USER’S MANUAL
SMART APP SINEWAVE UPS SERIES
PR750RT2UC
PRPR1000RT2
PR1500RT2UC
PR2000RT2UC
PR2200RT2UC
PR3000RT2UC| PR750RTXL2UC
PR1000RTXL2UC
PR1500RTXL2UC
PR2000RTXL2UC
PR2200RTXL2UC
PR3000RTXL2UC
---|---
K01-0001006-00
PRODUCT REGISTRATION
Thank you for purchasing a CyberPower product. Please take a few minutes to register your product at www.cyberpowersystems.com/registration. Registration certifies your product’s warranty, confirms your ownership in the event of a product loss or theft and entitles you to free technical support. Register your product now to receive the benefits of CyberPower ownership.
INTRODUCTIONS
The CyberPower Smart App Sinewave Uninterruptible Power Supply PR750RT2UC/
PR1000RT2UC/ PR1500RT2UC/ PR2000RT2UC/ PR2200RT2UC/ PR3000RT2UC/ PR750RTXL2UC/
PR1000RTXL2UC/ PR1500RTXL2UC/ PR2000RTXL2UC/ PR2200RTXL2UC/ PR3000RTXL2UC
features 2430 Joules of surge protection, provides battery backup during power
outages and is Active PFC compatible for safeguarding mission-critical
servers, telecom equipment, VoIP and internetworking hardware that require
seamless sine wave power. Its full Automatic Voltage Regulation (AVR)
boost/buck technology delivers a consistent and clean AC power, protecting
connected equipment and preventing costly business interruptions. This UPS is
GreenPower UPS™ Bypass circuitry patented to save on energy costs by reducing
energy consumption and heat buildup.
The UPS unit incorporates microprocessor-based full digital control and
includes PowerPanel® Business software providing the user unsurpassed
flexibility and control. An optional SNMP/HTTP Remote Management adapter
(RMCARD) supports remote management and control of the machine through a
standard web browser.
AUTOMATIC VOLTAGE REGULATOR (AVR)
The incoming utility power may be damaging to important data and hardware, but
with Automatic Voltage Regulation, the computer will not experience damaging
voltage levels. The AVR automatically increases low or decreases high voltage
to a safe and consistent output voltage.
CyberPower GreenPower UPS Technology
CyberPower’s patented GreenPower UPS with Bypass Technology are ENERGY STAR®
complainantensuring lower power consumption and energy costs compared to
conventional UPS models. Evenwhen utility power is normal, conventional UPS
models constantly pass power through a transformer. By contrast, under normal
conditions the advanced circuitry of a GreenPower UPS bypasses the
transformer. As a result, the power efficiency is significantly increased
while decreasing waste heat, using less energy, and reducing energy costs.
When an abnormal power condition occurs, the GreenPower UPS automatically runs
power through its transformer to regulate voltage and provide “safe” power.
Since utility power is normal over 88% of the time, the GreenPower UPS
operates primarily in its efficient bypass mode.
The GreenPower UPS is also manufactured in accordance with the Restriction on
Hazardous Substances (RoHS) directive making it one of the most
environmentally-friendly on the market today.
IMPORTANT SAFETY INSTRUCTIONS
(SAVE THESE INSTRUCTIONS)
This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please read and follow all instructions thoroughly before and during the installation and operation of the product.
CAUTION! The UPS must be connected to a grounded AC power outlet with
fuse or circuit breaker protection. DO NOT plug the UPS into an outlet that is
not grounded. If you need to de-energize this equipment, turn off and unplug
the UPS.
CAUTION! The battery can energize hazardous live parts inside even when
the AC input power is disconnected.
CAUTION! To prevent the risk of fire or electric shock, install in a
temperature and humidity controlled indoor area, free of conductive
contaminants. Please see specifications for acceptable temperature and
humidity range.
CAUTION! For pluggable equipment, the socket-outlet shall be installed
near the equipment and shall be easily accessible.
CAUTION! To reduce the risk of electric shock, do not remove the cover,
except to service the battery. There are no serviceable parts inside, except
for the battery.
CAUTION! To avoid electrical shock, turn off the unit and unplug it from
the AC power source before servicing the battery or installing a computer
component.
CAUTION! When installing the equipment, ensure that the sum of the
leakage current of the UPS and the connected equipment does not exceed 3.5mA.
CAUTION! Do not unplug the unit from AC Power during operation, as this
will invalidate the protective ground insulation.
CAUTION! To reduce the risk of fire, connect only to a circuit provided
with 20 amperes maximum branch circuit overcurrent protection in accordance
with the National Electric Code, ANSI/NFPA 70. (PR750RT2UC/ PR1000RT2UC/
PR1500RT2UC/ PR2000RT2UC/ PR750RTXL2UC/ PR1000RTXL2UC/ PR1500RTXL2UC/
PR2000RTXL2UC)
CAUTION! To reduce the risk of fire, connect only to a circuit provided
with 30 amperes maximum branch circuit overcurrent protection in accordance
with the National Electric Code, ANSI/NFPA 70. (PR2200RT2UC/ PR3000RT2UC/
PR2200RTXL2UC/ PR3000RTXL2UC)
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! DO NOT use in
any circumstance that would affect operation or safety of any life support
equipment, with any medical applications, or patient care.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire,
do not use with or near aquariums. Condensation from the aquarium can come in
contact with metal electrical contacts and cause the machine to short out.
CAUTION! DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO DIRECT
SUNLIGHT OR NEAR A STRONG HEAT SOURCE!
CAUTION! DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE HOUSING!
CAUTION! DO NOT USE THE UPS ON ANY TRANSPORTATION! To reduce the risk of
fire or electric shock, do not use the unit on any transportation such as
airplanes or ships. The effect of shock or vibration caused during transit and
the damp environment can cause the unit to short out.
CAUTION! Dispose of or recycle the UPS after the end of its life in
accordance with local regulations.
UNPACKING
When you receive the unit, the package should contain the following items:
PRODUCT OVERVIEW
BASIC CONFIGURATION
Front Panel
- Power Switch
- Toolless Battery Access Door
- LCD Module
- Front Panel Access Tabs
- Faceplate
Rear Panel
- Battery Backed and Surge Protected Outlet
- Output Circuit Breaker
- SNMP/HTTP Network Slot
- Cloud Monitoring (Ethernet Port)
- Input Circuit Breaker
- AC Inlet
- BM Port
- Dry Contact
- Serial Port
- USB Port
- EPO/ROO Port
- TVSS Screw
- Extended Battery Module Connector Socket
BM Port
Connection port for built-in battery management module on extended battery
module.
BASIC CONFIGURATION (continued)
INSTALLATION
The product is designed for tower installation and rack installation for
2-post rack and 4-post rack. Read and follow the procedures thoroughly before
and during your installation of the product.
The installation videos are available online. Scan the QR code below for
detailed information.
Preparation
CAUTION! It is strongly recommended to have an additional person assist
this installation process if the product is heavy.
CAUTION! It is strongly recommended that the 2-post rack be bolted to the
floor prior to the installation of the product.
- Remove all equipment connected to the product.
- Make sure the product is disconnected from AC power source.
- Remove internal batteries to reduce weight of the unit before the installation. Refer to BATTERY REPLACEMENT section for instructions.
Rack Installation for 2-post Rack
http://www.cyberpower.media/A39B81F8
- Attach the brackets with provided M5 flat head screws.
- Affix the product to the rack with suitable M5/M6 screws and cage nuts. (M5 trust head screws are provided with the product in the mechanical accessory box.)
INSTALLATION (continued)
Rack Installation for 4-post Rack
http://www.cyberpower.media/A1959C2D
- Use the provided M5 flat head screws to attach the brackets and provided M5 pan head screws for hanging brackets.
- Screw the hanging rails to the rack with provided M5 pan head screws and plastic washers.
- Lift the product upon the hanging rails and slide the unit into the rack. Affix the product to the rack with provided
M5 truss head screws. If handles are needed, affix them to the brackets with M4 flat head screws.
Note: The Rail Kit is included for selected models. See UNPACKING section. For other models, it is also available for purchase. Part number CP2RAIL02.
Tower Installation
http://www.cyberpower.media/25653BAE
- Attach the brackets to the baseplate with the provided M4 flat head screws.
- Remove the faceplate and rotate the LCD module, then re-install the faceplate.
- Screw the rubber feet with provided M4 round head screws and then put the UPS onto the assembled tower stand. You can also put the dust covers in the screw holes on the top side of the UPS to prevent dust from falling into the unit.
BASIC OPERATION
-
Properly install the UPS.
-
Connect equipment to the outlets on the rear panel of UPS.
-
Plug the UPS into a 2 pole, 3 wire grounded receptacle/ wall outlet.
-
Press the power switch on LCD module once. The display screen will light up and show “UPS On/Off” on the first line. Use the Up/Down button to select “On” or “Delay On” and then press the Enter button to turn on the UPS.
The display screen will show CyberPower in the first line and the UPS model in the second line. Then the Online or On Battery Indicator on the LCD module lights up, indicating the UPS is operating from utility or battery. -
To turn off the UPS, press the power switch on LCD module once. The display screen will light up and show “UPS On/Off” on the first line. Use the Up/Down button to select “Off” or “Delay Off” and then press the Enter button to turn off the UPS. The display screen will show “Goodbye” and all the indicators will be off.
IMPORTANT! For first time usage, plug your UPS into an AC outlet to disable
cold start protection. Otherwise, your UPS will not turn on.
IMPORTANT! Do not use an adapter, line conditioner, or other surge protection
devices between the wall outlet and the UPS. Use of such a device may impede
proper operation of the UPS.
Be aware of the following statements:
A. Your UPS may be used immediately upon receipt. However, charging the
battery for at least 12 hours is recommended to ensure the battery reaches its
maximum charge. Charge loss may occur during shipping and storage. To recharge
the battery, simply leave the unit plugged into an AC outlet. The unit will
charge in either the on or off state.
B. To maintain optimal battery charge, leave the UPS plugged into an AC outlet
at all times.
C. DO NOT plug a laser printer, copier, space heater, vacuum, paper shredder,
pumps or other large electrical device to the UPS. The power demands of these
devices will possibly overload and damage your UPS.
D. Always plug the UPS into a 2 pole, 3 wire grounded receptacle/ wall outlet.
Make sure the wall branch outlet is protected by a fuse or circuit breaker and
does not service equipment with large electrical demands, e.g. air
conditioner, refrigerator, copier, etc. Avoid using extension cords.
E. To prevent the risk of electric shock, follow the steps to ground the UPS:
(a) Connect a ground wire to the TVSS screw on the rear panel of UPS.
(b) Connect another side of the ground wire to the ground.
F. If your UPS freezes, you can do a hard reboot as below steps.
(a) Press and hold the power switch on the LCD module for around 15~20
seconds; the UPS will be forcibly shut down. All indicators, display screen,
and output will be off immediately.
(b) After an abnormal shutdown, the UPS restarts itself when it is powered by
utility. If the UPS does not restart automatically, slightly press the power
switch on LCD module once to wake up the UPS to perform the auto-restart
function.
When there is no utility, you need to follow below procedures to turn on the
UPS. Slightly press the power switch on LCD module once. The display screen
will light up and show “UPS On/Off” on the first line. Use the Up/Down button
to select “On” or “Delay On” and then press the Enter button to turn on the
UPS. The display screen will show CyberPower in the first line and the UPS
model in the second line. Then the On Battery Indicator on the LCD module
lights up, indicating the UPS is operating from battery.
Note: When the UPS is off, pressing and holding the power switch for
around 15~20 seconds cannot turn on the UPS even though the display screen
will light up for a few seconds. Follow above steps to correctly turn on the
product.
CLEANING AND MAINTENANCE
CAUTION! To reduce the risk of electric shock, do not remove the cover
except to service the battery. There are no user serviceable parts inside
except for the battery. For battery replacement, please refer to BATTERY
REPLACEMENT section.
CAUTION! Turn off the unit and unplug it from the AC power source before
cleaning.
CAUTION! Never immerse the unit in water or other liquids. Only use a
soft, slightly damp cloth to wipe the surface of the unit. Do not use a spray
directly to clean or disinfect the unit.
To store the product for an extended period, cover it and store with the
battery fully charged. While in storage, recharge the battery every 3 months
to ensure battery life.
OPERATION AND STORAGE ENVIRONMENT
To prevent risk of fire or electric shock, install or place the unit in a
temperature and humidity controlled indoor area, free of conductive
contaminants.
Operation | Temperature | 32°F – 104°F / 0°C – 40°C |
---|---|---|
Relative Humidity | 0% – 95% Non-condensing | |
Elevation | 0 – 9.843 feet / 0 – 3.000 meters | |
Storage | Temperature | 5°F – 113°F / -15°C – 45°C |
Relative Humidity | 0% – 95% Non-condensing | |
Elevation | 0 – 49.213 feet / 0 -15.000 meters |
NETWORK OPERATION
Local Monitoring
Connect either the USB cable or Serial cable to the corresponding port on the
UPS and on the computer with PowerPanel Business software installed.
PowerPanel Business software is available on our website. Please go to
www.cyberpowersystems.com/products/software/power-panel-
business for the free download.
Note: USB and Serial port cannot be used simultaneously. Serial port will
be disabled if the USB port is used.
Remote Monitoring
This product is equipped with a SNMP/HTTP network slot. If you would like to
control the UPS from a remote location, especially under a private network, a
CyberPower Remote Management Card (RMCARD) is required. For more information,
visit www.cyberpowersystems.com.
Cloud Monitoring
This product features an Ethernet port for Cloud Connection, which makes it
easy to monitor CyberPower UPS systems from anywhere. Follow below steps to
get your UPS on Cloud.
- Hardware installation: Connect the Cloud Monitoring (Ethernet Port) on the UPS rear panel to a wall jack or network switch using a suitable Ethernet cable.
| LED Indicators| Conditions
---|---|---
| Off| The UPS is not connected to the Network.
Link| On (Yellow)| The UPS is connected to the Network.
Tx/Rx| Off| The Cloud Monitoring (Ethernet Port) is not powered.
On (Green)| The Cloud Monitoring (Ethernet Port) is powered.
Flashing| – Receiving/transmitting data packet - Application installation: Install PowerPanel Cloud App on your smartphone and then launch the application. PowerPanel Cloud application is available for download on the Apple App Store or Google Play.
|
---|---
www.itms-apps://itunes.apple.com/app/apple- store/id1342462532?mt=8| https://play.google.com/store/apps/details?id=com.cyberpower.pppe - Sign up and login.
- Add a device in the PowerPanel Cloud App.
(a) Click “+” in the upper right corner of the homepage.
(b) Locate the “Add Device by QR Code” to add your Cloud UPS.
(c) Scan the QR Code on the top side of the UPS. If the QR Code scan was successful, click “Add” and name the device you are monitoring.
(d) After the setup is completed, you will see your device on the homepage.
(e) Wait till the UPS is successfully configured.
- Start monitoring your UPS!
In addition to the Mobile App, you can access the PowerPanel Cloud account via a web browser:
https://powerpanel.cyberpower.com. For more information, please refer to the PowerPanel Cloud User’s Manual.
PRODUCT ADVANCED SETTING
LCD OPERATION GUIDE
Display Interface
- Power Switch/Power On Indicator
- Online Indicator
- Fault/Warning Indicator
- On Battery Indicator
- Battery Fault Indicator
- Display Screen
- Menu Button
- Esc Button
- Up Button
- Down Button
- Enter Button
Basic Operation
Press Up/Down Button to scroll through the UPS status. Press Esc button to go
back to top.
Menu| | Item|
---|---|---|---
Status| •Operation Mode
Input Voltage Information
•Output Voltage Information| •Estimated Runtime
•Battery Information
•Load Information| •NCL Status
•UPS Temperature
– Date and Time
LCD Setting Guide
Press Menu Button to enter Setup Menu and use Up/Down Button to scroll through
menus. Press Enter Button to go into the selected menu and use the Up/Down
Button and Enter Button to select the setting item and to complete the
setting. Esc Button is pressed to exit the submenu and go back to previous
page.
Menu| | Item|
Basic Setup| •Utility Duality| •Sensitivity| Extended Battery Module Quantity’
‘Select models
Ambient Setup| •Eco Mode LED Brightness| •LCD Hibernation
•Cycling Display| Audible Alarm
Outlet Control| UPS Configuration| •NCL Configuration|
Test| Self Test| •Alarm Test|
Logs| •Event 1-10| |
About| •UPS Model Name
•UPS Serial Number
•Last Battery Change Date
•Next Battery Change Date| •UPS Firmware Version
•IP Address
•MAC ID
•Service Port Number| BM Status
UPS Battery Information
Advanced Setup| •Output Voltage
•Minimum Output Voltage
•Maximum Output Voltage
•Low Battery Threshold Battery Change Date| •Schedule Test
•Date and Time
•Power Meter Rest
•IP Access IP Address| Subnet Mask
Gateway
Firmware Update” Back to Default
-Only displayed in standby mode
Menu / Basic Setup
In order to better supply power to the connected equipment, it is recommended
to check settings in this menu before you start using your UPS.
Item Default | Option | Description |
---|---|---|
Utility Quality | Normal | •Good |
•Normal
•Poor| Select the voltage quality of the input utility power.
If Good is selected. the UPS will be more sensitive to power quality and go to
battery mode more often to supply the cleanest power to connected devices.
If Poor is selected. the UPS will tolerate more power fluctuations and go to
battery mode less often.
•(Customized)| ‘Customized” shows up when Maximum/Minimum Output Voltage has
been adjusted in Advanced Setup Menu or through software.
Sensitivity| Medium| •High
•Medium
•Low| Select the sensitivity level to power events for connected equipment.
If the connected equipment is highly sensitive to power events. select High:
the UPS will go to battery mode more often to provide the cleanest power.
If the connected equipment can tolerate more power events. select Low: the UPS
will go to battery mode less often.
Extended Battery
Module Quantity
Select models| 0| •0-10
•Auto-sensing| If Auto-sensing is selected. the UPS will change the numbers
automatically.
Menu / Ambient Setup
The settings in this menu affect the UPS display, alarm, and noise. Customize
your UPS to meet your needs.
LCD OPERATION GUIDE (continued)
Menu / Outlet Control
Use this menu to configure UPS outlet performance. Outlets are divided into
Critical (CL) and Non-Critical (NCL) outlets. Connect the mission critical
devices into Critical outlets and nonessential equipment into NCL outlets. If
equipment needs to be shut down or reboot in a specific order, plug the
equipment into separate outlet groups.
Enter the submenu “Config UPS” to configure the total output of the UPS,
including CL and NCL outlets. Enter “Config NCL” if you want to have
additional settings for NCL outlets, for example, cut off the power provision
to the nonessential equipment during a blackout to reserve runtime for mission
critical devices.
LCD OPERATION GUIDE (continued)
Menu / Test
This menu provides basic tests for users to check the current performance of
the UPS.
LCD OPERATION GUIDE (continued)
LCD OPERATION GUIDE (continued)
Fault Warning Display and Alarm
The following table shows the fault and warning indications of the UPS. The
warning message cycles when the UPS is still turned on. Refer to the error
code below and take necessary measures. After the UPS shuts down or is turned
off manually, the error message could disappear but the event records can be
found in the Log Menu. To safely check the logs, press the power switch once
and then press the Esc button to enter another operation mode – Standby Mode.
Press Menu button and go to Log Menu to do a check.
Note: When the UPS is in Standby Mode, it does not have output. All
indicators will not illuminate and only the display screen lights up when the
UPS is operated. To leave the Standby Mode, refer to BASIC OPERATION section
to turn on the UPS. Or you can disconnect the UPS from the AC power source,
wait for a minute, and then UPS will completely become off.
*Press any button to cancel the alarm.
EPO AND ROO CONFIGURATION
The Emergency Power Off (EPO) port is a safety feature that can be used to
immediately shut down the UPS and cut off its power supply to connected
equipment. It is necessary to manually press the power switch on the LCD
module to restart the UPS and reapply power to connected equipment.
The Remote On/Off (ROO) shares the same port with EPO and those two functions
can be used at the same time.
ROO is a remote power control function which allows users not only to power on
but also power off the UPS from a remote location.
Installation
-
Verify the UPS is off and unplugged.
-
The EPO/ROO interface is an IEC 60950 safety extra low voltage (SELV) circuit. Follow the appropriate circuit diagram below to wire the provided EPO cable to your EPO/ROO configuration. Connect isolated dry contacts and use ONLY latching switch.
-
After wiring, make sure the external EPO/ROO switch is not activated to enable UPS output.
-
Plug the UPS into an AC outlet and turn the UPS on via power switch on the LCD module.
-
Activate the external EPO/ROO switch to test the function. Check the status change of UPS from its LCD module.
-
For EPO user: De-activate the external EPO switch and restart the UPS via power switch on the LCD model.
