User Manual 19D-23C
Single Phase Energy Meter(CTs)
Version:1.0
19D-23C Single Phase Energy Meter
Read me
When you use 19D-23C single phase energy meter, be sure to read this user
manual carefully, and be able to fully understand the implications, the
correct guidance of operations in accordance with user manual, which will help
you make better use of 19D-23C single phase energy meter, and help to solve
the various problems at the scene.
- Before the meter turning on the power supply, be sure that the power supply within the provisions of the instrument;
- When installation, the current input terminal must non-open, voltage input terminals must Non- short circuit;
- Communication terminal (RS232/RS485) is strictly prohibited to impose on high pressure;
- Be sure the instrument wiring consistent with the internal system settings;
- When communicating with the PC, instrument communication parameters must be consistent with the PC.
- Please read this user manual carefully
- Please save this document
SUMMARIZE
Single-phase rail-type electric energy meter is an intelligent device used in
medium and low voltage systems (6-35KV and 0.4KV). It integrates data
acquisition and control functions, adopts segment code LCD screen, and has
single-phase AC power measurement and calculation. Energy accumulation, RS485
communication and other functions.
19D-23C single phase energy meter is a 3M width DIN rail energy meter, and use
external CT to expand the current range max to 999A. With RS485-RTU and pulse
output port, the LCD screen provides measurement circuit current and voltage
reading. This 19D-23C single phase energy meter suits scenarios such as
residential, public facilities, and industrial use.
FEATURES
- Maximum 999A, 1A/5A CT connection
- Provide energy import and export measurement (IMP & EXP)
- With one port energy pulse output
- RS485 Modbus communication (optional)
- Standard 35mm din rail mounting, width 3M size
- Detect voltage, current, active/reactive energy, power, frequency, Max demand, etc.
APPLICATIONS
- All power parameter measurement;
- Energy measurement and electrical fire monitor and control;
- Transformers, generators, capacitors and electric motors distributed detection;
- Medium and low pressure systems;
- SCADA, EMS, DCS integrators.
TECHNICAL PARAMETERS
Measurement & Display
Voltage | Rated 230V RMS value, Accuracy 0.2%, |
---|---|
Current | Rated 5A, Optional 1A, CT Connection, RMS value. |
Accuracy 0.2%;
Overload| 1.2 times rated continuous; 1 seconds for 10 times the rated
Frequency| 50/60Hz, Accuracy +0.01Hz
Display| LCD with white backlit
Maximum display value| 9999999MkWh
AUX Power| 90-240V AC, <2W/10VA
Output
Digital port | RS-485 MODBUS-RTU |
---|---|
Pulse port | 1600imp/kWh |
Other parameters
Working environment| -25~55°C Altitude ≤2500m, 0~95%RH, non- condensing, non-
corrosive gas
---|---
Storage environment| -40~70C
Voltage tolerance| 2KV 1min
Shock voltage| 6KV-1.2uS waveform
Insulation| Input, output, power supply to Shell >5MQ
INSTALLATION AND START-UP
The manual you hold in your hand contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep it in safety conditions. The instrument must not be powered on and used until its definitive assembly is on the cabinet’s door.
If the instrument is not used as manufacturer’s specifications, the protection
of the instrument will be damaged.
When any protection failure is suspected to exist (for example, it presents
external visible damages), the instrument must be immediately powered off. In
this case contact a qualified service representative.
3.1.- Installation
Mounting
Instrument is to be mounted on 35mm Din-rail. Keep all connections into the
cabinet. Please note that with the instrument powered on, the terminals could
be dangerous to touch and cover opening actions or elements removal may allow
accessing dangerous parts. Therefore, the instrument must not be used until
this is completely installed. Dimension: Unit: mm Notes:
Input signal: 19D-23C using a separate acquisition calculate for each
measurement channel, to ensure consistent in use, for different load forms,
it’s a variety of connection mode. Access wire shall be met 3 square mm.
A. Voltage input
Input voltage should not exceed the rated input voltage products 450V.
Otherwise, you should use external VT. Suggest 1A fuse be installed in the
voltage input side.
B. Current Input
Standard input current is 5A or 1A, if greater than 5A/1A should use external
CT.
When the CT is connected with other meters, make sure wiring methods be used
in series.
Warning: Forbid to install a CT on the live feeder wire with open secondary
leads. This can be extremely dangerous!
Before remove the current input connection, must be sure to disconnect the
primary circuit or shorted secondary circuit of CT.
C. Sequence of wire
Warning: Please make sure that the input voltage and current corresponding to
the same phase, sequence, and the same direction; Otherwise, the Values and
symbols will be wrong!
(Power and Energy)
Always observe the physical orientation of CT (P1 – P2) when installing on the
feeder wire.
Always pay attention to wiring polarity and phasing when terminating the CT
leads to the 19D-23C.
S1 connect to Ix*, 82 connect to Ix.
The input network configuration of instrument depends on the CT number of the
system:
in the condition of 2 CT, select the three-phase, three-lines two components;
in the condition of 3 CT, select the three-phase, four-lines three component
mode.
Instrument connection mode, set of the instrument (programming input network
NET) should be the same load wiring as measured wiring. Otherwise, the
measurement instrument will lead to incorrect voltage or power.
D. Auxiliary power
19D-23C with universal (AC / DC) power input, if not for a special statement,
we provide the 90- 240AC/DC power interface for standard products, please
ensure that the auxiliary power can match with meter to prevent unexpected
damage.
A. Suggest install 1A fuse in the fire line side.
B. For the areas with poor power quality, suggest install lightning surge
suppressor and rapid burst suppressor to prevent lightning strikes.
3.2. – Connection Terminal
Upper connection terminal
16 | 15 | 14 | 13 | 12 | 11 | 10 | 9 | |
---|---|---|---|---|---|---|---|---|
UN | UN | I | I* |
16. Neutral Voltage input
13. Voltage A-phase input
Lower connection terminal
8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 |
---|---|---|---|---|---|---|---|
RP- | RP+ | 485G | 485B | 485A | N | L |
Note:
The terminal pin definition may change depends on customer order; please
refer to the label on the meter!
3.3. — Typical Wiring Note:
This connection drawing is for reference only; the actual connecting
terminal please refer to the label on the rear part.
WARNINGS!
If power = -0.01 is shown for any of the phases and voltage and current are
not zero for this phase, check out following points:
– Assure that A, B and C phases coincide in voltage and current.
– Correct polarity? Reverse the current transformer placed at this phase.
SCREEN DISPLAY
4.1.- Screen description:
Panel & Screen introduction
- – 7 digital show energy value
- – Symbol for SUM energy record value
- – Symbol for multi-tariff function
- – Imp for energy consumption, Export for energy generate
- – Symbol for Maximum demand
- – Symbol for average value
- – PF=power factory; Hz=Frequency
- – Pulse output channal 1 and channel 2
- -symbol for communication active
- – symbol for timer
- – symbol for screen locked
4.2.- Indicator light description:
Name | Function definition(when lighting ) |
---|---|
Active power reverse | |
Active energy pulse |
4.3.- Screen pages’ description:
Screen No. | Screen interface | Description |
---|---|---|
1 | Voltage: 228.8V | |
2 | Current: 5.000A | |
3 | Active power: 4800W | |
4 | Reactive power: 1200Var | |
5 | Apparent power: 3208VA | |
6 | Power factor: 1.000 | |
7 | Frequency of grid: 49.99Hz | |
8 | Active power: 50.00kwh | |
9 | Reactive power: 20.00kwh | |
10 | Active reactive energy: 5.00kvarh | |
11 | Negative reactive energy: 5.00kvarh |
OPERATION MENU DESCRIPTION
5.1 Button description
| Short press is the up button, turning the page to display the measurement
data, displaying voltage, current, power, electric energy and other
measurement data.
---|---
| Short press is the down key, the function is the same as the up key, but the
page turning direction is opposite;
Long press is the menu key to enter the programming menu, and it isalso a
function key to exit the menu step by step.
| Short press is the confirmation key to confirm and save the entered
information or displayed settings.
5.2 Main menu
In the case of measuring data, press the “menu” button, and the prompt of
“PASS” (that is, “password”) will appear, press the “OK” button to enter the
user-level password (default is 0001), press the button to enter the
programming in this state, the instrument provides three types of input
setting menu items: system factory commissioning (SYS), input (-IN-), and
communication (bus).
Adopt LCD display layered menu structure management. 5.2.1 Description of menu characters:
| (Password) User password
---|---
| (Error) Wrong input information
| (Input) User Display Data Settings Menu
| (Bus) Communication settings menu
| (System) System settings menu (for factory debugging, not open yet)
| (Code) Enter password
| (Data) Communication parameter setting
| (Address) Local communication address setting
| (Baud) Communication baud rate
| (0.8.1) Indicates 8 data bits, 1 stop bit, odd parity
| (e.8.1) Indicates 8 data bits, 1 stop bit, even parity
| (n.8.1) Indicates 8 data bits, 1 stop bit, no parity bit
| (U.scl) Select rated input voltage
| (l.scl) Select rated input current
| (R.ct) Set the current multiplier
| (R.pt) Set voltage ratio
| (System) System settings menu (for factory debugging, not open yet)
| Modify password value
PULSE OUTPUT (OPTIONAL)
19D-23C provides 1* pulse output for the active energy.
