BLUE JAY BJ-MCM2401 Multi Channel Circuit Metering System User Guide

May 15, 2024
BLUE JAY

BLUE JAY BJ-MCM2401 Multi Channel Circuit Metering System

BLUE-JAY-BJ-MCM2401-Multi-Channel-Circuit-Metering-System-
PRODUCT

Product Information

Specifications

  • Product Name: Multi-channel Circuit Metering System BJ-MCM2401
  • Communication Protocol: MODBUS
  • Version: 1.2
  • Max Distance for RS-485 Bus: 1,200m
  • Maximum Connected Devices: 32 BJ194…
  • RS485 PIN Numbers: 58, 59, 60

Product Usage Instructions

Connection for the RS485 BUS
The RS-485 cabling must be carried out with a meshed screen cable (minimum 3 wire), with a diameter of not less than 0.5mm2. Ensure the maximum distance between the BJ194… and the master unit does not exceed 1,200m. Connect a maximum of 32 BJ194… devices to the bus.

Note

  1. For communication with the master unit, customers can choose the RS-232 to RS-485 converter.
  2. Full range of BJ-… meter RS485 PIN numbers are 58, 59, 60.
  3. Interface pin placement may vary due to product modifications or custom requirements. Refer to the product label on the rear board for specific details.

FAQ

  • Q: What is the maximum distance for the RS-485 Bus?
    A: The maximum distance for the RS-485 Bus is 1,200 meters.

  • Q: How many devices can be connected to the RS-485 Bus?
    A: A maximum of 32 BJ194… devices can be connected to the RS-485 Bus.

  • Q: What are the RS485 PIN numbers for the BJ-… meter?
    A: The RS485 PIN numbers for the BJ-… meter are 58, 59, and 60.

  • Q: How can I communicate with the master unit?
    A: Customers can choose the RS-232 to RS-485 converter for communication with the master unit.

Multi-channel Circuit Metering System

BJ-MCM2401
MODBUS register map
Version :1.2

COMMUNICATION PROTOCOL

Connection for the RS485 BUS

The composition of the RS-485 cabling must be carried out with a meshed screen cable (minimum 3 wire), diameter of not less than 0.5mm2, with a maximum distance of 1,200 m between the BJ194… and the master unit. This Bus may connect a maximum of 32 BJ194…

BLUE-JAY-BJ-MCM2401-Multi-Channel-Circuit-Metering-
System-

Note

  1. For communication with the master unit, customers can choose the RS-232 to RS-485 converter to use
  2. Full range of BJ-… meter RS485 PIN number is 58,59,60
  3. Due to product modifications or custom requirements, the interface pin place may be changed. For details, please refer to product label on the rear board

MODBUS © protocol

Modbus RTU Frame Format

  • Address code 1 BYTE Slave device address 1-247
  • Function code 1 BYTE Indicates the function codes like read coils I inputs
  • Data code 4BYTE
    • Starting address, high byte
    • Starting address, low byte
    • Number of registers, high byte
    • Number of registers, low byte
  • Error Check code 2 BYTE Cyclical Redundancy Check (CRC)

MODBUS FUNCTIONS

Code: Meaning: Description:

  • FUNCTION 03 Reading of n Words This function permits to read all the electrical parameters of the BJ 194 . . . series.
  • FUNCTION 06 Preset single Registers Write value in to the relevant register

Register Map

Basic Power Data-Primary Side (Read only)

Address Data Byte mode Instruction
0 CH1- u float 2
2 CH1- I float 2
4 CH1 P float 2
6 CH1_Q float 2
8 CH1 S float 2
10 CH1_PF float 2

0~1.000

12| CH1 FR| float| 2| Channel_1 Frequency,

Unit:0.01Hz

14| CH1 _ EpZ+| float| 2| Channel_1 positive active energy,

Unit: kWh

16| CH1_EpZ-| float| 2| Channel_1 negative active energy,

Unit: kVarh

18| CH1_EqZ+| float| 2| Channel1 positive reactive energy, Unit: kVarh
20| CH1 **
EqZ | float| 2| Channel_ 1** negative reactive energy,

Unit: kWh

22-42| CH2 parameter| float| 2| ** Structure refer to Channel 1
44-64| CH3 parameter| float| 2
. . . . . .| I| I| I
242-262**| CH12 parameter| float| 2

Meter status data, Read & Write (Disabled)

Address Data Byte mode Instruction Status
1200 Digital output int 1 0: without act

1 : active for trig

| R
1202| Alarm| int| 1| 0: without alarm         1: Alarm trigged Bit 0~4 show Alarm 1~5 status| R




1203

| ****



DO          working mode

| ****



int

| ****




1

| 0: Remote control

1 : Related to Alarm_1 2: Related to Alarm_2 3: Related to Alarm 3

4: Related to Alarm 4 5: Related to Alarm_5 6: trig to closed

7: triq to opened

| ****



R/W


1204

| ****

DO time delay

| ****

int

| ****

1

| In alarm mode: 0.0-999.9sec In remote control mode:

0 for Level output:

other value for pulse width 0.1-999.9sec

| ****

R/W


1240

| ****

Wiring mode

| ****

int

| ****

1

| 0: 3P4W

1: 3P3W-2CT

2: 3P3W-3CT

| ****

R

1241| Voltage range| int| 1| Unit: V| R
1242| Current range| int| 1| Unit: mA| R
1243| PT ratio| int| 1| Range: 1-9999| R
1244| CT of CH1| int| 1| Range: 1-9999| R
1245| CT of CH2| int| 1| Range: 1-9999| R
1246| CT of CH3| int| 1| Ranqe: 1-9999| R
1247| CT of CH4| int| 1| Range: 1-9999| R

Voltage harmonic (max 21th), Read Only

Address Data Byte mode Instruction
1300 THDU int 1
1301 TOHDU int 1
1302 TEHDU int 1
I I I
1310-1329 HU int 1

Current harmonic (max 21th), Read Only

Address Data Byte mode Instruction
1400 THDl1 int 1
1401 I I I
1402 I I I
1403 TOHDl1 int 1

0.1%
1404| I| I| I| Reserved
1405| I| I| I| Reserved
1406| TEHDl1| int| 1| Channel 1 Current even harmonic total distortion, unit 0.1%
1407| I| I| I| Reserved
1408| I| I| I| Reserved
1410-1429| Hl1| int| 20| Channel 1 Current harmonic ratio for 2 to 21th, unit 0.1%
1430-1459| CH2 Harmonic| int| 20| **** Structure refer to Channel 1
1460-1489| CH3 Harmonic| int| 20
….. .| I| II|
1730-1759| CH12 Harmonic| int| 20

Special operation (Disabled)

Address Data Byte mode Instruction Status
3000 Reset               energy counter int          I    1 Send code
0x0A0A (DEC 2570) to clear all the enerov counter w

Tel: +0086-023-67628702
www.cqbluejay.com
Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China
Email: tech@cqbluejay.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals