Carrier TV-UCXP683T-V Expandable Universal Controller Owner’s Manual
- June 13, 2024
- Carrier
Table of Contents
Carrier TV-UCXP683T-V Expandable Universal Controller
Introductions
The TruVu™ Expandable Universal Controller is ideal for HVAC equipment control, advanced air quality control and most zone-level applications. The TV-UCXP683T-V features a built-in flow sensor, dual Ethernet ports with built- in fail-safe that supports direct connection or daisy chain topologies using BACnet/IP and 17 points of onboard control. Designed to operate in a wide range of environmental conditions, it is well suited for mechanical rooms, equipment boxes, or almost any other weather-tight location.
Application Features
- Versatile controller suitable for a variety of applications, including: small AHUs, fan coils, exhaust fans
- Standard library of control programs available for most unitary equipment and zone applications
- Supports Snap graphical programming software
- Supports Carrier communicating sensors, which are available in a variety of zone and equipment sensing combinations
- Supports Carrier TruVu touchscreen interfaces for managing and troubleshooting the connected equipment easily and for occupant engagement
- Supports live, visual displays of control logic, which uses real time operational data and aids in optimizing and troubleshooting system operations
- Supports 50 Modbus points for system integrations
Hardware Features
- Dual 10/100 Mbps, BACnet IP and IP addressing
- Supports home run, daisy chain and ring IP network topologies
- Capacitor-backed real-time clock keeps time in the event of power failure or network interruption for at least three days
- Integral airflow sensor
- I/O expander bus supports two TV-UCXP IO Expanders
- USB port for local device updates, hard-wired, and wireless service connections
- DIN rail or screw mounting
System Features
- Connects seamlessly to the i-Vu building automation system
Specifications
BACnet Conformance| Conforms to the BACnet Advanced Application
Controller (B-AAC) and BACnet Broadcast Management Device (B-BBMD) standard
device profiles, as defined in BACnet 135-2001 2012 Annex L Protocol Rev 14
---|---
Power| 24Vac +/- 15% , 50 – 60Hz, 55VA | 24Vdc +/- 10%, 20W. (80VA / 35W
if Act Net devices are connected)
Communication| BAS Primary port Serial port 1 I/O Bus port Rnet port Act
Net port USB Service port USB Expansion port Dual 10/100 BaseT Ethernet ports
with built-in fail safe, supporting direct connection or daisy chain topology
natively using BACnet/IP (non-routing) RS-485 port for communication with
third party devices (up to 50 points). Network at 9,600 to 115,200 bps.
Supports up to two TV-UCXP I/O expanders 12Vdc @ 260mA Supports the following:
Up to 5 ZS sensors (freely mix ZS zone, ZS duct, ZS immersion and ZS outdoor
sensors), iVu Equipment Touch, or TruVu ET Displays (external power required)
Supports up to 5 Act Net communicating devices such as the i-Vu Smart Valves
and Smart Damper Kit For TruVu ET Display support |configuration | wireless
service access | firmware updates and controller recovery via USB drive |
TruVu ET Displays For support of comm expansion devices (future)
Inputs| Universal Auxiliary Power 8 Universal Inputs configurable to any
of the following: Dry | Pulse Counting |Thermistor | 0-10 Vdc 24Vdc @ 100mA
total current capacity
Integral Airflow Sensor| Precision differential pressure sensor 0–2 in.
H2O, sensitive down to ±0.001 in. H2O. Barbed tapered airflow connections
accept 3/16 in. (4.75 mm) I.D. tubing. Allows for readings across the 0–2in.
H2O range, accurate to ±5% of full flow at 2 in. H2O
Outputs| Universal output Analog Output Digital output 1 Output
selectable to 0–10 Vdc (20 mA max), 12 Vdc 80 Hz PWM, or (Dry Contact) Rated
@24VAC 1 Amp 2 Analog Outputs 10Vdc @ 20mA max (D/A Resolution 12 bits) 6
Digital outputs (Dry Contact) Rated @24Vac/Vdc 1 Amp. Configured normally open
Memory| 4 GBs eMMC Flash memory and 256 MB DDR3 DRAM. User data is
archived to non-volatile flash memory when parameters are changed, every 90
seconds
Real Time Clock| Real-time clock keeps track of time in the event of a
power failure for at least 3 days
Compliance| United States: FCC compliant to Title CFR47, Part 15,
Subpart B, Class A; UL Listed, File E143900; CCN PAZX, UL 916, Energy
Management Equipment; ANZ: RCM Mark AS/NZS 61000-6-3; Canada: UL Listed File
E143900, CCN PAZX7, CAN/CSA C22.2 No. 205 Signal Equip., Industry Canada
Compliant ICES-003, Class A; CE Mark Compliant with 2014/30/EU, and RoHS
Compliant: 2015/863/EU; UKCA Mark compliant with Electromagnetic Compatibility
Regulations 2016 – Gov.UK and RoHS for Electrical and Electronic Equipment
2012.
Plastic Rating| Fire-retardant plastic ABS, UL94-5VA
Environmental| Operating Range: -22 to 158°F (-30 to 70°C), 10-95% RH,
non-condensing Storage: -40 to 158°F (-40 to 70°C), 10-95% RH, non-condens
Physical
Minimum panel depth: 2.75 in. (7 cm)
| Dimensions:
Overall A:
7.785 in. (19.77 cm) B: 4.89 in. (12.43 cm) Depth: 2.00 in. (5.09 cm) Weight:
1.6 lb. (0.82 kg)
Screw Mounting
C: 6.45 in (16.38 cm) (fully extended) D: 4.5 in. (11.43 cm)
supports up to
two I/O expanders
Customers Support
|
---|---
©2021 Carrier. All Rights Reserved. Cat. No. 11-808-857-01 Rev. 12/22
Manufacturer reserves the right to discontinue, or change at any time,
specifications or designs, without notice and without incurring obligations.
All trademarks and service marks referred herein are property of their
respective owners.
For more information, contact
your local Carrier Controls Expert.