BLUE JAY GYID-10D36CAx-x Insulation Monitor User Manual
- June 10, 2024
- BLUE JAY
Table of Contents
BLUE JAY GYID-10D36CAx-x Insulation Monitor
Read me
When you use GYID series, be sure to read this user manual carefully, and be able to fully understand the implications, the correct guidance of operations in accordance with user manual, which will help you make better use of GYID series, and help to solve the various problems at the scene.
- Before turning on the power supply, be sure that the power supply within the provisions of the instrument;
- When installation, the current input terminal must non-open, voltage input terminals must Nonshort circuit;
- Communication terminal (RS485) is strictly prohibited to impose on high pressure;
- Be sure the instrument wiring consistent with the internal system settings;
- When communicating with the PC, instrument communication parameters must be consistent with the PC.
- Please read this user manual carefully
- Please save this document
SUMMARIZE
GYID series insulation monitor is used to monitor the insulation resistance between high voltage components (0-1000 Vdc.) and automobile chassis (earth) of power battery pack (pure electric or hybrid) power supply system in real time.
The measuring technology used in this product can monitor the insulation faults of DC side, AC side and motor side; can simultaneously monitor the asymmetric insulation faults of positive and negative poles and symmetrical insulation faults; can monitor the internal insulation faults of battery packs and locate the fault points; can monitor under the condition of short circuit of high voltage DC side; in the case of high intensity interference, such as acceleration, deceleration, energy recovery, the insulation resistance can be reliably monitored. fault information (insulation fault, overvoltage, self- error, etc.) is output through CAN bus interface.
FEATURES
- Monitor the positive and negative insulation resistance separately
- Monitor the total insulation resistance
- report the location of the battery insulation fault
- Automatically adapt to existing system Y capacitor CY(CY ≤4uF)
- High internal resistance up to 10MOeInjected signal amplitude ±15V
- Fault response time ≤5s
- High and low voltage side isolation voltage 3500 VD.C./2500 Vac.(rms)
- With CAN Bootloader, upgrade program by CAN
APPLICATIONS
- Monitor the insulation state
- DC floating system (IT system).
- Measuring battery pack DC voltage
- Continuous measurement of insulation resistance of 0~50MΩ
- Using the CAN bus interface
TECHNICAL PARAMETERS
Power supply
9~36VDC
Input power
≤ 2W
Standard
IEC 61851-23 (2014-03):2014-11
DC voltage range
0V~1000V
DC voltage at pile side accuracy
≤2V+0.3%
Vehicle side voltage measurement range
0V~1000V
Insulation resistance measurement range
0~50MΩ
Insulation monitoring accuracy
≤3KΩ+5%
Bus voltage measurement accuracy
1 %
Insulation resistance measurement accuracy
0~100 KΩ,CY≤ 2μF,Bus voltage stability: ±12 KΩ
100 kΩ~1 MΩ,CY≤ 2μF,Bus voltage stability:±10 %
1 MΩ~50 MΩ,CY =0μF,Bus voltage stability: ±10 %
Insulation resistance measurement response time
RISO≥ 500 kΩ, CY =0μF,Bus voltage stability: 4 s
RISO≥ 500 kΩ, CY =0μF,Bus voltage stability: 5 s
RISO=1 MΩ,CY =1μF,Bus voltage stability: 8 s
RISO=1 MΩ,CY =1μF,Bus voltage stability: 12 s
DC equivalent internal resistance
Power on: 10.2 MΩ
Amplitude of injection pulse signal
±15 V
High to low voltage withstanding voltage
3 500 Vd.c. 2 500 Va.c.(rms)
Off-line pressure test
<2mA
Environment
Storage: – 40°C ~+85°C
Work: – 40°C ~85°C
Humidity:85%
INSTALLATION
Dimension (Unit: mm)
Connection Terminal
(a) Class B Voltage (High Voltage Side) Connector
(b) Class A Voltage (Low Voltage Side) Connector
Voltage grade | Number/Color | Name | Wiring instructions |
---|---|---|---|
Class B voltage (High voltage side) | V red | DC+ | Connect to Battery Positive |
BUS+
black| DC-| Connect to Battery Negative BUS-
Class A voltage (low voltage side)| ⑥ orange| H| Connect to CAN Bus H Port
⑤ green| L| Connect to CAN Bus L Port
④ brown| E| Connect the chassis of the car (earth)
③ blue| A| Alarm output terminal (suspended if not required)
② black| V-| Connect to auxiliary power supply negative
① red| V+| Connect to auxiliary power supply positive
WIRING METHOD
Typical application
GYID series insulation monitor can be used in electric vehicle and hybrid electric vehicle, backup battery system, power grid energy storage and other occasions.
CAN communication circuit
The CAN communication circuit of GYID series insulation monitor is connected with a terminal resistance of 120Ω.
Wiring indication for actual vehicle application
ALARM circuit
The ALARM function of GYID series insulation monitor consists of optocoupler output. The negative end of the output of the optocoupler device in the insulation monitor has been connected with the negative end of the auxiliary power supply in the insulation monitor. Therefore, when the ALARM function is selected, users need to connect a resistor R and alarm indicator LED in series between the “A” port and the “V+” port to form a circuit, and ensure that the maximum current of the circuit does not exceed 100 mA.
COMMUNICATION PROTOCOL
Communication parameters
Data | Parameter | Definition |
---|---|---|
Receiving ID | 0x1819A1A5 (Extended frame) |
- Turn on insulation resistance monitoring Function command: 00 01 02 03 04 05 06 07
- Turn off insulation resistance monitoring Function command: 07 06 05 04 03 02 01 00
Default: 0x1819A1A5,adjustable
Receiving cycle| 10 ms|
Send ID| 0x1819A1A4(Extended frame)| Default:0x1819A1A4,adjustable
Sending cycle| 1s| Default: 1s,adjustable
Baud rate| 250 kbps| Default: 250 kbps, adjustable
Data definition
Byte | Bit | Definition |
---|---|---|
Byte 0 | 7 | 1:Insulation resistance monitoring function already |
started. 0:Insulation resistance monitoring function already stopped.
6| 1:Output RISO+ and RISO– 0:Output RISO
5| 10:RISO+ > RISO–
01:RISO+ < RISO–
00:RISO+ = RISO–
4
3| Reserved (Default 0)
2| 1:Battery Overvoltage Alarm (Default: ∞V , adjustable) 0:No Battery
Overvoltage Alarm
1| 1:Level-2 Insulation Alarm (Default: 1 000Ω/V , adjustable) 0:No
Level-2 Insulation Alarm
0| 1:Level-1 Insulation Alarm (Default: 500Ω/V , adjustable) ① 0:No
Level-1 Insulation Alarm
Byte| Bit| Definition
---|---|---
Byte 1~7| GYID-10D36CAx-x(output RISO+ and RISO-)| GYID-10M36CAx-x
(output RISO)
Byte 1| RISO+ High byte /Unit kΩ| RISO High byte/Unit kΩ
Byte 2| RISO+ Low byte| RISO Low byte
Byte 3| Battery Voltage VDC High byte ② /Unit 0.1V
Byte 4| Battery Voltage VDC Low byte
Byte 5| RISO– High byte/Unit kΩ| Grounding position V1 High byte
Byte 6| RISO- Low byte| Grounding position V1 Low byte
Byte 7| Counting / 00~FF(HEX) cycle, plus 1 for each transmission cycle
Notes:
① To type GYID-10D36CAx-x, the insulation alarm value equals min [RISO+,
RISO-]. To type GYID10M36CAx-x, it equals RISO.
② The data converted from two bytes of battery voltage VDC to decimal contains
one decimal point. Example: The two-byte data of battery voltage VDC is 04D2
(HEX), and the data converted into decimal system is 1234, then the battery
voltage VDC = 123.4 V.
MODEL SELECTION SHEET
Notes (must be read when selecting model)
Note 1: Differences between GYID-10D36CAx-x and GYID-10M36CAx-x
The output of GYID-10D36CAx-x type is defined as RISO + and RISO − respectively.
GYID-10M36CAx-x output “parallel value of positive and negative pole-to-ground insulation resistance”, defined here as RISO.
GYID-10D36CAx-x When Battery Voltage VDC (Voltage Value Between DC+, DC-of Insulation Monitor Terminal):
① When the battery voltage VDC > 20 Vdc., the output positive and
negative poles of the insulation monitor is RISO+ and RISO −, respectively.
② When the battery voltage VDC is greater than 0 Vdc. and VDC is less
than 20 Vdc., the output positive and negative poles of the insulation monitor
are equal to the ground insulation resistance respectively, and both are equal
to the parallel value of the two. Namely RISO+ = RISO- =RISO.
GYID-10M36CAx-x type insulation monitors normally outputs RISO of positive and negative pole-to-ground insulation resistance when the battery voltage VDC ranges from 0 to 1 000 Vdc.
Note 2: Projects that can be modified or adjusted according to user needs
- CAN Communication Baud Rate: Default 250 kbps.
- Send ID: default 0x1819A1A4 (Extended frame).
- CAN communication transmission cycle: Default 1s (Adjustable, but not recommended).
- “Level-1 Insulation Alarm “Value: Default 500 Ω/V ① (Unit: Ω/V or kΩ, adjustable).
- “Level-2 Insulation Alarm “Value: Default 1000 Ω/V (Unit: Ω/V or kΩ, adjustable).
- “Battery Overvoltage Alarm” Value: Default ∞ V (Adjustable)
Note:
① According to GB/T 18384.1 “Safety Requirements for Electric Vehicles – Part 1: On-board Rechargeable Energy Storage System (REESS)”, the insulation resistance of battery packs containing AC circuits should not be less than 500Ω/V.
SAFETY CONSIDERATIONS
All installation specification described at the previous chapters named:
INSTALLATION AND STARTUP, INSTALLATION MODES and SPECIFICATIONS.
Please note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. This instrument is factory-shipped at proper operation condition.
- The device must have a professional installation and maintenance
- Any operation of the device, you must cut off the input signal and power;
MAINTENANCE
The GYID series does not require any special maintenance. No adjustment, maintenance or repairing action should be done when the instrument is open and powered on, should those actions are essential, high-qualified operators must perform them.
Before any adjustment, replacement, maintenance or repairing operation is carried out, the instrument must be disconnected from any power supply source.
When any protection failure is suspected to exist, the instrument must be immediately put out of service. The instrument’s design allows a quick replacement in case of any failure.
FAQS
Question 1: The insulation monitoring resistance is infinite after the simulation of insulation resistance
Check whether the ground cable is connected reliably at GND port.
Question 2: The insulation monitoring resistance is much smaller than actual value
The DC ground capacitance may be too large. Check the DC ground capacitance
CUSTOMER SUPPORT
For any inquiry about the instrument performance or any failure,
contact to Blue Jay’s technical service.
Blue Jay – After-sales service
E-mail: tech@cqbluejay.com
Tel: +0086-023-67628702
Email:tech@cqbluejay.com
www.cqbluejay.com
Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>