BLUE JAY 19D-23C Single Phase Energy Meter User Manual

June 1, 2024
BLUE JAY

User ManualBLUE JAY 19D 23C Single Phase Energy
Meter 19D-23C
Single Phase Energy Meter(CTs)
Version:1.0

19D-23C Single Phase Energy Meter

Read me
When you use 19D-23C single phase energy meter, be sure to read this user manual carefully, and be able to fully understand the implications, the correct guidance of operations in accordance with user manual, which will help you make better use of 19D-23C single phase energy meter, and help to solve the various problems at the scene.

  1. Before the meter turning on the power supply, be sure that the power supply within the provisions of the instrument;
  2. When installation, the current input terminal must non-open, voltage input terminals must Non- short circuit;
  3. Communication terminal (RS232/RS485) is strictly prohibited to impose on high pressure;
  4. Be sure the instrument wiring consistent with the internal system settings;
  5. When communicating with the PC, instrument communication parameters must be consistent with the PC.
  • Please read this user manual carefully
  • Please save this document

SUMMARIZE

Single-phase rail-type electric energy meter is an intelligent device used in medium and low voltage systems (6-35KV and 0.4KV). It integrates data acquisition and control functions, adopts segment code LCD screen, and has single-phase AC power measurement and calculation. Energy accumulation, RS485 communication and other functions.
19D-23C single phase energy meter is a 3M width DIN rail energy meter, and use external CT to expand the current range max to 999A. With RS485-RTU and pulse output port, the LCD screen provides measurement circuit current and voltage reading. This 19D-23C single phase energy meter suits scenarios such as residential, public facilities, and industrial use.

FEATURES

  • Maximum 999A, 1A/5A CT connection
  • Provide energy import and export measurement (IMP & EXP)
  • With one port energy pulse output
  • RS485 Modbus communication (optional)
  • Standard 35mm din rail mounting, width 3M size
  • Detect voltage, current, active/reactive energy, power, frequency, Max demand, etc.

APPLICATIONS

  • All power parameter measurement;
  • Energy measurement and electrical fire monitor and control;
  • Transformers, generators, capacitors and electric motors distributed detection;
  • Medium and low pressure systems;
  • SCADA, EMS, DCS integrators.

TECHNICAL PARAMETERS

Measurement & Display

Voltage Rated 230V RMS value, Accuracy 0.2%,
Current Rated 5A, Optional 1A, CT Connection, RMS value.

Accuracy 0.2%;
Overload| 1.2 times rated continuous; 1 seconds for 10 times the rated
Frequency| 50/60Hz, Accuracy +0.01Hz
Display| LCD with white backlit
Maximum display value| 9999999MkWh
AUX Power| 90-240V AC, <2W/10VA

Output

Digital port RS-485 MODBUS-RTU
Pulse port 1600imp/kWh

Other parameters

Working environment| -25~55°C Altitude ≤2500m, 0~95%RH, non- condensing, non- corrosive gas
---|---
Storage environment| -40~70C
Voltage tolerance| 2KV 1min
Shock voltage| 6KV-1.2uS waveform
Insulation| Input, output, power supply to Shell >5MQ

INSTALLATION AND START-UP

The manual you hold in your hand contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep it in safety conditions. The instrument must not be powered on and used until its definitive assembly is on the cabinet’s door.

If the instrument is not used as manufacturer’s specifications, the protection of the instrument will be damaged.
When any protection failure is suspected to exist (for example, it presents external visible damages), the instrument must be immediately powered off. In this case contact a qualified service representative.
3.1.- Installation
Mounting
Instrument is to be mounted on 35mm Din-rail. Keep all connections into the cabinet. Please note that with the instrument powered on, the terminals could be dangerous to touch and cover opening actions or elements removal may allow accessing dangerous parts. Therefore, the instrument must not be used until this is completely installed. BLUE JAY 19D 23C Single Phase Energy Meter -
InstallationDimension: Unit: mm BLUE JAY
19D 23C Single Phase Energy Meter - Installation 1Notes:
Input signal: 19D-23C using a separate acquisition calculate for each measurement channel, to ensure consistent in use, for different load forms, it’s a variety of connection mode. Access wire shall be met 3 square mm.
A. Voltage input
Input voltage should not exceed the rated input voltage products 450V.
Otherwise, you should use external VT. Suggest 1A fuse be installed in the voltage input side.
B. Current Input
Standard input current is 5A or 1A, if greater than 5A/1A should use external CT.
When the CT is connected with other meters, make sure wiring methods be used in series.
Warning: Forbid to install a CT on the live feeder wire with open secondary leads. This can be extremely dangerous!
Before remove the current input connection, must be sure to disconnect the primary circuit or shorted secondary circuit of CT.
C. Sequence of wire
Warning: Please make sure that the input voltage and current corresponding to the same phase, sequence, and the same direction; Otherwise, the Values and symbols will be wrong!
(Power and Energy)
Always observe the physical orientation of CT (P1 – P2) when installing on the feeder wire.
Always pay attention to wiring polarity and phasing when terminating the CT leads to the 19D-23C.
S1 connect to Ix*, 82 connect to Ix.
The input network configuration of instrument depends on the CT number of the system:
in the condition of 2 CT, select the three-phase, three-lines two components;
in the condition of 3 CT, select the three-phase, four-lines three component mode.
Instrument connection mode, set of the instrument (programming input network NET) should be the same load wiring as measured wiring. Otherwise, the measurement instrument will lead to incorrect voltage or power.
D. Auxiliary power
19D-23C with universal (AC / DC) power input, if not for a special statement, we provide the 90- 240AC/DC power interface for standard products, please ensure that the auxiliary power can match with meter to prevent unexpected damage.
A. Suggest install 1A fuse in the fire line side.
B. For the areas with poor power quality, suggest install lightning surge suppressor and rapid burst suppressor to prevent lightning strikes.

3.2. – Connection Terminal
Upper connection terminal

16 15 14 13 12 11 10 9
UN UN I I*

16. Neutral Voltage input
13. Voltage A-phase input
Lower connection terminal

8 7 6 5 4 3 2 1
RP- RP+ 485G 485B 485A N L

Note:
The terminal pin definition may change depends on customer order; please refer to the label on the meter!

3.3. — Typical WiringBLUE JAY 19D 23C Single Phase Energy Meter -
Typical Note:
This connection drawing is for reference only; the actual connecting terminal please refer to the label on the rear part.
WARNINGS!
If power = -0.01 is shown for any of the phases and voltage and current are not zero for this phase, check out following points:
– Assure that A, B and C phases coincide in voltage and current.
– Correct polarity? Reverse the current transformer placed at this phase.

SCREEN DISPLAY

4.1.- Screen description:
Panel & Screen introduction

  1. – 7 digital show energy value
  2. – Symbol for SUM energy record value
  3. – Symbol for multi-tariff function
  4. – Imp for energy consumption, Export for energy generate
  5. – Symbol for Maximum demand
  6. – Symbol for average value
  7. – PF=power factory; Hz=Frequency
  8. – Pulse output channal 1 and channel 2
  9. -symbol for communication active
  10. – symbol for timer
  11. – symbol for screen locked

4.2.- Indicator light description:

Name Function definition(when lighting )
Active power reverse
Active energy pulse

4.3.- Screen pages’ description:

Screen No. Screen interface Description
1 Voltage: 228.8V
2 Current: 5.000A
3 Active power: 4800W
4 Reactive power: 1200Var
5 Apparent power: 3208VA
6 Power factor: 1.000
7 Frequency of grid: 49.99Hz
8 Active power: 50.00kwh
9 Reactive power: 20.00kwh
10 Active reactive energy: 5.00kvarh
11 Negative reactive energy: 5.00kvarh

OPERATION MENU DESCRIPTION

5.1 Button description

| Short press is the up button, turning the page to display the measurement data, displaying voltage, current, power, electric energy and other measurement data.
---|---
| Short press is the down key, the function is the same as the up key, but the page turning direction is opposite;
Long press is the menu key to enter the programming menu, and it isalso a function key to exit the menu step by step.
| Short press is the confirmation key to confirm and save the entered information or displayed settings.

5.2 Main menu
In the case of measuring data, press the “menu” button, and the prompt of “PASS” (that is, “password”) will appear, press the “OK” button to enter the user-level password (default is 0001), press the button to enter the programming in this state, the instrument provides three types of input setting menu items: system factory commissioning (SYS), input (-IN-), and communication (bus).
Adopt LCD display layered menu structure management. BLUE JAY 19D 23C Single
Phase Energy Meter - Main manu5.2.1 Description of menu characters:

| (Password) User password
---|---
| (Error) Wrong input information
| (Input) User Display Data Settings Menu
| (Bus) Communication settings menu
| (System) System settings menu (for factory debugging, not open yet)
| (Code) Enter password
| (Data) Communication parameter setting
| (Address) Local communication address setting
| (Baud) Communication baud rate
| (0.8.1) Indicates 8 data bits, 1 stop bit, odd parity
| (e.8.1) Indicates 8 data bits, 1 stop bit, even parity
| (n.8.1) Indicates 8 data bits, 1 stop bit, no parity bit
| (U.scl) Select rated input voltage
| (l.scl) Select rated input current
| (R.ct) Set the current multiplier
| (R.pt) Set voltage ratio
| (System) System settings menu (for factory debugging, not open yet)
| Modify password value

PULSE OUTPUT (OPTIONAL)

19D-23C provides 1* pulse output for the active energy.
The host / PLC / DI module can cumulative the data of both the active and reactive power energy sent by the pulse from opt coupler relay.

  1. Electrical specification: voltage VCC < 48V, 1z < 50mA.
  2. Pulse: 5000 imp / kWh, pulse up to 80ms.
    This means: When the device detects 1 kWh, the port will generate 5000 pulse

Note:
1 kWh energy is for secondary side energy data, if there have PT and CT accessed; primary side energy data is “1 kWh xPT ratiox CT ratio”.

Voltage (V) Current (A) Pulse constant (imp / kWh)
380 or 220 5
1 5000

20000
100| 5
1| 20000
80000

Example: In measure time “T”, the received total pulse is “N”.
Primary side input of voltage is 10Kv
Primary side input of current is 400A.
Secondary side measurement range is 100V and 5A.
In the time “T”, energy accumulated is: N / 20000 x 100 x 80

COMMUNICATION INTERFACE

7.1.- Connection for RS485 BUS
The composition of the RS-485 cabling must be carried out with a meshed screen cable (minimum 3 wire), diameter of not less than 0.5mm?, with a maximum distance of 1,200 m between the 19D-23C… and the master unit. This Bus may connect a maximum of 32pcs BLUE JAY 19D 23C Single Phase Energy Meter -
Connection

Notes:

  • For communication with the master unit, user can choose RS-485 to RS-232 converter or RS485 to USB adapter to use.
  • For expand the number of devices in the communication network, a signal repeater can be used.
  • RS485 PIN number is 58,59,60
  • Due to product modifications or special requirements, the interface pin place may be change. For details, please refer to product label on the rear side

7.2.- MODBUS © Protocol
Modbus RTU Frame Format:

Address code 1BYTE Slave device address 1-247
Function code 1BYTE Indicates the function codes like read coils / inputs
Data code 4BYTE Starting address, high byte

Starting address, low byte
Number of registers, high byte
Number of registers, low byte
Error Check code| 2BYTE| Cyclical Redundancy Check (CRC)

MODBUS FUNCTIONS:

Code Meaning Description
FUNCTION 01 Read Coil Status Only valid when equipped DO port
FUNCTION 02 Read Input Status Only valid when equipped DI port
FUNCTION 03 Reading of n Words This function permits to read all the

electrical parameters
FUNCTION 05| Force Single coil| When DO in remote control mode can work
FUNCTION 06| Preset Single register| Disable in default
I need valid this code, please contact Blue Jay Sales Team before your order!

Note: Float data follow IEEE754, float low bit first, high bit next. (CD AB)
7.3.- Register Map
7.3.1.- Basic power data—Primary Side

Register Data Byte mode Instruction
Ox00 U float 2
OxOc I float 2
0x12 P float 2
Ox1a Q float 2
0x22 S float 2
Ox2a PF float 2
0x32 FR float 2
0x34 Ep+ float 2
0x36 Ep- float 2
0x38 Eq+ float 2
Ox3a Eq- float 2

7.3.2.- Basic power data—Secondary Side

Register Data Byte mode Instruction
Ox100 Ua int 1

Current, Unit:0.001 A
0x106| la| int| 1
0x109| Pa| int| 1| Active power, Unit: W
Ox10d| Qa| int| 1| Reactive power, Unit: Var
Ox111| Sa| int| 1| Apparent power, Unit: Va
Ox115| PFa| int| 1| Power factor, 0-1.000
0x119| FR| int| 1| Frequency, unit:0.01hz
Ox11a| Ep+| int| 2| Positive active energy, Unit: Wh
Ox11c| Ep-| int| 2| Negative active energy, Unit: Wh
Ox11e| Eq+| int| 2| Inductive reactive power, Unit: Varh
Ox120| Eq-| int| 2| Capacitive reactive power

Notes:

  1. The data can be read out depends on your multi-function meter model, please refer to the corresponding product manual before build your software.
  2. Some software has different definitions of the start bit of register address, there will be offset, please add 1 for the right address. To get more info, please contact technical support.

7.4.- Example
Host inquiry slave device

Addr.| Func.| Data Address high| Data Address low| Data Number high| Data number low| CRC16 low| CRC16 high
---|---|---|---|---|---|---|---
OCH| 03H| OOH| OOH| OOH| 06H| C4H| D5H

PC user ask upload UA, UB, UC, IA, IB, IC
Slave device response

Addr.| Func.| Byte count| Data1 high| Data1 low| Data2 high| Data2 low| Data3 high| Data3 low
---|---|---|---|---|---|---|---|---
OCH| 03H| OCH| 03H| E8H| 03H| E9H| 03H| E8H
Data4 high| Data4 low| Data5 high| Data5 low| Data6 high| Data6 low| CRC16 low| CRC16 high|
13H| 84H| 13H| 88H| 13H| 8AH| A6H| D6H|

Show the data:
UA=3E8H (100.0)
UB=3E9H (100.1)
UC=3E7H (99.9)
IA=1384H (4.996)
1B=1388H (5.000)
IC=138AH (5.002)
Notes:

  1. Blue Jay disable the 06 function in default setting, if Activated the write command, please check the host device program to avoid the meaningless write operation, that may reduce the reduce the register working life.
  2. When the write is unsuccessful, no return data from the slave device. In this addition, please re- send write inquiry again.

SAFETY CONSIDERATIONS

Al installation specification described at the previous chapters named:
INSTALLATION AND STARTUP, INSTALLATION MODES and SPECIFICATIONS.
Please note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. This instrument is factory-shipped at proper operation condition.

  • The device must have a professional installation and maintenance
  • Any operation of the device, you must cut off the input signal and power;

MAINTENANCE

The 19D-23C single phase energy meter does not require any special maintenance. No adjustment, maintenance or repairing action should be done when the instrument is open and powered on, should those actions are essential, high-qualified operators must perform them.
Before any adjustment, replacement, maintenance or repairing operation is carried out, the instrument must be disconnected from any power supply source.
When any protection failure is suspected to exist, the instrument must be immediately put out of service. The instrument’s design allows a quick replacement in case of any failure.

TECHNICAL SERVICE

FAQ’s

  1. – Once cabled and connected is seen to give a correct voltage and current reading, but shows negative values for active power (generation).
    This is an error with the cabling for the current transformer secondary; the direction of the transformer current has to be respected as shown in the connection diagram. The current transformers have a two face primary; the current must pass from P1 to P2 giving the result in secondary (S1 and S2) of 5 amps.
    The error stems from:
    a). The current transformers have been incorrectly installed. As a result, it gives the direction of the current as passing from P2 to P1; to resolve this problem, the current transformer does not have to be dismantled and installed again, but the transformer secondary (S1 and S2) just has to be inverted.
    b). The connection of the current secondary in the current transformers have been incorrectly connected; to resolve this problem just connect the S1 transformer secondary to the S1 on the meter and the S2 on the current transformer to the S2 on the meter.

  2. – Once cabled and connected, is seen to give an incoherent Power factor and Cos® reading (- 0.01 or similar).
    This is again a current transformer and voltage phase connection error phase A, must correspond to the current transformer installed in phase A; phase B, must correspond to the current transformer installed in phase B; and phase C, must correspond to the current transformer installed in phase C.
    This connection terminal is clearly shown on the area side of the device.

  3. – The measuring voltage and is displaying the secondary voltage (for example 110 volts).
    Ensure that the voltage Transformer ratio has been correctly set.

  4. – Device does not correctly display the current reading. It shows values varying between 0 to 5 amps of current.
    Ensure that the Current Transformer ratio has been correctly set.

Calculation formula of electrical parameter

Formula Parameter
Voltage RMS value
Current RMS value
Total active power cycle average
Single-phase apparent power cycle average
Power factor
Reactive power

(Pq is positive and the direction cannot be determined; P algorithm can be used to shift the voltage component by 90°)
| Electric energy

Note: In above formula, N for sampling points in one AC wave.
For any inquiry about the instrument performance or any failure, contact to Blue Jay’s technical service.
Blue Jay – After-sales service
E-mail: [email protected]

Tel: +0086-023-67628702
www.cgbluejay.com
Add: 1802,Building 2,No.88 Jianxin East Road,
Chongging,400020,China
Email: [email protected]

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

BLUE JAY User Manuals

Related Manuals