BLUE JAY BJ192P-3 Three Phase Active Power Meter User Manual

June 10, 2024
BLUE JAY

BJ192P-3
Three-phase Active Power Meter
(Unbalance load)
User Manual
Version:1.4

BJ192P-3 Three Phase Active Power Meter

Read me
When you use BJ192-X series Digital Meter, be sure to carefully read this user manual, and be able to fully understand the implications, the correct guidance of operations in accordance with user manual, which will help you make better use BJ192 series
Multifunction Power Meter, and help to solve the various problems at the scene.

  1. Before the meter turning on the power supply, be sure that the power supply within the  provisions of the instrument;
  2. When installation, the current input terminal must non-open, voltage input terminals must  Non-short circuit;
  3. Communication terminal (RS232 or RS485) is strictly prohibited to impose high pressure;
  4. Be sure the instrument wiring consistent with the internal system settings;
  5. When communicating with the PC, instrument communication parameters must be consistent with the PC.
  • Please read carefully before using this user manual
  •  Please save this document

SUMMARIZE

BJ192-X series Digital Meter is used for power quality monitoring, factory automation and building automation.
These series can measure the power parameters in power grid:

Current, Reactive power,
Voltage, Apparent power,
Frequency, Energy,
Active power, Power factor,

It can replace many of a traditional analog measurement instruments, improve system accuracy and reliability.

SPECIFICATIONS

  1. Reference standard:
    Basic electricity: GB/T13850-1998 (IEC688-1992)
    Active power : GB/T17215-2002 (IEC61036:2000)
    Reactive power : GB/T17882-1999 (IEC61268:1995)

  2. Accuracy standards****
    Parameter| Accuracy| A phase| B phase| C phase
    ---|---|---|---|---
    Active Power| 0.5%fs| W1| W2| W3

  3. Input
    Voltage: Rated 100/400V
    Current: Rated 5A (optional 1A)
    Frequency: 45-65Hz

  4. Load
    Voltage: <0.5VA / phase (rated 220V)
    Current: <0.5VA / phase (rated 5A)

  5. Overload
    Current: 2 times rated continuous; 10 seconds for 10 times the rated  Voltage: 2 times the rated continuous; 10 seconds for 600V

  6. Dielectric strength
    IEC 688 / IEC 255-3 (1989)
    2kV AC RMS 1 minute, between input / output / case / power supply

  7. EMC Test**
    standard Test voltage** Electrostatic discharge immunity test:IEC-61000-4-2 level 48KVElectrical fast transient burst immunity testIEC61000-4-4 level 3Input 1kV; Power supply 2kVSurge (Shock) immunity testIEC61000-4-5 level 4common mode test voltage 4kV

  8. Work environment
    **** Temperature: -20℃ ~ +60℃ (-4℉ ~ 140℉)
    Humidity: RH 20%~95%(No condensation)

  9. Protection
    Panel: IP40

  10. Storage Conditions
    Temperature: -25℃~+70℃(-13℉ ~ 158℉)
    Humidity: RH 20%~95%

  11. Power Supply
    AC /DC 80-270V
    Maximum power consumption 3W

  12. Dimensions
    L × W × H =96x96x123mm (3.78×3.78×4.85 inch)

  13. Installation hole size
    L × W =(91+0.8)mm×(91+0.8)mm [(3.58+0.032)inchx(3.58+0.032)inch]

INSTALLATION AND START-UP

The manual you hold in your hands contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions. The instrument must not be powered and used until its definitive assembly on the cabinet’s door.
Whether the instrument is not used as manufacturer’s specifications, the protection of the instrument can be damaged.
When any protection failure is suspected to exist (for example, it presents external visible damages),the instrument must be immediately powered off. In this case contact a qualified  service representative.
3.1.- Installation
Mounting
Instrument is to be mounted on panel (cut-out 91+0.8 x 91+0.8 mm). All connections keepinside the cabinet.
Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts.
Therefore, the instrument must not be used until this is completely installed.