For ROO user: Press the external ROO switch again to restart the UPS.
Restriction on ROO
A. ROO can only turn on the UPS when utility is available.
B. ROO becomes inactive if the UPS is shut down due to Fault, Low Battery, or
EPO; it is necessary to manually press the power switch on the LCD module to
restart the UPS and reapply power to connected equipment.
C. ROO is active only when UPS power status is the same as ROO circuit. If
they are different, manually adjust the external ROO switch to synchronize
current UPS status.
For instance, the UPS is turned off via power switch on the LCD module;
however, the ROO switch stays in “on” position, which means the contact is
closed. Users have to manually press the external ROO switch to “off”
position, making contact open, to reactivate the ROO, verifying the power
status shown on LCD module and ROO switch is on the same page. And then users
can press the external ROO switch again to turn on the UPS.
Power switch on the LCD module, software and external ROO switch can all turn on/off the UPS.
DRY CONTACT
This UPS offers users the solution for UPS status monitoring via two output
relays. Refer to Network Operation in this manual, verifying the UPS is
connected to a computer with PowerPanel Business software installed or is
equipped with RMCARD. Follow below circuit to wire your dry contact port and
choose your preferred monitoring status via those interfaces.
UPS status which can be monitored by dry contact is listed below:
UPS Status | UPS Conditions |
---|---|
Power Failure* | UPS detects utility failure. |
Battery Low* | Battery capacity is lower than threshold. |
Summary Alarm | UPS exits alarms due to Inverter Fault, Output Short, Over |
Temperature, Overload, Battery
Overcharge, Low Battery, Battery Disconnected, and Battery Defect.
UPS Fail| UPS has malfunctioned due to Inverter Fault, DC Power Fault, and
Over Temperature.
*Default settings of relay contacts are Power Failure and Battery Low (Normally Open).
Internal Circuit
Relay Status | UPS Status |
---|---|
Pin1 short to Pin5 | Battery Low |
Pin8 short to Pin5 | Power Failure |
Example Application
Supply 12VDC to the Common contact and connect LEDs to the DB9 port Pin1 and
Pin8. When UPS detects utility failure or when UPS battery capacity is lower
than threshold, the connected LEDs will illuminate.
BATTERY REPLACEMENT
Read and follow the important safety instructions before servicing the
batteries. Visit CyberPower official website
www.cyberpowersystems.com or contact your
dealer for more information on replacement batteries.
The battery replacement video is available online. Scan the QR code below for
detailed information.
CAUTION! RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE.
When replacing batteries, replace with the same number of the following
battery: CyberPower RB1250X4 for PR750RT2UC, CyberPower RB1270X4H for
R1000RT2UC/ PR750RTXL2UC/ PR1000RTXL2UC, CyberPower RB1290X4J for PR1500RT2UC/
PR2000RT2UC/ PR2200RT2UC/ PR3000RT2UC/ PR1500RTXL2UC/ PR2000RTXL2UC/
PR2200RTXL2UC/ PR3000RTXL2UC.
CAUTION! Risk of Energy Hazard, 12V, maximum 6 Ampere-hour battery.
(PR750RT2UC) CAUTION! Risk of Energy Hazard, 12V, maximum 9 Ampere-hour
battery. (PR1000RT2UC/ PR1500RT2UC/ PR2000RT2UC/ PR2200RT2UC/ PR3000RT2UC/
PR750RTXL2UC/ PR1000RTXL2UC/ PR1500RTXL2UC/ PR2000RTXL2UC/ PR2200RTXL2UC/
PR3000RTXL2UC)
CAUTION! The used batteries are considered hazardous waste and must be
disposed through recycling. Most retailers that sell lead-acid batteries
collect used batteries for recycling, as required by local regulations. Do not
dispose of batteries in a fire. The batteries may explode.
CAUTION! Do not open or mutilate batteries. Released material is harmful
to the skin and eyes. It may be toxic.
CAUTION! Do not replace batteries while the UPS is in battery mode.
CAUTION! When the battery pack is disconnected, the loads connected to
the UPS are not protected from power failure.
CAUTION! Do not use a damaged or deformed battery pack.
Take the following precautions before replacing the battery:
- Remove watches, rings, or other metal objects.
- Use tools with insulated handles.
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground.
CONTACT WITH ANY PART OF A GROUNDED BATTERY CAN RESULT IN ELECTRICAL
SHOCK. The likelihood of such shock can be reduced if such grounds are removed
during installation and maintenance (applicable to equipment and remote
battery supplies not having a grounded supply circuit).
Battery Replacement Procedure
http://www.cyberpower.media/E9E4F6B2
- Remove faceplate and unscrew the thumbscrews on battery cover and then open the battery cover. Note: Thumbscrews are designed fixed on the battery cover, do not remove them from the metal cover.
- Disconnect the battery and battery management module connector.
- Insert the new battery pack. Assemble the connectors, thumbscrews and faceplate. Recharge the unit for at least 12 hours to ensure the UPS performs expected runtime.
Reminder: Battery Change Date is optional setup information for users to record the installation date of battery pack.
It can be adjusted through LCD module in Advanced Setup Menu or through software.
TECHNICAL SPECIFICATIONS
*Refer below de-rating information for 100/110V systems:
PR1500RT2UC: 1200VA/1200W@100V, 1350VA/1350W@110V; PR2000RT2UC:
1600VA/1600W@100V, 1800VA/1800W@110V; PR3000RT2UC: 2400VA/2400W@100V,
2700VA/2700W@110V.
TECHNICAL SPECIFICATIONS (continued)
*Refer below de-rating information for 100/110V systems:
PR1500RTXL2UC: 1200VA/1200W@100V, 1350VA/1350W@110V; PR2000RTXL2UC:
1600VA/1600W@100V, 1800VA/1800W@110V; PR3000RTXL2UC: 2400VA/2400W@100V,
2700VA/2700W@110V.
TROUBLESHOOTING
Prblem | POssinle Cause | Solution |
---|
UPS does not provide
power to equipment.| Circuit breaker hat tripped due toan overload.| Turn the
uPS off and unplug at least one piece of equipment. Wan 10 seccods. reset the
circuit breaker and then turn the UPS on.
Batteries are discharged.| Recharge the UPS for at least 3 hour.
UPS has been damaged by a surge or spike.| Contact CyberPower for repair.
Non-critical outlets have turned off automatically due to an overload in
battery meek| NCL outlets will be turned on automatically as utility ‘
restored lb avoid recumng. check ‘Off on Overload’ setting in Outlet Control
Menu and usable the fund. c,
tars does not perform r • ccc ted runtime.| Batteries are not fully changed|
Recharge the batteries by leaving the UPS plugged tr
Batteries are degraded| Contact CyberPower about replacement batteries.
Ups does not recognize the correct quantity of Extended Battery
modules| Adjust the setting of Extended Battery Module Quantity on your UPS
to correct numbers Na LCD module. PowerPanel Business software or RMCARD
interface (If installed).
UPS does not perform
expected runtime.| UPS is connected t.
to an AC outlet not connect| The unit must be connected to a 100 -130V or 100
– 12W OUtlet. (See TECHNICAL SPECIFICATIONS section)
Batteries are worn out.| Contact CyberPower about replacement batteries.
Mechanicalproblem.| – – -tact CyberPower for repair.
Pan of hard reboot process has been performed| -..; oress of the power switch
to forcibly shut down the
”when It freezes. When the UPS is oft long press of
Dower switch to light up the display screen for a few-
ds. This does not turn on the UPS. Refer to BASIC
: RATION section to correctly turn on the UPS.
UPS cannot be turned on.| The serial cable or USB cable is not connected| , cc
t the cable to your UPS and computer. Use the s n lc that came with the unit
if your own
communication cable does not work.
The serial cable or USB cable is connected to the wrong or defected port.| Try
another port on the computer.
| IA’S It not providing battery Pew” Shut down the computer and turn the UPS
off. Wait 10 seconds and turn the UPS back on to reset the unit.
PowerPanel Business is
inactive.| The Battery Replacement Date has reached the recommended mamenence
period.| Perform a runtime estimation via Foy/L.0.6nel Business software to
verily battery capacity is sufficiem and acceptable.
if batteries have been recently replaced. reset the Battery Replacement Date
using PowerPanel Business software or RMCARD interface: you can also reset the
Battery Change Date in Advanced Setup Menu through LCD module.
“Fault” or “Error” message
is appearing on display
screen.| An internal malfunction may haveoccurred.| Please refer to Fault
Warning Display and Alarm in the LCD OPERATION GUIDE section. if the fault
persists take note and contact CyberPower for repay.
Additional troubleshooting information can be found at www.cyberpowersystems.com.
DISPOSAL
The Waste Electrical and Electronic Equipment (WEEE) Directive aims to
contribute to sustainable production and consumption by contributing to the
efficient use of resources and the retrieval of secondary raw materials
through re-use, recycling, and other forms of recovery. The symbol on this
product and/or its packaging indicates that the product must be disposed of
separately from ordinary household wastes at its end of life. Contact your
related WEEE management authority, local office, or your household waste
disposal service about information on the recycling drop off site.
BATTERY DISPOSAL
This product contains non-spillable lead acid batteries. The used batteries
are considered hazardous waste and must be disposed through recycling. Do not
dispose of used batteries with your ordinary household wastes. Dispose of the
batteries according to local regulations. Note: Most retailers that sell lead-
acid batteries collect used batteries for recycling, as required by local
regulations.
REGULATORY COMPLIANCE
FCC Compliance Statement (PR750RT2UC/ PR1000RT2UC/ PR1500RT2UC/ PR2000RT2UC/
PR750RTXL2UC/ PR1000RTXL2UC/ PR1500RTXL2UC/ PR2000RTXL2UC)
This device complies with part 15 of the FCC rules. Operation is subject to
the following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more
of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment to an outlet on a circuit different from that to which
the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help
Important: Changes or modifications not expressly approved by the party
responsible for compliance could void the user’s authority to operate the
equipment.
Canadian Compliance Statement (PR750RT2UC/ PR1000RT2UC/ PR1500RT2UC/
PR2000RT2UC/ PR750RTXL2UC/ PR1000RTXL2UC/ PR1500RTXL2UC/ PR2000RTXL2UC) CAN
ICES-3 (B)/NMB-3(B)
VCCI Compliance Statement (PR750RT2UC/ PR1000RT2UC/ PR1500RT2UC/ PR2000RT2UC/
PR750RTXL2UC/ PR1000RTXL2UC/ PR1500RTXL2UC/ PR2000RTXL2UC)
FCC Compliance Statement (PR2200RT2UC/ PR3000RT2UC/ PR2200RTXL2UC/
PR3000RTXL2UC)
This device complies with part 15 of the FCC rules. Operation is subject to
the following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference when theequipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
Important: Changes or modifications not expressly approved by the party
responsible for compliance could void the user’s authority to operate the
equipment.
Canadian Compliance Statement (PR2200RT2UC/ PR3000RT2UC/ PR2200RTXL2UC/
PR3000RTXL2UC) CAN ICES-3 (A)/NMB-3(A)
TECHNICAL SUPPORT
Visit our website at
www.cyberpowersystems.com/support
to access extensive service and in-depth support to gain the information you
need about power protection. Use the website links to find answers to common
questions, obtain troubleshooting tips, learn about our power management
software, view warranty details, and examine product literature. Our online,
self-service resources are available 24/7. CyberPower also offers assistance
from our expert team of sales, technical, and product support associates.
Our Technical Support team will be happy help you with technical questions
during business hours. Choose the ways described below you would like us to
help you.
- Live Chat: Monday – Sunday, 24 Hours. Visit www.cyberpowersystems.com/support.
- Submit a Form (recommended): Monday – Sunday, 24 Hours. Visit www.cyberpowersystems.com/support.
- Email: Monday – Sunday, 24 Hours. Contact tech@cyberpower.com.
- Call Toll Free: Monday – Friday, 24 Hours. Call 1-877-297-6937 (press 1).
Technical Support is available on our website.
Visit CyberPower at
www.cyberpowersystems.com to get more
information.
© 2022 Cyber Power Systems (USA), Inc. CyberPower®, the CyberPower logo and PowerPanel® are registered trademarks of Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks used are property of their respective owners.
References
- CyberPower UPS Systems, Battery Backup, PDUs, USB Surge Protectors
- Registration | CyberPower
- Support | CyberPower
- powerpanel.cyberpower.com
- CyberPower UPS Systems, Battery Backup, PDUs, USB Surge Protectors
- Registration | CyberPower
- Support | CyberPower
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>