The host / PLC / DI module can cumulative the data of both the active and
reactive power energy sent by the pulse from opt coupler relay.
- Electrical specification: voltage VCC < 48V, 1z < 50mA.
- Pulse: 5000 imp / kWh, pulse up to 80ms.
This means: When the device detects 1 kWh, the port will generate 5000 pulse
Note:
1 kWh energy is for secondary side energy data, if there have PT and CT
accessed; primary side energy data is “1 kWh xPT ratiox CT ratio”.
Voltage (V) | Current (A) | Pulse constant (imp / kWh) |
---|---|---|
380 or 220 | 5 | |
1 | 5000 |
20000
100| 5
1| 20000
80000
Example: In measure time “T”, the received total pulse is “N”.
Primary side input of voltage is 10Kv
Primary side input of current is 400A.
Secondary side measurement range is 100V and 5A.
In the time “T”, energy accumulated is: N / 20000 x 100 x 80
COMMUNICATION INTERFACE
7.1.- Connection for RS485 BUS
The composition of the RS-485 cabling must be carried out with a meshed screen
cable (minimum 3 wire), diameter of not less than 0.5mm?, with a maximum
distance of 1,200 m between the 19D-23C… and the master unit. This Bus may
connect a maximum of 32pcs
Notes:
- For communication with the master unit, user can choose RS-485 to RS-232 converter or RS485 to USB adapter to use.
- For expand the number of devices in the communication network, a signal repeater can be used.
- RS485 PIN number is 58,59,60
- Due to product modifications or special requirements, the interface pin place may be change. For details, please refer to product label on the rear side
7.2.- MODBUS © Protocol
Modbus RTU Frame Format:
Address code | 1BYTE | Slave device address 1-247 |
---|---|---|
Function code | 1BYTE | Indicates the function codes like read coils / inputs |
Data code | 4BYTE | Starting address, high byte |
Starting address, low byte
Number of registers, high byte
Number of registers, low byte
Error Check code| 2BYTE| Cyclical Redundancy Check (CRC)
MODBUS FUNCTIONS:
Code | Meaning | Description |
---|---|---|
FUNCTION 01 | Read Coil Status | Only valid when equipped DO port |
FUNCTION 02 | Read Input Status | Only valid when equipped DI port |
FUNCTION 03 | Reading of n Words | This function permits to read all the |
electrical parameters
FUNCTION 05| Force Single coil| When DO in remote control mode can work
FUNCTION 06| Preset Single register| Disable in default
I need valid this code, please contact Blue Jay Sales Team before your order!
Note: Float data follow IEEE754, float low bit first, high bit next. (CD
AB)
7.3.- Register Map
7.3.1.- Basic power data—Primary Side
Register | Data | Byte mode | Instruction |
---|---|---|---|
Ox00 | U | float | 2 |
OxOc | I | float | 2 |
0x12 | P | float | 2 |
Ox1a | Q | float | 2 |
0x22 | S | float | 2 |
Ox2a | PF | float | 2 |
0x32 | FR | float | 2 |
0x34 | Ep+ | float | 2 |
0x36 | Ep- | float | 2 |
0x38 | Eq+ | float | 2 |
Ox3a | Eq- | float | 2 |
7.3.2.- Basic power data—Secondary Side
Register | Data | Byte mode | Instruction |
---|---|---|---|
Ox100 | Ua | int | 1 |
Current, Unit:0.001 A
0x106| la| int| 1
0x109| Pa| int| 1| Active power, Unit: W
Ox10d| Qa| int| 1| Reactive power, Unit: Var
Ox111| Sa| int| 1| Apparent power, Unit: Va
Ox115| PFa| int| 1| Power factor, 0-1.000
0x119| FR| int| 1| Frequency, unit:0.01hz
Ox11a| Ep+| int| 2| Positive active energy, Unit: Wh
Ox11c| Ep-| int| 2| Negative active energy, Unit: Wh
Ox11e| Eq+| int| 2| Inductive reactive power, Unit: Varh
Ox120| Eq-| int| 2| Capacitive reactive power
Notes:
- The data can be read out depends on your multi-function meter model, please refer to the corresponding product manual before build your software.