BLUE JAY BJ192P-3 Three Phase Active Power Meter -
Mounting

Notes:
Auxiliary power:
BJ192X Series Power Meter with universal (AC / DC) power input, if not for a special statement, we provide the 220VAC/DC or 110VAC/DC power interface for standard products Instruments limit work power supply : AC / DC :80-270V, please ensure that the auxiliary power can match for BJ192-X series meter to prevent damage to the product.
A. Suggest install 1A fuse in the fire line side.
B. For the areas with poor power quality, suggest install lightning surge suppressor and rapid burst suppressor to prevent lightning strikes
3.2.- Connection terminal and drawing for BJ192P (see label on the rear part)
Terminal description

1. Supply voltage input: 0 V
2.
Supply voltage input:220 Va.c4. Current A-phase – S1 input
5. Current A-phase – S2 input
6. Current B-phase – S1 input
7. Current B-phase – S2 input
8. Current C-phase – S1 input
9. Current C-phase – S2 input
11. Voltage A-phase input
12. Voltage B-phase input
13. Voltage C-phase input
14. Neutral Voltage input
58. RS-485 ( + )
59. RS-485 ( – )
60. RS-485 ( GND )

BLUE JAY BJ192P-3 Three Phase Active Power Meter - Terminal
description Three-phase network.- 3 wires (low voltage):
BLUE JAY BJ192P-3 Three Phase Active Power Meter - Terminal
description1 IMPORTANT REMARK!
If power = -0.01 is shown for any of the phases and voltage and current are not zero for this phase, check out following points:

  • Assure that A,B,C phases coincide in voltage and current.
  • Correct polarity? Reverse the current transformer placed at this phase.

Screen display

4.1.- Panel diagram;
BLUE JAY BJ192P-3 Three Phase Active Power Meter - Panel
diagram 4.2.- Display Summary

No. Display Explanation
1 Digital display module Three lines 4 digital LED show active power
2 Indicator of the data Unit K means thousand
3* Enter key For menu selection and confirmation
4* Menu key Used to open the menu and return to previous menu
5* Up and Down key Set the programming value

Note: Please see detail instructions of “*” items at “OPERATION MODE”

OPERATION MODE

The instrument has three displays. Every led will be on according to the parameter presently shown in screen.
When the 192-X is powered up, all the LED indicator will on, and meter start self- test, after some seconds, the meter is ready for operation and shows one of the available screens.
BLUE JAY BJ192P-3 Three Phase Active Power Meter -
icon1 Parameters on display can be switch by pressing the key or . LED on the right indicate the parameters shown on screen at any moment.
At programming display mode, press and to increase or decrease the value, pressing the key and or and the instantaneous at the same time, value can increase or decrease number “x10”.
Pressing the “Mani” key the can open the programming menu and return to previous menu.
Pressing the ”Enter” key ,you exit it with saving any modification that you might have done,  in menu operation press “Enter” key ,user can go to the next menu.

ETUP PROCEDURE

The SETUP procedure of the BJ192-X is performed by means of several SETUP options.
Once into the SETUP, use the keyboard to select different options and enter required variables:

  1. Password enter
  2. Input signal selection
  3. Communication preferences

BLUE JAY BJ192P-3 Three Phase Active Power Meter -
SETUP

Note:
The procedure above is for reference, not all series have the step 3 (communication preference), only the K series have this step. If you want the X series and D series have this function, please contact the Technical Service.

SAFETY CONSIDERATIONS

All installation specification described at the previous chapters named : INSTALLATION AND STARTUP, INSTALLATION MODES and SPECIFICATIONS.
Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. This instrument is factory-shipped at proper operation condition.

MAINTENANCE

The 192X does not require any special maintenance. No adjustment, maintenance or  repairing action should be done when the instrument open and powered on, should those actions are essential, high-qualified operators must perform them.
Before any adjustment, replacement, maintenance or repairing operation is carried out, the instrument must be disconnected from any power supply source.
When any protection failure is suspected to exist, the instrument must be immediately put our of service. The instrument’s design allows a quick replacement in case of any failure.

TECHNICAL SERVICE

For any inquiry about the instrument performance or whether any failure happens, contact to Blue Jay’s technical service.
Blue Jay – After-sales service
E-mail : [email protected]

Tel: +0086-023-67628702
Email: [email protected]
www.cqbluejay.com
Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals