Concord 97G2V Two Stage Variable Speed Gas Furnace Owner’s Manual
- June 4, 2024
- CONCORD
Table of Contents
97G2V
PRODUCT SPECIFICATIONS
TWO STAGE VARIABLE SPEED
GAS FURNACE FORM NO. 97G2V-100 (10/2023)
97G2V Two Stage Variable Speed Gas Furnace
CONFIGURATIONS
- Upflow / Horizontal
- Downflow
VENTING
- 2-speed induced draft motor with stainless steel shaft, steel ball bearings, and fan cooled for long life
- Vent materials for Canadian applications must comply with ULC S636
- Certified for direct vent (2-pipe) or non-direct (1-pipe) applications
- Direct vent refers to a combustion air supply intake pipe installed in conjunction with flue gas vent pipe.
INSTALLATION FEATURES
- Left or right gas and electric entry
- Zero step horizontal conversion
- Removable floor base (upflow/horizontal units) for bottom return air
- All models comply with California’s South Coast Air Quality Management district Low NOx requirements
HEAT EXCHANGER DESIGN
- Aluminized steel primary heat exchanger with crimped nonwelded construction
- AL29-4C Stainless steel secondary heat exchanger
- Non-welded crimped S-curve primary heat exchanger design for maximum durability
BURNERS
- Aluminized steel in shot burners for smooth ignition
- Isolated burner enclosure for quiet operation
CABINET CONSTRUCTION
- Compact 33″ height
- Standardized widths for easy coil fit
- Unitized construction for cabinet integrity
- Heat exchanger compartment is insulated to increase efficiency and reduce sound levels
- Baked on pre painted steel cabinet finish
AIR DELIVERY SYSTEM
- Efficient ECM variable speed blower motor
- Motor features “soft start” and “soft stop” for quiet operation
- Active and passive dehumidification feature
- Easily removable slide-out blower design
- Dynamically balanced blower wheel with resilient motor mounts for smooth and quiet operation
CONTROLS
- Two stage gas valve
- Integrated ignition and fan control
- System Sentry™ control retains last five (5) fault codes with push button memory recall, regardless of power interruption
- Hot surface ignition system uses silicon nitride ignitor
- Control features 120 volt electronic air cleaner and humidifier terminals
- Control circuit is fuse protected
- Color coded control wiring
- Compatible with single or two stage thermostats for heating.
- Two stage thermostat is recommended when installed with two stage cooling unit.
WARRANTY
10 year limited parts warranty / lifetime heat exchanger warranty available.
See limited warranty document for details.
California Only
If installed in South Coast Air Quality Management District (SCAQMD) only:
This furnace does not meet the SCAQMD Rule 1111 NOx emission limit (14 ng/J),
and thus is subject to a mitigation fee of up to $450. This furnace is not
eligible for the Clean Air Furnace Rebate Program:
www.CleanAirFurnaceRebate.com.
If installed in San Joaquin Valley Air Pollution Control District (SJVAPCD)
only: This furnace does not meet the SJVAPCD Rule 4905 NOx emission limit (14
ng/J), and thus is subject to a mitigation fee of up to $450.
MODEL NUMBER GUIDE
PHYSICAL AND ELECTRICAL DATA
| M ODEL| 1ST STAGE| 2ND STAGE| AFUE (ICUS)|
NOM. COOLING CAPACITY (TONS)| GAS INLET (IN.)|
VOLTS/ HZ/ PHASE| MIN. TIME DELAY BREAKER OR
FUSE| NOMINAL F.L.A.| TRANS. (V.A.)| APPROX. WEIGHT
(LBS.)
---|---|---|---|---|---|---|---|---|---|---|---
INPUT (BTUH)| OUTPUT (BTUH)| INPUT (BTUH)| OUTPUT
(BTUH)
UPFLOW/HORIZONTAL| 97G2UH045BV12| 29,000| 28,000| 44,000| 43,000| 97.0|
3| 1/2| 120-60-1| 15| 7.7| 40| 120
97G2UH070BV12| 43,000| 42,000| 66,000| 64,000| 97.0| 3| 1/2| 120-60-1| 15|
7.7| 40| 124
97G2UH090CV12| 57,000| 56,000| 88,000| 85,000| 97.0| 3| 1/2| 120-60-1| 15|
7.7| 40| 144
97G2UH090CV20| 57,000| 56,000| 88,000| 86,000| 97.0| 5| 1/2| 120-60-1| 20|
12.8| 40| 153
97G2UH110CV20| 72,000| 70,000| 110,000| 107,000| 97.0| 4| 1/2| 120-60-1| 15|
12.8| 40| 159
97G2UH135DV20| 86,000| 84,000| 132,000| 127,000| 97.0| 5| 1/2| 120-60-1| 20|
12.8| 40| 178
DOWNFLOW| 97G2DF070BV16| 43,000| 42,000| 66,000| 64,000| 97.0| 4| 1/2|
120-60-1| 15| 10.1| 40| 136
97G2DF090CV20| 57,000| 56,000| 88,000| 86,000| 97.0| 5| 1/2| 120-60-1| 20|
12.8| 40| 152
97G2DF110CV20| 72,000| 70,000| 110,000| 108,000| 97.0| 5| 1/2| 120-60-1| 20|
12.8| 40| 163
Note: For vent length and clearances to combustibles, please reference
installation instructions.
FILTER REQUIREMENT DATA
Airflow Descriptor | Disposable Filters | Cleanable Filters |
---|---|---|
Minimum Area (sq. in.) | Minimum Area (sq.in.) | |
12 | 576 | 288 |
16 | 768 | 384 |
20 | 960 | 480 |
- The Airflow Descriptor is the two digits following the “B” , “C”, or “D” in the model number; e.g. “20” is the Airflow Descriptor.
- Areas shown for permanent filters are based on filters rated at 600 feet per minute face velocity.
BLOWER PERFORMANCE DATA – UPFLOW / HORIZONTAL
| MODEL| MOTOR SIZE (HP)| BLOWER SIZE| HEATING
TEMP. RISE (°F)| HEATING CFM @ .10″ –
.80″ W.C.| COOLING STAGE| COOLING CFM @ .10″
– .80″ W.C.| SPEED ADJUST.
---|---|---|---|---|---|---|---|---
SETTING “D”| SETTING “C”| SETTING “B”| SETTING
“A”| SETTING “D”| SETTING “C”| SETTING “B”|
SETTING “A”
UPFLOW / HORIZONTAL| 97G2UH045BV12| 1/2| 10×9| 35-65 High Fire| 745|
875| 990| 1005| 2nd Stage| 905| 1075| 1210| 1370| +
685| 765| 895| 910| 815| 980| 1120| 1255| Norm
610| 695| 785| 810| 720| 885| 1020| 1135| –
20-50 Low Fire| 685| 765| 895| 910| 1st Stage| 595| 760| 865| 980| +
620| 705| 800| 820| 540| 660| 785| 890| Norm
545| 625| 715| 725| 485| 600| 695| 790| –
97G2UH070BV12| 1/2| 10×9| 50-80 High Fire| 965| 1060| 1130| 1255| 2nd Stage|
860| 1060| 1215| 1365| +
880| 960| 990| 1140| 810| 960| 1130| 1265| Norm
810| 840| 890| 1030| 705| 840| 1005| 1140| –
25-55 Low Fire| 940| 990| 1070| 1195| 1st Stage| 600| 740| 840| 970| +
830| 895| 965| 1100| 555| 665| 770| 855| Norm
755| 825| 840| 975| 500| 600| 680| 790| –
97G2UH090CV12| 1/2| 10×9| 60-90 High Fire| 1060| 1135| 1240| 1315| 2nd Stage|
875| 1040| 1210| 1360| +
960| 1040| 1120| 1199| 800| 945| 1100| 1245| Norm
830| 935| 980| 1084| 720| 840| 970| 1115| –
30-60 Low Fire| 960| 1040| 1120| 1206| 1st Stage| 625| 710| 830| 950| +
875| 945| 995| 1100| 565| 670| 760| 860| Norm
790| 840| 920| 950| 520| 610| 685| 785| –
97G2UH090CV20| 1| 11×11| 40-70 High Fire| 1450| 1565| 1725| 1865| 2nd Stage|
1385| 1595| 1820| 2020| +
1310| 1450| 1585| 1690| 1225| 1465| 1645| 1885| Norm
1155| 1305| 1450| 1545| 1065| 1320| 1504| 1675| –
25-55 Low Fire| 1120| 1265| 1420| 1520| 1st Stage| 935| 1055| 1275| 1465| +
965| 1120| 1285| 1395| 835| 980| 1120| 1335| Norm
865| 950| 1120| 1235| 740| 870| 1010| 1150| –
97G2UH110CV20| 1| 11×11| 45-75 High Fire| 1560| 1760| 1905| 1955| 2nd Stage|
1310| 1560| 1745| 1955| +
1415| 1610| 1740| 1795| 1220| 1405| 1570| 1795| Norm
1285| 1485| 1560| 1635| 1075| 1270| 1430| 1635| –
35-65 Low Fire| 1155| 1325| 1420| 1500| 1st Stage| 935| 1065| 1245| 1405| +
1055| 1200| 1310| 1360| 865| 970| 1145| 1280| Norm
935| 1075| 1170| 1245| 790| 890| 1025| 1165| –
97G2UH135DV20| 1| 11×11| 45-75 High Fire| 1650| 1845| 2000| 2055| 2nd Stage|
1395| 1640| 1840| 2055| +
1495| 1660| 1880| 1905| 1290| 1480| 1660| 1905| Norm
1360| 1500| 1670| 1705| 1170| 1330| 1500| 1705| –
35-65 Low Fire| 1300| 1435| 1630| 1652| 1st Stage| 1015| 1160| 1330| 1480| +
1190| 1325| 1465| 1491| 940| 1085| 1200| 1345| Norm
1095| 1190| 1340| 1343| 870| 965| 1110| 1225| –
BLOWER PERFORMANCE DATA – DOWNFLOW
| MODEL| MOTOR SIZE (HP)| BLOWER SIZE| HEATING
TEMP. RISE (°F)| HEATING CFM @ .10″ –
.80″ W.C.| COOLING STAGE| COOLING CFM @ .10″
– .80″ W.C.| SPEED ADJUST.
---|---|---|---|---|---|---|---|---
SETTING “D”| SETTING “C”| SETTING “B”| SETTING
“A”| SETTING “D”| SETTING “C”| SETTING “B”|
SETTING “A”
DOWNFLOW| 97G2DF070BV16| 3/4| 11×10| ****
35-65 High Fire
| 1110| 1305| 1430| 1700| 2nd Stage| 1110| 1340| 1575| 1800| +
995| 1175| 1315| 1520| 995| 1230| 1420| 1650| Norm
880| 1055| 1170| 1365| 880| 1085| 1290| 1460| –
25-55 Low Fire| 860| 1020| 1140| 1340| 1st Stage| 740| 915| 1055| 1255| +
795| 910| 1030| 1230| 660| 820| 940| 1120| Norm
680| 825| 910| 1085| 575| 735| 850| 995| –
97G2DF090CV20| 1| 11×11| 40-70 High Fire| 1395| 1555| 1695| 1825| 2nd Stage|
1335| 1600| 1750| 1980| +
1275| 1395| 1585| 1670| 1225| 1450| 1630| 1830| Norm
1145| 1265| 1405| 1525| 1120| 1270| 1450| 1660| –
30-60 Low Fire| 1130| 1230| 1365| 1475| 1st Stage| 955| 1115| 1265| 1450| +
1040| 1130| 1250| 1340| 855| 1005| 1150| 1285| Norm
910| 1025| 1130| 1210| 750| 890| 1060| 1170| –
97G2DF110CV20| 1| 11×11| 45-75 High Fire| 1595| 1795| 1955| 2010| 2nd Stage|
1335| 1585| 1790| 2010| +
1450| 1615| 1795| 1865| 1220| 1440| 1630| 1865| Norm
1290| 1460| 1610| 1680| 1100| 1275| 1475| 1680| –
35-65 Low Fire| 1165| 1305| 1465| 1547| 1st Stage| 920| 1095| 1265| 1440| +
1055| 1185| 1315| 1404| 830| 965| 1130| 1290| Norm
930| 1070| 1180| 1272| 735| 860| 1035| 1155| –
DIMENSIONS (IN.) – UPFLOW / HORIZONTAL
| **MODEL| A| B| C| D
---|---|---|---|---|---
UPFLOW/HORIZONTAL**| 97G2UH045BV12| 17-1/2| 16-3/8| 16| 7-5/8
97G2UH070BV12| 17-1/2| 16-3/8| 16| 7-5/8
97G2UH090CV12| 21| 19-7/8| 19-1/2| 9-3/8
97G2UH090CV20| 21| 19-7/8| 19-1/2| 9-3/8
97G2UH110CV20| 21| 19-7/8| 19-1/2| 9-3/8
97G2UH135DV20| 24-1/2| 23-3/8| 23| 11-1/8
DIMENSIONS (IN.) – DOWNFLOW
| MODEL| A| B| C| D
---|---|---|---|---|---
DOWNFLOW| 97G2DF070BV16| 17-1/2| 16-3/8| 16| 15-1/2
97G2DF090CV20| 21| 19-7/8| 19-1/2| 19
97G2DF110CV20| 21| 19-7/8| 19-1/2| 19
ACCESSORY LIST
CATALOG NUMBER | DESCRIPTION |
---|
EXTERNAL FILTER RACK KITS
1.841018| 1 PACK (16 X 25)
1.841039| 10 PACK (16 X 25)
NATURAL TO LP KITS
11K48| 2-STAGE – 90
11K47| HIGH ALTITUDE 2-STAGE (>4500FT.)
RETURN AIR BASE
68W62| 17.5″ B WIDTH
68W63| 21.0″ C WIDTH
68W64| 24.5″ D WIDTH
DOWNFLOW COMBUSTIBLE FLOORING BASE
11M60| 17.5″ B WIDTH
11M61| 21.0″ C WIDTH
NIGHT SERVICE KITS
84W50| TWO STAGE
HORIZONTAL SUSPENSION KIT
51W10| 80% & 90% KIT
FLUSH MOUNT TERMINATION (90% FURNACES ONLY) US ONLY
51W11| 2″ & 3″ VENT VERSION
CONCENTRIC VENT KIT (90% FURNACES ONLY) US ONLY
71M80| 1-1/2″ VENT VERSION
69M29| 2″ VENT VERSION
60L46| 3″ VENT VERSION
CONCENTRIC VENT KIT (90% FURNACES ONLY) CANADA
44W92| 1-1/2″ AND 2″ VENT VERSION
44W93| 3″ VENT VERSION
For vent length and clearances to combustibles, please reference installation
instructions.
All specifications and illustrations subject to change without notice and
without incurring obligations.
FORM NO. 97G2V-100 (10/2023)
© 2023 Allied Air Enterprises LLC,
a Lennox International Inc. Company
Printed in the U.S.A.