- Some software has different definitions of the start bit of register address, there will be offset, please add 1 for the right address. To get more info, please contact technical support.
7.4.- Example
Host inquiry slave device
Addr.| Func.| Data Address high| Data Address low| Data Number high| Data
number low| CRC16 low| CRC16 high
---|---|---|---|---|---|---|---
OCH| 03H| OOH| OOH| OOH| 06H| C4H| D5H
PC user ask upload UA, UB, UC, IA, IB, IC
Slave device response
Addr.| Func.| Byte count| Data1 high| Data1 low| Data2 high| Data2 low| Data3
high| Data3 low
---|---|---|---|---|---|---|---|---
OCH| 03H| OCH| 03H| E8H| 03H| E9H| 03H| E8H
Data4 high| Data4 low| Data5 high| Data5 low| Data6 high| Data6 low| CRC16
low| CRC16 high|
13H| 84H| 13H| 88H| 13H| 8AH| A6H| D6H|
Show the data:
UA=3E8H (100.0)
UB=3E9H (100.1)
UC=3E7H (99.9)
IA=1384H (4.996)
1B=1388H (5.000)
IC=138AH (5.002)
Notes:
- Blue Jay disable the 06 function in default setting, if Activated the write command, please check the host device program to avoid the meaningless write operation, that may reduce the reduce the register working life.
- When the write is unsuccessful, no return data from the slave device. In this addition, please re- send write inquiry again.
SAFETY CONSIDERATIONS
Al installation specification described at the previous chapters named:
INSTALLATION AND STARTUP, INSTALLATION MODES and SPECIFICATIONS.
Please note that with the instrument powered on, the terminals could be
dangerous to touching and cover opening actions or elements removal may allow
accessing dangerous parts. This instrument is factory-shipped at proper
operation condition.
- The device must have a professional installation and maintenance
- Any operation of the device, you must cut off the input signal and power;
MAINTENANCE
The 19D-23C single phase energy meter does not require any special
maintenance. No adjustment, maintenance or repairing action should be done
when the instrument is open and powered on, should those actions are
essential, high-qualified operators must perform them.
Before any adjustment, replacement, maintenance or repairing operation is
carried out, the instrument must be disconnected from any power supply source.
When any protection failure is suspected to exist, the instrument must be
immediately put out of service. The instrument’s design allows a quick
replacement in case of any failure.
TECHNICAL SERVICE
FAQ’s
-
– Once cabled and connected is seen to give a correct voltage and current reading, but shows negative values for active power (generation).
This is an error with the cabling for the current transformer secondary; the direction of the transformer current has to be respected as shown in the connection diagram. The current transformers have a two face primary; the current must pass from P1 to P2 giving the result in secondary (S1 and S2) of 5 amps.
The error stems from:
a). The current transformers have been incorrectly installed. As a result, it gives the direction of the current as passing from P2 to P1; to resolve this problem, the current transformer does not have to be dismantled and installed again, but the transformer secondary (S1 and S2) just has to be inverted.
b). The connection of the current secondary in the current transformers have been incorrectly connected; to resolve this problem just connect the S1 transformer secondary to the S1 on the meter and the S2 on the current transformer to the S2 on the meter. -
– Once cabled and connected, is seen to give an incoherent Power factor and Cos® reading (- 0.01 or similar).
This is again a current transformer and voltage phase connection error phase A, must correspond to the current transformer installed in phase A; phase B, must correspond to the current transformer installed in phase B; and phase C, must correspond to the current transformer installed in phase C.
This connection terminal is clearly shown on the area side of the device. -
– The measuring voltage and is displaying the secondary voltage (for example 110 volts).
Ensure that the voltage Transformer ratio has been correctly set. -
– Device does not correctly display the current reading. It shows values varying between 0 to 5 amps of current.
Ensure that the Current Transformer ratio has been correctly set.
Calculation formula of electrical parameter
Formula | Parameter |
---|---|
Voltage RMS value | |
Current RMS value | |
Total active power cycle average | |
Single-phase apparent power cycle average | |
Power factor | |
Reactive power |
(Pq is positive and the direction cannot be determined; P algorithm can be
used to shift the voltage component by 90°)
| Electric energy
Note: In above formula, N for sampling points in one AC wave.
For any inquiry about the instrument performance or any failure, contact to
Blue Jay’s technical service.
Blue Jay – After-sales service
E-mail: tech@cqbluejay.com
Tel: +0086-023-67628702
www.cgbluejay.com
Add: 1802,Building 2,No.88 Jianxin East Road,
Chongging,400020,China
Email: tech@cqbluejay.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>