Tikal Tef-Gel®)!
Fasteners not included in the
package!
The relevant CSS and weight values can be found in this document.
DRIVER CONNECTION-DRIVER MOUNTED ON FORK
**** AC and CONTROL cables must be connected by the installer
|
---|---
REMOVE SCREWS| CONNECT THE AC, CONTROL, AND LED MODULE WIRES
MAKE THE ELECTRICAL CONNECTION
blade dimensions: 3.5 x 0.5 mm
**** Use appropriate tools for electrical connections!| TIGHTEN THE DRIVER
COVER
MAINS CONNECTION
**CLAMPING RANGE: 10-17MM
In case of using a smaller outer diameter cable, please replace the cable
gland’s internal gasket with the one attached in the packaging.
Modified clamping range: 7-13 mm
**
DALI
2X M16 CABLE GLAND
CLAMPING RANGE: 5-10MM
DMX
2X M16 CABLE GLAND
CLAMPING RANGE: 5-10MM
OPTICAL BLOCK
M32 CABLE GLAND
CLAMPING RANGE: 13-21MM
In case of using a smaller outer diameter cable, please replace the cable
gland’s internal gasket with the one attached in the packaging.
Modified clamping range: 8-14 mm
2 channels
CONNECTOR ID | CABLE ID EU | CABLE ID US |
---|---|---|
GND | Yellow/Green | Green |
+1 | 1 / Brown | 1 / Pink |
-1 | 2 / Blue | 2 / White |
+3 | 3 / Black | 3 / Black |
-3 | 4 / Grey | 4 /White-Black |
CONNECTOR ID | CABLE ID EU | CABLE ID US |
---|---|---|
GND | Yellow/Green | Green |
+1 | 1 | 1 / Pink |
-1 | 2 | 2 / White |
+2 | 3 | 3 / Black |
-2 | 4 | 4 / White-Black |
+3 | 5 | 5 / Blue |
-3 | 6 | 6 / Orange |
DRIVER CONNECTION – REMOTE DRIVER INSTALLATION
L<100m WIRE SIZE 1,5mm2
100<L<200m WIRE SIZE 2,5mm2
MAX REMOTE DISTANCE 200M!| 3 + 4 MODULE TYPES
AVAILABLE WITH QPD CONNECTOR| 5 + 6 MODULE TYPES
AVAILABLE WITH JUNCTION BOX
---|---|---
QPD CONNECTOR
TYPE (5-CORE WIRE)
THE INTERCONNECTION CABLE IS NOT INCLUDED IN THE PACKAGE!
| JUNCTION BOX
TYPE (7-CORE WIRE)
THE INTERCONNECTION CABLE IS NOT INCLUDED IN THE PACKAGE!
---|---
DRIVER CONNECTION ACCORDING TO PAGES 3-4-5
1a
DRIVER TERMINAL | QPD ID |
---|---|
GND | |
1 | 1 |
-1 | 2 |
3 | 3 |
-3 | 4 |
CLAMPING RANGE:
Ø9-16mm 5G1.5mm2 – 5G2.5mm2
Remove screws from the junction box cover
Connect the junction box to the junction box support plate
Make the electrical connection with WAGO terminal blocks
Tighten the junction box cover
ANGLE ADJUSTMENT
**ECOBLAST 3
ALLOWED tilt angle is between -10° to 70°
STEPS
**
- Loosen the clamp screws (4xM8)
- Adjust the tilting angle
- Tighten the clamp screws with 13Nm
ANGLE LIMITATIONS
****|
---|---
Direct installation| Suspended installation
ECOBLAST 4-5-6
The swing arm inclination is adjustable in 5-degree increments relative to
fork base
Separate scale sheet for adjusting optical block angles relative to the swing
arm The inclination angle of the swing arm and the optical blocks can be
adjusted separately
ALLOWED tilt angle is between -10° to 70°
OFFSET LAYOUT INSTALLATION
REASSEMBLY STEPS
Lay the complete luminaire with all optical block front faces touching the
ground|
---|---
Loosen the screws of the 2 main clamps and the 2 set screws of the brackets|
Remove the shaft by rotating and pulling it in one direction|
Remove the 2 main clamps, 4 screws, nuts, washers, and anti-rotation clips
from the initial position|
Remove the 2 main clamps, 4 screws, nuts, washers, and anti-rotation clips
from the initial position|
Align the fork to the brackets with the 2nd position hole|
Insert and rotate the shaft until the flat surface is toward the set screws in
the brackets|
|
OFFSET LAYOUT LIMITATIONS
In the case of the standard mounting option, the angle of inclination can only be between 60° and 70° without any collision
INRUSH DATA AND LUMINAIRES PER CIRCUIT BREAKER
The maximum number of LED drivers connectable to a single MCB is reported in
the following table for each nominal input voltage. a maximum number of LED
drivers connectable to a single MCB is reported in the following table for
each nominal input voltage. Due to the different kinds of circuit breakers
available on the market, this table just for reference. to the different
kinds of circuit breakers available on the market, this table is just for
reference.
1200 W
VIN| Inrush Current Data| | | | | | Drivers For Each Circuit Breaker| | | |
---|---|---|---|---|---|---|---|---|---|---|---
Nominal
[VAC]| I peak
[A]| Half Value Time [its]| | | Type B| | | | | Type C| | | | | Type D| |
10A| 16A| 20A| 25A| 32A| 10A| 16A| 20A| 25A| 32A| 10A| 16A| 20A| 25A| 32A
220/240| 26| 6400| 1| 2| 2| 3| 4| 1| 2| 2| 3| 4| 1| 2| 2| 3| 4
400| 14| 4700| 2| 3| 4| 5| 6| 2| 3| 4| 5| 6| 2| 3| 4| 5| 6
1800 W
VIN| Inrush Current Data| | | | | | Drivers For Each Circuit Breaker| | | |
---|---|---|---|---|---|---|---|---|---|---|---
Nominal
[VAC]| I peak [A]| Half Value
Time [µs]| | | Type B| | | | | Type C| | | | | Type D| |
10A| 16A| 20A| 25A| 32A| 10A| 16A| 20A| 25A| 32A| 10A| 16A| 20A| 25A| 32A
220/240| 26| 6400| 1| 1| 2| 2| 3| 1| 1| 2| 2| 3| 1| 1| 2| 2| 3
400| 20| 1500| 1| 2| 2| 3| 4| 1| 2| 2| 3| 4| 1| 2| 2| 3| 4
SAFETY INSTRUCTIONS
The light source contained in this luminaire shall only be replaced by the
manufacturer or his service agent or a similarly qualified person. Always
switch off the power prior to installation, maintenance, or repair activities.
RISK GROUP 2 – CAUTION! Hazardous optical radiation may be emitted from
this product. Do not stare at the luminaire when operating as it may be
harmful to the eyes. The luminaire should be positioned so that prolonged
staring at the luminaire at a distance of fewer than 0.2m is not expected.
This product contains a light source of an energy efficiency class G or
higher. In the case of PVC insulated mains cable, the installer MUST ensure
that the WHOLE cable is protected against climatic conditions, especially UV
rays and rain, by making sure that the cable is contained inside the luminaire
and pole
Y-connection: In case of damage to the wire, it has to be replaced only
by the manufacturer, distributor, or an expert, to avoid risks.
01-85-943 | DOC-0018707 rev J | 12-2021
www.schreder.com